Schneider Electric VW3A3310d Ethernet card parameters, IPC1.IPC2.IPC3.IPC4, IPM1.IPM2.IPM3.IPM4

Page 32

11. Modbus TCP server

11. 3. Ethernet card parameters

Comments:

Parameters on 2 words are double words (low order in address word n, high order in address word n+1).

Parameters 60 019 to 60 043 and 60 066 to 60 068 can be accessed in both read and write mode. They can be reset using a write operation.

The current IP addresses (60006 to 60017) are the ones displayed on the terminal. The EEPROM IP addresses (60075 to 60079) are the ones used by the card.

Address

Size

Description

Access

Possible values, comments

 

(in words)

 

 

 

60 000

6

MAC address

R

00-80-F4-80-xx-yy

 

 

 

 

00: 60 000

 

 

 

 

80: 60 001

 

 

 

 

F4: 60 002

 

 

 

 

80: 60 003

 

 

 

 

xx: 60 004

 

 

 

 

yy: 60 005

 

 

 

 

 

60 006

4

Current value of IP Address

R/W

IPC1.IPC2.IPC3.IPC4

 

 

[IP card] (IPC-)

 

IPC1: 60 006

 

 

 

 

IPC2: 60 007

 

 

 

 

IPC3: 60 008

 

 

 

 

IPC4: 60 009

60 010

4

Current value of Subnet mask

R/W

IPM1.IPM2.IPM3.IPM4

 

 

[IP Mask] (IPM-)

 

IPM1: 60 010

 

 

 

 

IPM2: 60 011

 

 

 

 

IPM3: 60 012

 

 

 

 

IPM4: 60 013

 

 

 

 

 

60 014

4

Current value of Gateway Address

R/W

IPG1.IPG2.IPG3.IPG4

 

 

[IP Gate] (IPG-)

 

IPG1: 60 014

 

 

 

 

IPG2: 60 015

 

 

 

 

IPG3: 60 016

 

 

 

 

IPG4: 60 017

60 018

1

Transmission speed

R

= 0: Speed not defined

 

 

[Bit rate] (bdr)

 

= 10: 10 Mbps

 

 

 

 

= 100: 100 Mbps

60 019

2

OK transmission counter

R/W

 

60 021

1

Store-and-forward transmission counter

R/W

 

60 022

1

Late collision counter

R/W

 

60 023

1

Buffer (Tx) error counter

R/W

 

60 024

2

OK reception counter

R/W

 

60 026

1

CRC error counter

R/W

 

60 027

1

Frame error counter

R/W

 

60 028

1

Buffer (Rx) error counter

R/W

 

60 029

1

Collision counter

R/W

 

60 030

1

Multiple collision counter

R/W

 

60 031

1

OverRun counter

R/W

 

60 032

2

Sent Modbus TCP message counter

R/W

IO Scanning messages not included

60 034

2

Received Modbus TCP message counter

R/W

IO Scanning messages not included

60 036

1

Modbus TCP message error counter

R/W

IO Scanning messages not included

60 037

2

Sent IO Scanning message counter

R/W

 

60 039

2

Received IO Scanning message counter

R/W

 

60 041

1

IO Scanning message error counter

R/W

 

60 042

1

Active traffic (msg/s)

R/W

 

60 043

1

Max. traffic (msg/s)

R/W

 

60 044

1

Number of active TCP connections

R

8 maximum

32

Image 32
Contents Altivar 61 Page Table of contents Table of contents Important Information Please NoteBefore you begin Hazard of Electric SHOCK, EXPLOSION, or ARC FlashInstallation Manual Documentation structureProgramming Manual ATV61Notation IntroductionPresentation Hardware setup Installing the card in the driveReceipt Hardware descriptionConnecting to the Ethernet network Card RJ45 connector pinoutPin Signal Example of connection to an Ethernet networkEthernet network connection elements Access to Ethernet menu via graphic display terminal Access to Ethernet menu via the integrated display terminalEthernet menu ENTEthernet menu parameters Code Description IPP IPP1 0.0.0 0 0 0 IPP2 IPP3IPP4 IPFFdrA FdrSFdrt FdrEConfiguration List of functions to be configuredConfiguring IP addresses Power-up InitializationAssigning IP addresses Static Addressing DynamicConfiguring Bootp Configuring FDREntering IP addresses in the terminal IP card IPC1 IPC2 IPC3 IPC4 IP Mask IPM1 IPM2 IPM3 IPM4Configuring IO Scanning Reserving controlConfiguring the control Control via Ethernet in I/O profileControl via Ethernet or the terminals in I/O profile Parameter Value CommentControl via Ethernet in CiA402 Drivecom profile Control via Ethernet or the terminals in CiA402 profileProfile Separate Configuring communication interruption management Communication monitoringNetwork management CommunicationCOM. Fault Management External FaultDrive response RDY NETConfiguring monitored parameters Format Range Terminal displayColor/ state Description DiagnosticsSignalling LEDs Available information Monitoring the controlIntegrated display Terminal Workshop Web serverTroubleshooting communication interruptions Ethernet communication interruption typeExtended communication interruption CodeTroubleshooting the card Software setup List of services supportedClient Service Number of connections TCP connectionsUnit ID Modbus TCP server Accessible parameters Modbus TCP serverModbus TCP frames Drive Modbus serversAddress Size Description Access Possible values, comments Ethernet card parametersIPC1.IPC2.IPC3.IPC4 IPM1.IPM2.IPM3.IPM4IPP1.IPP2.IPP3.IPP4 IPF1.IPF2.IPF3.IPF4FDR autosave List of Modbus functions supported Read Holding Registers 3 functionCode Modbus name Description Size of data Decimal Byte MeaningWrite Single Register 6 function Write Multiple Registers 16 = 16#10 function Read/Write Multiple Registers 23 = 16#17 function 16#17Read Device Identification 43 = 16#2B function Bytes Meaning With the VW3A3310d Ethernet cardIO Scanning service Periodic variablesAddress Description Default value Address tableFDR service Local configuration Downloaded configuration Drive parameters configurationFirst use IP assignment Save DownloadingSave the drive configuration parameters in the FDR server Replacing a driveDownload the IP addresses Check that the system is operationalOther commands Configuration filePeriodic saving LimitationsHome menu Monitoring menu Diagnostics menu Setup menu Security submenu Documentation menuStandard web server Web server functionsApplets Access to the web server Username and passwordMonitoring menu Web server user interfaceHome menu Altivar Viewer Data Viewer Altivar Chart Diagnostics menuSetup menu Ethernet StatisticsHttp password and Data write password pages FDR Agent Lcfg = No nOLocal Config File ErrorError Code Restore CounterIO Scanner Enabling IO Scanning Assigning the IO Scanning periodic variablesTime out MasterMail Important NoticeDocumentation menu Access FTP serverFunctions File systemFTP functionality Comment DIRDownloading from the web server PrincipleFile management File name 32 characters maxWeb server Standard web server resources Type File name Size Complete URL BytesType File name Complete URL BytesTree structure Snmp agentPresentation ATV Objects Description Access Default valueObjects handled Setup using PL7 Defining the hardware configurationBootp configuration Multi Configuring Modbus messagingModbus Configuring periodic variables PLC Configuring the Dhcp address server FDR Setup using Concept Setup using ProWORX NxT Hardware configuration Traffic Cop Network configurationTCP/IP configuration O Scanner configuration Page 30072-452-37 2008-02