EMC DS-16B manual Installation Considerations, Standalone, Fiber Channel, Cable Connections

Page 24

Installation

Installation Considerations

The switch has optional mounting hardware to mount the switch in a standard 19-inch rack. If the switch has had its rubber mounting feet installed, they may need to be removed for a rack installation.

Standalone

The switch is shipped in its standalone configuration. Adhesive

 

rubber feet are supplied if the switch is surface mounted. Rubber feet

 

installation is required for proper or safe switch operation.

To install the adhesive rubber feet:

1.Clean the four depressions at each corner of the chassis bottom so that they are free of dust.

2.Remove the rubber feet from the sheet and place one in each depression.

3.Firmly press the rubber feet in place.

 

Fiber Channel

All network cable connections are to the switch’s front panel. All

 

Cable Connections

recommended cabling supports the switch’s 1.0625-Gbps transfer

 

 

 

rate, as shown in Table 2-1.

 

 

 

Table 2-1

Cabling Connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GBIC module

 

 

 

 

 

 

 

Maximum run

Optical

 

 

 

Cable type

Cable Specification

length

Wavelength

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SWL Fiber Optic

Duplex SC plug connectors

500 meters

780-860 m

 

 

 

 

 

Multimode fiber

1641 feet

without open fiber

 

 

 

 

 

50 mm core diameter

 

control (non-OFC)

 

 

 

 

 

 

 

 

 

 

 

 

125 mm cladding diameter duplex

 

 

 

 

 

 

 

cable

 

 

 

 

 

 

 

 

 

 

 

 

LWL Fiber

Duplex SC plug connectors

10 Kilometers

1270-1350 m

 

 

 

Optica

Single mode fiber

84480 feet

without open fiber

 

 

 

 

 

9 mm core diameter

 

control (non-OFC)

 

 

 

 

 

 

 

 

 

 

 

 

125 mm cladding diameter duplex

 

 

 

 

 

 

 

cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The switch is not designed to interoperate with devices using an Open Fibre

 

 

 

Control optical interface.

 

 

 

 

 

 

 

 

 

 

 

