DIP SWITCH GROUP B (Available on Select Models)
LOAD SHARING/EQUALIZE BATTERY CHARGE
Using a small tool, set the "Load Sharing" Configuration DIP Switches, #1 and #2 of Group B (located on the front panel of your APS; see Diagram 1, p. 33). DIP Switch #3, Group B should be kept in the "UP" position when you are not equalizing your batteries' charges. DIP Switch #4, Group B has no function.
• Load Sharing
(DIP Switches #1, Group B & #2, Group B)
Your APS features a
To reduce the chance of tripping this breaker, select APS models may be set to automatically limit their charger output to help keep the sum of their AC load and charger power within their line source circuit breakers' rating.
This charger limiting function has four settings, allowing you to choose less charger limiting for APS configurations with higher rated breakers. The figures below show how to set your DIP Switches to select how heavy a load can be placed on your APS before charger limiting begins. For suggested settings based on your APS model and breaker ratings, see specifications.
Load Sharing: Battery Charger Limiting Points
Charger limiting takes effect the moment any load is applied; charger output falls gradually from full output at no load to no output at full load.
Most Limiting
#1 & #2 Up
Charger limiting begins when the APS's load reaches 33% of the APS's load rating. Charger output falls gradually from full output at 33% of the APS's load rating to about 40% of full output at full load.
Less Limiting
#1 Down & #2 Up
Charger limiting begins when the APS's load reaches 66% of the APS's load rating. Charger output falls gradually from full output at 66% of the APS's load rating to about 40% of full output at full load.
Least Limiting
#1 Up & #2 Down
No charger limiting occurs at any load size. This is the factory de- fault setting.
No Limiting
#1 & #2 Down*
• Equalize Battery Charge
(DIP Switch #3, Group B)
This DIP Switch is momentarily engaged to begin the process of equalizing the internal resistance of your battery's cells. This can extend the useful life of certain types of batteries; consult with your battery's manufacturer to determine if your batteries could benefit from this process. The charge equalization process is automatic and once started can only be stopped by removing the input power.
SETTING PROCEDURE:
1)Move to "Equalize" (DOWN) position for three seconds.
2)Move to "Reset" (UP) position and leave it there.
CAUTION: Battery charge equalization should only be performed in strict accordance with the battery manufacturer's instructions and specifications.
CAUTION: Do not leave DIP switch #3 in the down position after beginning process.
| Battery Charge | Switch Position |
| Reset |
| ...........................................................Reset | Up* |
|
|
| Equalize | Down |
| Equalize |
6 | * Factory default settings. |
|
| |
|
|
|
9906058 230V APS |
|
|