Note If you are installing a redundant power supply in the Cisco AS5350XM universal gateway, you should attach spade terminals of the appropriate size to the stripped ends of the ground and input wires.
Step 4 Install the safety grounds (green wire) in the terminal block ground connectors and tighten the locking screws. Ensure that no bare wire is exposed.
Note For central office installations, we recommend using a green number 6 AWG copper ground wire with one end connected to reliable earth ground. The other end of the wire should be crimped onto the
Step 5 Insert the 48 VDC Return wires into the terminal block positive connectors (+) and tighten the locking screws. Ensure that no bare wire is exposed.
Caution Do not overtorque the terminal block contact screws. The recommended torque is 5
Step 6 Insert the
Step 7 Make sure that the power supply wires are secured to cable
Warning |
| After wiring the DC power supply, remove the tape from the circuit breaker switch handle and reinstate power by |
|
| moving the handle of the circuit breaker to the ON position. Statement 8 |
Step 8 |
|
|
Power up the universal gateway. The internal power supply fan should power up. | ||
|
|
|
6Power Up the Universal Gateway
Note The information in this document applies to the Cisco AS5350XM and Cisco AS5400XM universal gateways.
Checklist for Power Up
You are ready to power up the Cisco universal gateway if the following steps have been completed:
•The chassis is securely mounted.
•Power and interface cables are connected.
•Your PC terminal emulation program is configured for 9600 baud, 8 data bits, 1 stop bit, and no parity.
•You have selected passwords for access control.
•You have determined the IP addresses for the Ethernet and serial interfaces.
31