Schneider Electric VW3A3310d Code Description IPP, IPP1 0.0.0 0 0 0 IPP2 IPP3, IPP4, Ipf, IPF4

Page 14

7. Ethernet menu

 

 

Code

 

Description

 

 

 

 

 

 

(IPP-)

 

b [IP Master]

 

 

 

 

(IPP1)

 

 

M [0.0.0.0] (0) (0) (0) (0)

 

 

 

 

(IPP2)

 

 

 

 

 

 

 

 

 

 

(IPP3)

 

 

IP address of the device that retains control

 

 

 

 

(IPP4)

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

 

 

Display (read-only) if the address is supplied by a DHCP server

 

 

 

 

 

 

 

Possible

 

• 0 to 255 for each of fields IPP1, IPP2, IPP3 and IPP4.

 

 

 

 

 

 

 

values:

 

• If the value is [0.0.0.0] (0) (0) (0) (0), writing of the control word (CMd) is accepted

 

 

 

 

 

 

 

 

 

 

by the Ethernet card regardless of which device has sent it.

 

 

 

 

 

 

 

 

 

If the value is other than [0.0.0.0] (0) (0) (0) (0) only the device which has the IP address

 

 

 

 

 

 

 

 

 

 

[IP Master] is authorized to write the control word (CMd).

 

 

 

 

 

 

 

 

 

Note: This configuration also affects the type of communication monitoring.

 

 

 

 

 

 

 

Default value:

 

[0.0.0.0] (0) (0) (0) (0)

 

 

 

 

(IPF-)

 

b [IP FDR]

 

 

 

 

 

 

(IPF1)

 

 

M [0.0.0.0] (0) (0) (0) (0)

 

 

 

 

(IPF2)

 

 

 

 

 

 

 

 

 

 

(IPF3)

 

 

IP address of the FDR server

 

 

 

 

(IPF4)

 

 

Type:

 

Display (read-only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Possible

 

• 0 to 255 for each of fields IPF1, IPF2, IPF3 and IPF4.

 

 

 

 

 

 

 

values:

 

• If the value is [0.0.0.0] (0) (0) (0) (0), there is no server.

 

 

 

 

 

 

 

Default value:

 

[0.0.0.0] (0) (0) (0) (0)

 

 

 

 

(ISA)

 

 

M [IO Scan.activ.]

 

 

 

 

 

 

 

 

 

 

Enable IO Scanner

 

 

 

 

 

 

 

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

Possible

 

[No] (nO): IO Scanner disabled.

 

 

 

 

 

 

 

values:

 

[Yes] (YES): IO Scanner enabled.

 

 

 

 

 

 

 

Default value:

 

[Yes] (YES)

 

 

 

 

(tOUt)

 

 

M [time out]

 

 

 

 

 

 

 

 

 

 

Ethernet communication monitoring time out

 

 

 

 

 

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

Possible

 

[0] (0): Monitoring disabled.

 

 

 

 

 

 

 

values:

 

[0.5 s] (0.5) to [60.0 s] (60.0): Time out value (unit: 0.1 s).

 

 

 

 

 

 

 

Default value:

 

[2.0 s] (2.0)

 

 

 

 

(FdrU)

 

 

M [FDR validation]

 

 

 

 

 

 

 

 

 

 

Enable FDR service

 

 

 

 

 

 

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

Possible

 

[No] (nO): FDR service disabled.

 

 

 

 

 

 

 

values:

 

[Yes] (YES): FDR service enabled.

 

 

 

 

 

 

 

Default value:

 

[Yes] (YES)

 

 

 

 

(LCFG)

 

 

M [FDR Local Config.]

 

 

 

 

 

 

 

Selection of local or server configuration

 

 

 

 

 

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

Possible

 

[No] (nO): The drive configuration is downloaded from an FDR server.

 

 

 

 

 

 

 

values:

 

[Yes] (YES): The drive configuration is local and saved in a FDR server.

 

 

 

 

 

 

 

Default value:

 

[No] (nO)

 

 

 

 

(FdrF)

 

 

M [FDR Error Mgt.]

 

 

 

 

 

 

 

 

 

 

Enable FDR file error detection

 

 

 

 

 

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

Possible

 

In the event of a problem with the FDR file (missing or invalid):

 

 

 

 

 

 

 

values:

 

[No] (nO): The Ethernet card does not trigger an [FDR fault] (Fdrd).

