Schneider Electric VW3A3310d Local Config, File Error, AutoSave, Period, FDR State, Error Code

Page 57

14. Standard web server

Information

Corresponding

Description/Possible values

on the FDR

terminal display

 

 

Agent page

 

 

 

Validation

[FDR validation]

Enables the FDR function

 

(FdrU)

• Off = [No] (nO): FDR service disabled.

 

 

• On = [Yes] (YES): FDR service enabled.

Local Config

[FDR Local Config.]

Selection of local or server configuration

 

(LCFG)

• Off = [No] (nO): The drive configuration is downloaded from an FDR server.

 

 

On = [Yes] (YES): The drive configuration is local.

 

 

 

File Error

[FDR Error Mgt.]

Enables the FDR file error detection.

 

(FdrF)

• Off = [No] (nO): In the event of a problem with the FDR file (missing or invalid),

 

 

 

the Ethernet card does not trigger an Ethernet [FDR fault] (Fdrd).

 

 

• On = [Yes] (YES): In the event of a problem with the FDR file (missing or invalid),

 

 

 

the Ethernet card triggers an [FDR fault] (Fdrd).

 

 

 

AutoSave

[FDR autosave]

Enables periodic saving of the FDR service.

 

(FdrS)

• Off = [No] (nO): Automatic saving disabled.

 

 

• On = [Yes] (YES): Automatic saving enabled.

 

 

 

Period

[FDR t.autosave]

Interval for periodic saving of the FDR service.

 

(Fdrt)

2 min to 9999 min

FDR State

[FDR state]

FDR service state.

 

(FdrE)

• Idle = [IDLE] (IdLE): FDR service inactive.

 

 

• Initialization = [INIT] (InIt): Initialization of the current Ethernet card.

 

 

Configuration = [CONF] (COnF): Configuration of the current Ethernet card.

 

 

• Ready = [RDY] (rdY): Ethernet card ready.

 

 

Get Conf = [GET] (GEt): Downloads the current configuration from the FDR server.

 

 

Store Conf = [SET] (SEt): Saves the current configuration to the FDR server.

 

 

Apply Conf = [APP] (APP): Writes the FDR server configuration to the drive.

 

 

Operational = [OPE] (OPE): Operational.

 

 

• Unconfigured = [UCFG] (UCFG): FDR service interruption.

 

 

 

Error Code

[FDR fault]

Ethernet error code.

 

(Fdrd)

• = [0]: No communication interruption

 

 

Service Unavailable = The FDR server is not available.

 

 

• = [2]: The FDR configuration file is not compatible with the drive type

 

 

 

(example: the drive is not the same rating as that defined in the FDR file).

 

 

• = [3]: Error reading the FDR configuration file on the server.

 

 

• = [4]: Error writing the FDR configuration file to the server.

 

 

• = [7]: Time out for receipt of the FDR configuration file from the server.

 

 

• = [9]: Duplication of IP address.

 

 

• File Not Found = [12]: The FDR configuration file is missing.

 

 

• = [203]: Inconsistent hardware configuration.

Save Counter

Not accessible

Number of times the configuration has been saved to the FDR server.

 

 

This counter is incremented even if the drive configuration is identical to that of the server.

Restore Counter

Not accessible

Number of times the configuration has been downloaded from the FDR server.

 

 

This counter is not incremented if the drive configuration is identical to that of the server

 

 

(comparison of checksums).

Delete Counter

Not accessible

Number of times the configuration file has been deleted in the FDR server.

 

 

 

Save File

[FDR Action]

Command to save the configuration to the FDR server.

 

(FdrA)

Corresponds to the display terminal command: [SAVE] (SAUE).

Restore File

[FDR Action]

Command to download the configuration from the FDR server.

 

(FdrA)

Corresponds to the display terminal command: [REST] (rESt).

Delete File

[FDR Action]

Command to delete the configuration file in the FDR server.

 

(FdrA)

Corresponds to the display terminal command: [DEL] (dEL).

Reset counter

Not accessible

Command to reset the “Save counter”, “Restore counter” and “Delete counter” counters.

