Battery Connection (Standard)
1. Connect your APS's positive DC Terminal directly to a fuse.
UL requires that you install a recognized UL component fuse block and fuse within 18 inches of the battery. The fuse's rating must equal or exceed the Minimum DC Fuse Rating listed in your APS model's specifications on pages
2.Choose a battery configuration appropriate to your batteries.
•Single Battery Connection: Refer to Diagram 4, page 34. When using a single battery, its voltage must be equal to the voltage of your APS's Inverter Nominal Input Voltage (see specs).
•Parallel Battery Connection: Refer to Diagram 5, page 34. When using multiple batteries in parallel, each battery's voltage must be equal to the voltage of your APS's Inverter Nominal Input Voltage (see specs).
•Series Battery Connection: Refer to Diagram 6, page 34. When using multiple batteries in series, all batteries must be equal in voltage and amp hour capacity, and the sum of their voltages must be equal to the voltage of your APS's Inverter Nominal Input Voltage (see specs).
3.Use the SHORTEST and HEAVIEST GAUGE battery cabling.
Use #4 cabling for DC cable lengths up to 10 feet. Use #2 cabling for lengths up to 16 ft. Shorter and heavier gauge cabling limits DC voltage drop and allows for maximum transfer of current.*
*APS models are capable of delivering a much higher wattage output for brief periods of time. Wiring should be configured to handle this brief
Battery Connection (DC Vehicular)
APS systems may permanently mounted in a car, truck or boat and connected to draw power from the vehicle's battery. Note: An APS can ONLY be connected to vehicle batteries with voltage that matches the APS's Nominal DC
Caution: Never operate your APS from an alternator without a battery connected as shown in Diagrams 7 or 8, p. 35
AC Connection
Before AC connection, match the power requirements of your equipment with the power output of your APS to avoid overload.
When figuring the power requirements of your equipment, do not confuse "continuous" power ratings with "peak" power ratings. Electric motors require more power to turn on ("peak power") than they require to run continuously. "Peak" power ratings are usually 2 to 5 times "Continuous" ratings. Most electric motors require "peak power" only during initial powerup. The electric motors in equipment such as refrigerators and sump pumps, however, constantly turn on and off according to demand. These motors require "peak power" at multiple, unpredictable times during their operation.