Schneider Electric VW3A3310d Enabling IO Scanning, Assigning the IO Scanning periodic variables

Page 59

14. Standard web server

b Enabling IO Scanning

Control by the IO Scanner is enabled if the “IoScanner” field is set to “Yes” and disabled if the “IoScanner” field is set to “No”.

The “IoScanner” field corresponds to the parameter [IO Scan.activ.] (IOSA).

UNINTENDED EQUIPMENT OPERATION

DANGER

Do not disable a drive's IO scanning support when the PLC is using the IO scanner to monitor/control client devices.

Do not modify the assignment of the periodic variables if the PLC is using IO scanning to monitor/control client devices.

Disabling a drive's IO Scanning or modifying the assignment of periodic variables can result in a loss of control via the network, and could result in unintended equipment operation.

Failure to follow these instructions will result in death, serious injury, or equipment damage.

Disabling a drive's IO Scanning or modifying the assignment of periodic variables can result in a loss of control via the network, and could result in unintended equipment operation.

Note: Disabling IO Scanning results in loss of control if a PLC is using the IO Scanner.

Before disabling IO Scanning, you must disable the time out (set the value to 0). However, communication monitoring remains active and the card will detect a communication interruption at the end of the period defined by the time out. In factory settings mode, a communication interruption will trigger a resettable stop condition [Com. network] (CnF) and initiate a freewheel stop.

Once the value in the “IoScanner” field has been modified, it may take a while to update the page, depending on the capacity of your computer and network.

The “IoScanner” field corresponds to the parameter [IO Scan.activ.] (IOSA).

b Assigning the IO Scanning periodic variables

Note: Modifying the assignment of the periodic variables can result in loss of control if a PLC is using the IO Scanner.

To modify the IO Scanning periodic variables, proceed as follows:

1Enter “No” in the “Io Scanner” field.

2Modify the assignment of periodic variables.

3Apply these modifications using the “Save” button.

4Enter “Yes” in the “Io Scanner” field.

Once the value in the “IoScanner” field has been set to “No”, it may take a while to update the page, depending on the capacity of your computer.

A drop down menu is used to modify the assignment of each of the periodic variables.

Click on the periodic variable whose assignment you wish to modify, then choose the code corresponding to the drive parameter to be assigned.

Modifications to “Output parameters” and/or “Input parameters” can be confirmed by clicking the “Save” button or canceled by clicking the “Abort” button.

Each time the “Save” button is pressed the address table will be saved to an EEPROM on the Ethernet card. The assignments are now saved, even if the power is turned off.

59

Image 59
Contents Altivar 61 Page Table of contents Table of contents Please Note Important InformationHazard of Electric SHOCK, EXPLOSION, or ARC Flash Before you beginATV61 Installation ManualDocumentation structure Programming ManualNotation IntroductionPresentation Hardware description Hardware setupInstalling the card in the drive ReceiptExample of connection to an Ethernet network Connecting to the Ethernet networkCard RJ45 connector pinout Pin SignalEthernet network connection elements ENT Access to Ethernet menu via graphic display terminalAccess to Ethernet menu via the integrated display terminal Ethernet menuEthernet menu parameters IPF Code Description IPPIPP1 0.0.0 0 0 0 IPP2 IPP3 IPP4FdrE FdrAFdrS FdrtList of functions to be configured ConfigurationStatic Addressing Dynamic Configuring IP addressesPower-up Initialization Assigning IP addressesIP card IPC1 IPC2 IPC3 IPC4 IP Mask IPM1 IPM2 IPM3 IPM4 Configuring BootpConfiguring FDR Entering IP addresses in the terminalReserving control Configuring IO ScanningParameter Value Comment Configuring the controlControl via Ethernet in I/O profile Control via Ethernet or the terminals in I/O profileControl via Ethernet or the terminals in CiA402 profile Control via Ethernet in CiA402 Drivecom profileProfile Separate Communication Configuring communication interruption managementCommunication monitoring Network managementRDY NET COM. Fault ManagementExternal Fault Drive responseFormat Range Terminal display Configuring monitored parametersColor/ state Description DiagnosticsSignalling LEDs Terminal Workshop Web server Available informationMonitoring the control Integrated displayCode Troubleshooting communication interruptionsEthernet communication interruption type Extended communication interruptionTroubleshooting the card TCP connections Software setupList of services supported Client Service Number of connectionsDrive Modbus servers Unit ID Modbus TCP server Accessible parametersModbus TCP server Modbus TCP framesIPM1.IPM2.IPM3.IPM4 Address Size Description Access Possible values, commentsEthernet card parameters IPC1.IPC2.IPC3.IPC4IPF1.IPF2.IPF3.IPF4 IPP1.IPP2.IPP3.IPP4FDR autosave Byte Meaning List of Modbus functions supportedRead Holding Registers 3 function Code Modbus name Description Size of data DecimalWrite Single Register 6 function Write Multiple Registers 16 = 16#10 function 16#17 Read/Write Multiple Registers 23 = 16#17 functionBytes Meaning With the VW3A3310d Ethernet card Read Device Identification 43 = 16#2B functionPeriodic variables IO Scanning serviceAddress table Address Description Default valueFDR service Local configuration IP assignment Save Downloading Downloaded configurationDrive parameters configuration First useCheck that the system is operational Save the drive configuration parameters in the FDR serverReplacing a drive Download the IP addressesLimitations Other commandsConfiguration file Periodic savingWeb server functions Home menu Monitoring menu Diagnostics menuSetup menu Security submenu Documentation menu Standard web serverApplets Username and password Access to the web serverMonitoring menu Web server user interfaceHome menu Altivar Viewer Data Viewer Diagnostics menu Altivar ChartEthernet Statistics Setup menuHttp password and Data write password pages Lcfg = No nO FDR AgentRestore Counter Local ConfigFile Error Error CodeIO Scanner Assigning the IO Scanning periodic variables Enabling IO ScanningMaster Time outImportant Notice MailDocumentation menu FTP server AccessDIR FunctionsFile system FTP functionality CommentFile name 32 characters max Downloading from the web serverPrinciple File managementWeb server Complete URL Bytes Standard web server resourcesType File name Size Complete URL Bytes Type File nameTree structure Snmp agentPresentation ATV Objects Description Access Default valueObjects handled Defining the hardware configuration Setup using PL7Bootp configuration Multi Configuring Modbus messagingModbus Configuring periodic variables PLC Configuring the Dhcp address server FDR Setup using Concept Hardware configuration Traffic Cop Network configuration Setup using ProWORX NxTTCP/IP configuration O Scanner configuration Page 30072-452-37 2008-02