 

 

 

 

57

Image 57
Contents Altivar 61 Page Table of contents Table of contents Please Note Important InformationHazard of Electric SHOCK, EXPLOSION, or ARC Flash Before you beginDocumentation structure Installation ManualProgramming Manual ATV61Introduction PresentationNotation Installing the card in the drive Hardware setupReceipt Hardware descriptionCard RJ45 connector pinout Connecting to the Ethernet networkPin Signal Example of connection to an Ethernet networkEthernet network connection elements Access to Ethernet menu via the integrated display terminal Access to Ethernet menu via graphic display terminalEthernet menu ENTEthernet menu parameters IPP1 0.0.0 0 0 0 IPP2 IPP3 Code Description IPPIPP4 IPFFdrS FdrAFdrt FdrEList of functions to be configured ConfigurationPower-up Initialization Configuring IP addressesAssigning IP addresses Static Addressing DynamicConfiguring FDR Configuring BootpEntering IP addresses in the terminal IP card IPC1 IPC2 IPC3 IPC4 IP Mask IPM1 IPM2 IPM3 IPM4Reserving control Configuring IO ScanningControl via Ethernet in I/O profile Configuring the controlControl via Ethernet or the terminals in I/O profile Parameter Value CommentControl via Ethernet or the terminals in CiA402 profile Control via Ethernet in CiA402 Drivecom profileProfile Separate Communication monitoring Configuring communication interruption managementNetwork management CommunicationExternal Fault COM. Fault ManagementDrive response RDY NETFormat Range Terminal display Configuring monitored parametersDiagnostics Signalling LEDsColor/ state Description Monitoring the control Available informationIntegrated display Terminal Workshop Web serverEthernet communication interruption type Troubleshooting communication interruptionsExtended communication interruption CodeTroubleshooting the card List of services supported Software setupClient Service Number of connections TCP connectionsModbus TCP server Unit ID Modbus TCP server Accessible parametersModbus TCP frames Drive Modbus serversEthernet card parameters Address Size Description Access Possible values, commentsIPC1.IPC2.IPC3.IPC4 IPM1.IPM2.IPM3.IPM4IPF1.IPF2.IPF3.IPF4 IPP1.IPP2.IPP3.IPP4FDR autosave Read Holding Registers 3 function List of Modbus functions supportedCode Modbus name Description Size of data Decimal Byte MeaningWrite Single Register 6 function Write Multiple Registers 16 = 16#10 function 16#17 Read/Write Multiple Registers 23 = 16#17 functionBytes Meaning With the VW3A3310d Ethernet card Read Device Identification 43 = 16#2B functionPeriodic variables IO Scanning serviceAddress table Address Description Default valueFDR service Local configuration Drive parameters configuration Downloaded configurationFirst use IP assignment Save DownloadingReplacing a drive Save the drive configuration parameters in the FDR serverDownload the IP addresses Check that the system is operationalConfiguration file Other commandsPeriodic saving LimitationsSetup menu Security submenu Documentation menu Home menu Monitoring menu Diagnostics menuStandard web server Web server functionsApplets Username and password Access to the web serverWeb server user interface Home menuMonitoring menu Altivar Viewer Data Viewer Diagnostics menu Altivar ChartEthernet Statistics Setup menuHttp password and Data write password pages Lcfg = No nO FDR AgentFile Error Local ConfigError Code Restore CounterIO Scanner Assigning the IO Scanning periodic variables Enabling IO ScanningMaster Time outImportant Notice MailDocumentation menu FTP server AccessFile system FunctionsFTP functionality Comment DIRPrinciple Downloading from the web serverFile management File name 32 characters maxWeb server Type File name Size Complete URL Bytes Standard web server resourcesType File name Complete URL BytesSnmp agent PresentationTree structure Objects Description Access Default value Objects handledATV Defining the hardware configuration Setup using PL7Bootp configuration Configuring Modbus messaging ModbusMulti Configuring periodic variables PLC Configuring the Dhcp address server FDR Setup using Concept Hardware configuration Traffic Cop Network configuration Setup using ProWORX NxTTCP/IP configuration O Scanner configuration Page 30072-452-37 2008-02