Troubleshooting
Try these remedies for common APS problems before calling for help. Before returning your UPS for service, call Tripp Lite Customer Service at (773)
SYMPTOM | PROBLEMS | CORRECTIONS |
APS does not provide | APS not properly connected to | Connect APS to utility power. |
AC output (AC input present). | utility power. |
|
| Circuit breaker is tripped. | Reset circuit breaker. |
|
|
|
| APS shutdown due to excessive | Turn APS “OFF”. Wait 1 minute and |
| battery voltage, indicating possible | switch to “AUTO/REMOTE”. |
| charger failure. Line disconnected |
|
| to prevent permanent battery |
|
| damage. |
|
| APS is set to “OFF.” | Set APS to “AUTO/REMOTE” or |
|
|
|
|
|
|
APS does not provide | Circuit breaker is tripped. | Reset circuit breaker. |
AC output (AC input absent). |
|
|
|
|
|
| Operating Mode Switch is set | Set Operating Mode Switch to “AUTO/ |
| to “CHARGE ONLY.” | REMOTE.” |
|
|
|
| Load or High Temperature fault. | Turn APS “OFF.” Wait 1 minute. Remove |
|
| overload. Switch to “AUTO/REMOTE.” |
| Excessive battery discharge. | Check battery condition. |
|
|
|
APS will not charge the | Connected batteries are dead. | Check and replace old batteries. |
battery (AC input present). |
|
|
| Battery fuse* is blown. | Check and replace fuse. |
|
|
|
| Battery cabling* is loose or degraded. | Check and tighten or replace cabling. |
| APS charger failure. | Turn APS “OFF.” Wait 1 minute and |
|
| switch to “AUTO/REMOTE.” If |
|
| automatic shutdown occurs, call Tripp |
|
| Lite Customer Service. |
|
|
|
All APS Indicator Lights are | This is normal if the APS is set | — |
OFF (AC input absent). | to |
|
|
|
|
All APS Indicator Lights are | Excessive battery discharge. | Use an auxiliary charger* to raise |
OFF (AC input is present or |
| battery voltage. Check external battery |
absent). |
| connections and fuse. Automatically |
|
| resets when condition is cleared. |
|
|
|
All APS Battery Indicator | Excessive battery discharge. | Use an auxiliary charger* to raise |
Lights are slowly flashing. |
| battery voltage. Automatically resets |
|
| when condition is cleared. |
|
|
|
APS “LOW” Battery Light | Inverter shutdown because battery | Reset by cycling control switch to |
flashing. | voltage dropped too low for more | “OFF” position then to “AUTO/ |
| than 5 seconds. Protects battery | REMOTE.” |
| from permanent damage. |
|
|
|
|
All APS Battery Lights are | High battery voltage shutdown | Check all charging sources. Reset by |
rapidly flashing. | during Charge mode. | cycling control switch to “OFF” then to |
|
| “AUTO/REMOTE" or |
|
|
|
APS “LOAD” Indicator Light | Inverter overload caused by | Reset by reducing load and cycling control |
is rapidly flashing. | excessive load or short circuit. | switch to “OFF” position then to “AUTO/ |
| If sustained for more then 5 | REMOTE.” |
| seconds the Inverter is shut down. |
|
*User supplied |
|
|
|
| 13 |
9906058 230V APS |
|
|