Departmental Switch Model DS-16B Hardware Reference Manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 24
Contents Departmental Switch Model DS-16B Hardware Reference ManualCopyright 2000 EMC Corporation. All rights reserved Departmental Switch Model DS-16B Hardware Reference Manual Trademark Information FCC Warning USA only Departmental Switch Model DS-16B Hardware Reference Manual Contents Chapter Switch Management Chapter Front Panel DiagnosticsAppendix a Specifications Appendix B Switch SupportAppendix C Error Messages Departmental Switch Model DS-16B Hardware Reference Manual Figures Figures Preface Related Publications Conventions Used in This Manual For Information On SeeCommand line arguments when used in text Examples of specific command entries that youArguments used in examples of command line Ask for Customer ServiceDepartmental Switch Model DS-16B Hardware Reference Manual Introduction Introduction System ComponentsDS-16B Switch FeaturesFollowing features IntroductionPerformance ManageabilityUnit may be managed in band or out of band via Telnet, via Ethernet portSystem Components Fabric OperatingSystem GBICsInstallation Unpacking the Switch Power Requirements Site ConsiderationsCooling RequirementsInstallation Considerations To install the adhesive rubber feetStandalone Fiber ChannelVerify Power-On Self EthernetConnection Test PostDepartmental Switch Model DS-16B Hardware Reference Manual Switch Management Comparing Switch Management Access Methods SESManaging Through Front Panel Buttons Control ButtonsSelect Menu Configuration Menu Activating MenuDisplay Front panel buttons activates the displayDS-16B Switch Menus Following menus are controlled using the front panel buttonsCommands Shows the front panel commands and their equivalentTelnet command Menu Front Panel Telnet Command DefaultUnset QuickLoop Port Configure QuickLoop Partner WWN Cmem Data Retention Test Configuration Menu Configuration menu SeeRatov Edtov Configuration menu Ethernet IP address 10To enter an IP address Ethernet Subnetmask noneTo update the Fibre Channel’s IP address Fibre Channel IP AddressFibre Channel IP address Fibre Channel SubnetmaskGateway address To enter the gateway addressDomain BBcreditRatov Pressing Enter while Ratov is selected, displays RatovEdtov Pressing Enter while Edtov is selected, displays EdtovOperating Mode Operating modes for the switch areFor the corresponding operating mode Operating modes are determined by the host adapter. The sixVC Link Ctl VC Class 2VC Class 3 VC MulticastReset to Default Accept? Yes No VC Priorities 0,1,2,2,2,2,3,3Frame Collection Method? Bundle/Piling Default values Allows you to select commandsOperation Menu Menu. Pressing Enter while the Operation Menu is selectedSwitch Online Operation Menu Switch OfflineOperation Menu Switch Online Operation Menu Port DisableOperation Menu Port Enable Port Enable Accept? Yes NoOperation Menu Reboot Reboot Accept? Yes NoSwitch Name sw15 Status MenuMenu is informational only you cannot make changes to Status Menu SeeBooted At Sat Sep 19 183420 Worldwide Name 1000606900eFirmware Version Current Date Mon Oct 21 102335Boot Prom Date Jun 12 084829 PST Powered Time 137 daysFlash Date Jun 12 084829 PST Up Time DayModule TypeL Port Throughput 75MB/sTemperature 36 34 37 36 3Temperature Sensor Approximate Locations on MotherboardError Log Selecting Error Log, then pressing Enter, displays Feb 12 084829 Err SENSOR-FAILED-3Test Menu LicensesLicenses 01f Front Panel Diagnostics Front Panel Diagnostics DiagnosticThis section gives a diagnostic overview and discusses OverviewDiagnostic Front FaultRemoving Power Panel DisplaysStatus and Activity Indicators IndicatorsFront Panel LED Port Color and flash speed of each port’s LED, as describedPower-On Diagnostics PostDiagnostic Tests Switch Offline Accept? Yes No Switch Online Accept? Yes NoSystem Memory Test at 0x1021d460 len Offline Tests Offline & Online TestsRelated error messages DIAG-MEMORY, DIAG-MEMSZ Related error messages DIAG-REGERR, DIAG-REGERRUNRSTIf the memory tests OK, the front panel displays 0x10199a10 len 13091456 ramTest passedRelated error messages DIAG-CMBISTRO, DIAG-CMBISRF Central MemTest passedRelated error messages DIAG-INIT, DIAG-PORTDIED Port Loopback Test AbortedSpinSilk Press any button to terminate Push Button Test To exit Specifications General Specifications Table A-1 shows the switch specificationsSpecifications Description Fabric Management Specifications Table A-2 shows Fabric management specificationsSafety Specifications Table A-3 Shows Safety specificationsSafety Specifications Switch’s primary operating environments are server roomsSpecification Value Optical PortPower Supply DimensionsRack Mount Dimensions Table Top DimensionsSwitch Support Switch Support Support ToolError Messages Error Message Formats Front PanelMessage Formats Feb 12To display error message from the front panel Diagnostic Error Message Formats Failed test ReplaceError Message Error Number Test Name Error NameNumbers DIAG-TIMEOUT DIAG-CMBISRTODIAG-CMBISRF DIAG-LCMEMTXDIAG-ERRSTAT Encin DIAG-ERRSTAT CRCDIAG-ERRSTAT Trunc DIAG-ERRSTAT 2LONGDIAG-ERRSTATENCIN DIAG-ERRSTATCRLDIAG-ERRSTATTRUNC DIAG-ERRSTAT2LONGDIAG-PORTSTOPPED Error Message Tables Message Description Probable Cause ActionCMI message received failed bad DIAG-ERRSTAT Asic failure Replace Err#1F26 Message Description Probable Cause FLASH, Badmirror RPC, SvcexitRPC, Svcreg FCIU, IUBAD, L, SFCIU, IUCOUNT, L, S FCPH, EXCHBAD, L, SFCPH, EXCHFREE, L, S MQ, QWRITE, L, MSYS BADPTR, Logerror SYS FLASHRD, LogerrorSYS FLASHWR, Logerror TIMERS, MSG,LOGWARNINGLogerror MCAST, NoparentlsrUCAST, RRTIM, Logcritical Sales and Service Locations International Sales LocationsDepartmental Switch Model DS-16B Hardware Reference Manual Departmental Switch Model DS-16B Hardware Reference Manual Index Index Departmental Switch Model DS-16B Hardware Reference Manual Departmental Switch Model DS-16B Hardware Reference Manual