 

 

 

 

 

 

 

 

 

[Yes] (YES): The Ethernet card triggers an [FDR fault] (Fdrd).

 

 

 

 

 

 

 

Default value:

 

[Yes] (YES)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

Image 14
Contents Altivar 61 Page Table of contents Table of contents Important Information Please NoteBefore you begin Hazard of Electric SHOCK, EXPLOSION, or ARC FlashProgramming Manual Installation ManualDocumentation structure ATV61Notation IntroductionPresentation Receipt Hardware setupInstalling the card in the drive Hardware descriptionPin Signal Connecting to the Ethernet networkCard RJ45 connector pinout Example of connection to an Ethernet network Ethernet network connection elements Ethernet menu Access to Ethernet menu via graphic display terminalAccess to Ethernet menu via the integrated display terminal ENTEthernet menu parameters IPP4 Code Description IPPIPP1 0.0.0 0 0 0 IPP2 IPP3 IPFFdrt FdrAFdrS FdrEConfiguration List of functions to be configuredAssigning IP addresses Configuring IP addressesPower-up Initialization Static Addressing DynamicEntering IP addresses in the terminal Configuring BootpConfiguring FDR IP card IPC1 IPC2 IPC3 IPC4 IP Mask IPM1 IPM2 IPM3 IPM4Configuring IO Scanning Reserving controlControl via Ethernet or the terminals in I/O profile Configuring the controlControl via Ethernet in I/O profile Parameter Value CommentControl via Ethernet in CiA402 Drivecom profile Control via Ethernet or the terminals in CiA402 profileProfile Separate Network management Configuring communication interruption managementCommunication monitoring CommunicationDrive response COM. Fault ManagementExternal Fault RDY NETConfiguring monitored parameters Format Range Terminal displayColor/ state Description DiagnosticsSignalling LEDs Integrated display Available informationMonitoring the control Terminal Workshop Web serverExtended communication interruption Troubleshooting communication interruptionsEthernet communication interruption type CodeTroubleshooting the card Client Service Number of connections Software setupList of services supported TCP connectionsModbus TCP frames Unit ID Modbus TCP server Accessible parametersModbus TCP server Drive Modbus serversIPC1.IPC2.IPC3.IPC4 Address Size Description Access Possible values, commentsEthernet card parameters IPM1.IPM2.IPM3.IPM4IPP1.IPP2.IPP3.IPP4 IPF1.IPF2.IPF3.IPF4FDR autosave Code Modbus name Description Size of data Decimal List of Modbus functions supportedRead Holding Registers 3 function Byte MeaningWrite Single Register 6 function Write Multiple Registers 16 = 16#10 function Read/Write Multiple Registers 23 = 16#17 function 16#17Read Device Identification 43 = 16#2B function Bytes Meaning With the VW3A3310d Ethernet cardIO Scanning service Periodic variablesAddress Description Default value Address tableFDR service Local configuration First use Downloaded configurationDrive parameters configuration IP assignment Save DownloadingDownload the IP addresses Save the drive configuration parameters in the FDR serverReplacing a drive Check that the system is operationalPeriodic saving Other commandsConfiguration file LimitationsStandard web server Home menu Monitoring menu Diagnostics menuSetup menu Security submenu Documentation menu Web server functionsApplets Access to the web server Username and passwordMonitoring menu Web server user interfaceHome menu Altivar Viewer Data Viewer Altivar Chart Diagnostics menuSetup menu Ethernet StatisticsHttp password and Data write password pages FDR Agent Lcfg = No nOError Code Local ConfigFile Error Restore CounterIO Scanner Enabling IO Scanning Assigning the IO Scanning periodic variablesTime out MasterMail Important NoticeDocumentation menu Access FTP serverFTP functionality Comment FunctionsFile system DIRFile management Downloading from the web serverPrinciple File name 32 characters maxWeb server Type File name Standard web server resourcesType File name Size Complete URL Bytes Complete URL BytesTree structure Snmp agentPresentation ATV Objects Description Access Default valueObjects handled Setup using PL7 Defining the hardware configurationBootp configuration Multi Configuring Modbus messagingModbus Configuring periodic variables PLC Configuring the Dhcp address server FDR Setup using Concept Setup using ProWORX NxT Hardware configuration Traffic Cop Network configurationTCP/IP configuration O Scanner configuration Page 30072-452-37 2008-02