Schneider Electric VW3A3310d user manual Reserving control, Configuring IO Scanning

Page 19

8. Configuration

8. 3. Reserving control

It is strongly recommended that control should be reserved for a single master device.

If control were not to be reserved for a master device (for example a PLC):

Any other Modbus TCP Ethernet client could send unwanted commands.

Other clients could use the 8 available TCP connections and prevent the master from having control.

UNINTENDED EQUIPMENT OPERATION

DANGER

Ensure that a valid address for the IP master device has been specified.

Failure to follow this instruction will result in death, serious injury, or equipment damage.

Use the [IP Master] (IPP) menu option to configure a network master device. If a valid IP address for a master device is not specified using this option, other Ethernet clients can saturate the TCP connections or send incorrect commands leading to unintended operation.

To configure this reservation, enter an IP address other than [0.0.0.0] (0) (0) (0) (0) in the [1.9 COMMUNICATION] (COM-)menu, [ETHERNET] (EtH-)submenu, [IP Master] submenu.

If control has been reserved:

Only the control word (CMd) written by the master with control will be accepted via IO Scanning or via Modbus TCP messaging. 2 TCP connections are reserved for this device. In this way, you avoid other TCP clients using all the available connections

(8 maximum) and the control master no longer being able to access the drive Modbus TCP server.

Other parameters written from other IP addresses are accepted (for example, adjustments or writing a setpoint). When control has been reserved and another device attempts to write the control word (CMd):

-via IO Scanning: The Modbus TCP connection for this client is immediately reinitialized.

-via Modbus TCP messaging: Control is denied.

If control has not been reserved ([IP Master] = [0.0.0.0] (0) (0) (0) (0)), control can come from any IP address.

8. 4. Configuring IO Scanning

Refer to the “IO Scanning Service” section.

The drive IO Scanning service can be enabled or disabled in the [1.9 - COMMUNICATION] (COM-)menu, [ETHERNET] (EtH-)submenu via parameter [IO Scan.activ.] (IOSA).

It is not possible to modify the assignment of the IO Scanning periodic variables using the display terminal (integrated or graphic).

To configure IO Scanning, use the standard web server or the PowerSuite software workshop.

19

Image 19
Contents Altivar 61 Page Table of contents Table of contents Please Note Important InformationHazard of Electric SHOCK, EXPLOSION, or ARC Flash Before you beginATV61 Installation ManualDocumentation structure Programming ManualPresentation IntroductionNotation Hardware description Hardware setupInstalling the card in the drive ReceiptExample of connection to an Ethernet network Connecting to the Ethernet networkCard RJ45 connector pinout Pin SignalEthernet network connection elements ENT Access to Ethernet menu via graphic display terminalAccess to Ethernet menu via the integrated display terminal Ethernet menuEthernet menu parameters IPF Code Description IPPIPP1 0.0.0 0 0 0 IPP2 IPP3 IPP4FdrE FdrAFdrS Fdrt List of functions to be configured ConfigurationStatic Addressing Dynamic Configuring IP addressesPower-up Initialization Assigning IP addressesIP card IPC1 IPC2 IPC3 IPC4 IP Mask IPM1 IPM2 IPM3 IPM4 Configuring BootpConfiguring FDR Entering IP addresses in the terminalReserving control Configuring IO ScanningParameter Value Comment Configuring the controlControl via Ethernet in I/O profile Control via Ethernet or the terminals in I/O profileControl via Ethernet or the terminals in CiA402 profile Control via Ethernet in CiA402 Drivecom profileProfile Separate Communication Configuring communication interruption managementCommunication monitoring Network managementRDY NET COM. Fault ManagementExternal Fault Drive responseFormat Range Terminal display Configuring monitored parametersSignalling LEDs DiagnosticsColor/ state Description Terminal Workshop Web server Available informationMonitoring the control Integrated displayCode Troubleshooting communication interruptionsEthernet communication interruption type Extended communication interruptionTroubleshooting the card TCP connections Software setupList of services supported Client Service Number of connectionsDrive Modbus servers Unit ID Modbus TCP server Accessible parametersModbus TCP server Modbus TCP framesIPM1.IPM2.IPM3.IPM4 Address Size Description Access Possible values, commentsEthernet card parameters IPC1.IPC2.IPC3.IPC4IPF1.IPF2.IPF3.IPF4 IPP1.IPP2.IPP3.IPP4FDR autosave Byte Meaning List of Modbus functions supportedRead Holding Registers 3 function Code Modbus name Description Size of data DecimalWrite Single Register 6 function Write Multiple Registers 16 = 16#10 function 16#17 Read/Write Multiple Registers 23 = 16#17 functionBytes Meaning With the VW3A3310d Ethernet card Read Device Identification 43 = 16#2B functionPeriodic variables IO Scanning serviceAddress table Address Description Default valueFDR service Local configuration IP assignment Save Downloading Downloaded configurationDrive parameters configuration First useCheck that the system is operational Save the drive configuration parameters in the FDR serverReplacing a drive Download the IP addressesLimitations Other commandsConfiguration file Periodic savingWeb server functions Home menu Monitoring menu Diagnostics menuSetup menu Security submenu Documentation menu Standard web serverApplets Username and password Access to the web serverHome menu Web server user interfaceMonitoring menu Altivar Viewer Data Viewer Diagnostics menu Altivar ChartEthernet Statistics Setup menuHttp password and Data write password pages Lcfg = No nO FDR AgentRestore Counter Local ConfigFile Error Error CodeIO Scanner Assigning the IO Scanning periodic variables Enabling IO ScanningMaster Time outImportant Notice MailDocumentation menu FTP server AccessDIR FunctionsFile system FTP functionality CommentFile name 32 characters max Downloading from the web serverPrinciple File managementWeb server Complete URL Bytes Standard web server resourcesType File name Size Complete URL Bytes Type File namePresentation Snmp agentTree structure Objects handled Objects Description Access Default valueATV Defining the hardware configuration Setup using PL7Bootp configuration Modbus Configuring Modbus messagingMulti Configuring periodic variables PLC Configuring the Dhcp address server FDR Setup using Concept Hardware configuration Traffic Cop Network configuration Setup using ProWORX NxTTCP/IP configuration O Scanner configuration Page 30072-452-37 2008-02