Schneider Electric VW3A3310d user manual FdrA, FdrS, Fdrt, FdrE, Fdrd

Page 15

7. Ethernet menu

 

 

Code

 

Description

 

 

 

 

 

 

(FdrA)

 

M [FDR Action]

 

 

 

 

 

 

 

 

FDR service command

 

 

 

 

 

 

Type:

Command (read and write)

 

 

 

 

 

 

Possible

[IDLE] (IdLE): No command.

 

 

 

 

 

 

values:

[SAVE] (SAUE): Command: save.

 

 

 

 

 

 

 

[REST] (rESt): Command: download.

 

 

 

 

 

 

 

[DEL] (dEL): Command: delete.

 

 

 

 

 

 

 

The command remains displayed during the action then reverts to the value [IDLE] (IdLE).

 

 

 

 

 

 

Default value:

[IDLE] (IdLE)

 

 

 

 

(FdrS)

 

M [FDR autosave]

 

 

 

 

 

 

 

 

Enable periodic saving of the FDR service

 

 

 

 

 

 

Type:

Configuration (read and write)

 

 

 

 

 

 

Possible

[No] (nO): Automatic saving disabled.

 

 

 

 

 

 

values:

[Yes] (YES): Automatic saving enabled.

 

 

 

 

 

 

Default value:

[No] (nO)

 

 

 

 

(Fdrt)

 

M [FDR t.autosave]

 

 

 

 

 

 

 

 

Interval for periodic saving of the FDR service

 

 

 

 

 

 

Type:

Configuration (read and write)

 

 

 

 

 

 

Possible

[2] (2) to [9999] (9999): 2 min to 9999 min.

 

 

 

 

 

 

values:

 

 

 

 

 

 

 

 

Default value:

[10] (10)

 

 

 

 

(FdrE)

 

M [FDR state]

 

 

 

 

 

 

 

 

FDR service state

 

 

 

 

 

 

 

 

Type:

Display (read-only)

 

 

 

 

 

 

Possible

[IDLE] (IdLE): “Idle”.

 

 

 

 

 

 

values:

[INIT] (INIt): Initialization.

 

 

 

 

 

 

 

[CONF] (CONF): Configuration.

 

 

 

 

 

 

 

[RDY] (rdY): Ready.

 

 

 

 

 

 

 

[GET] (GEt): Download the current configuration.

 

 

 

 

 

 

 

[SET] (SEt): Save the current configuration.

 

 

 

 

 

 

 

[APP] (APP): Write the FDR server configuration to the drive.

 

 

 

 

 

 

 

[OPE] (OPE): Operational.

 

 

 

 

 

 

 

[UCFG] (UCFG): Not configured.

 

 

 

 

 

 

Default value:

[IDLE] (IdLE)

 

 

 

 

(Fdrd)

 

M [FDR Error Code]

 

 

 

 

 

 

 

FDR service status code

 

 

 

 

 

 

Type:

Display (read-only)

 

 

 

 

 

 

Possible

[0] (0): No communication interruption

 

 

 

 

 

 

values:

[2] (2): The FDR configuration file is not compatible with the drive type

 

 

 

 

 

 

 

 

(example: the drive is not the same rating as that defined in the FDR file).

 

 

 

 

 

 

 

[3] (3): Error reading the FDR configuration file on the server.

 

 

 

 

 

 

 

[4] (4): Error writing the FDR configuration file to the server.

 

 

 

 

 

 

 

[7] (7): Time-out for receipt of the FDR configuration file from the server.

 

 

 

 

 

 

 

[9] (9): Duplication of IP address.

 

 

 

 

 

 

 

[12] (12): The FDR configuration file is missing.

 

 

 

 

 

 

Default value:

[0] (0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

Image 15
Contents Altivar 61 Page Table of contents Table of contents Please Note Important InformationHazard of Electric SHOCK, EXPLOSION, or ARC Flash Before you beginATV61 Installation ManualDocumentation structure Programming ManualIntroduction PresentationNotation Hardware description Hardware setupInstalling the card in the drive ReceiptExample of connection to an Ethernet network Connecting to the Ethernet networkCard RJ45 connector pinout Pin SignalEthernet network connection elements ENT Access to Ethernet menu via graphic display terminalAccess to Ethernet menu via the integrated display terminal Ethernet menuEthernet menu parameters IPF Code Description IPPIPP1 0.0.0 0 0 0 IPP2 IPP3 IPP4FdrE FdrAFdrS FdrtList of functions to be configured ConfigurationStatic Addressing Dynamic Configuring IP addressesPower-up Initialization Assigning IP addressesIP card IPC1 IPC2 IPC3 IPC4 IP Mask IPM1 IPM2 IPM3 IPM4 Configuring BootpConfiguring FDR Entering IP addresses in the terminalReserving control Configuring IO ScanningParameter Value Comment Configuring the controlControl via Ethernet in I/O profile Control via Ethernet or the terminals in I/O profileControl via Ethernet or the terminals in CiA402 profile Control via Ethernet in CiA402 Drivecom profileProfile Separate Communication Configuring communication interruption managementCommunication monitoring Network managementRDY NET COM. Fault ManagementExternal Fault Drive responseFormat Range Terminal display Configuring monitored parametersDiagnostics Signalling LEDsColor/ state Description Terminal Workshop Web server Available informationMonitoring the control Integrated displayCode Troubleshooting communication interruptionsEthernet communication interruption type Extended communication interruptionTroubleshooting the card TCP connections Software setupList of services supported Client Service Number of connectionsDrive Modbus servers Unit ID Modbus TCP server Accessible parametersModbus TCP server Modbus TCP framesIPM1.IPM2.IPM3.IPM4 Address Size Description Access Possible values, commentsEthernet card parameters IPC1.IPC2.IPC3.IPC4IPF1.IPF2.IPF3.IPF4 IPP1.IPP2.IPP3.IPP4FDR autosave Byte Meaning List of Modbus functions supportedRead Holding Registers 3 function Code Modbus name Description Size of data DecimalWrite Single Register 6 function Write Multiple Registers 16 = 16#10 function 16#17 Read/Write Multiple Registers 23 = 16#17 functionBytes Meaning With the VW3A3310d Ethernet card Read Device Identification 43 = 16#2B functionPeriodic variables IO Scanning serviceAddress table Address Description Default valueFDR service Local configuration IP assignment Save Downloading Downloaded configurationDrive parameters configuration First useCheck that the system is operational Save the drive configuration parameters in the FDR serverReplacing a drive Download the IP addressesLimitations Other commandsConfiguration file Periodic savingWeb server functions Home menu Monitoring menu Diagnostics menuSetup menu Security submenu Documentation menu Standard web serverApplets Username and password Access to the web serverWeb server user interface Home menuMonitoring menu Altivar Viewer Data Viewer Diagnostics menu Altivar ChartEthernet Statistics Setup menuHttp password and Data write password pages Lcfg = No nO FDR AgentRestore Counter Local ConfigFile Error Error CodeIO Scanner Assigning the IO Scanning periodic variables Enabling IO ScanningMaster Time outImportant Notice MailDocumentation menu FTP server AccessDIR FunctionsFile system FTP functionality CommentFile name 32 characters max Downloading from the web serverPrinciple File managementWeb server Complete URL Bytes Standard web server resourcesType File name Size Complete URL Bytes Type File nameSnmp agent PresentationTree structure Objects Description Access Default value Objects handledATV Defining the hardware configuration Setup using PL7Bootp configuration Configuring Modbus messaging ModbusMulti Configuring periodic variables PLC Configuring the Dhcp address server FDR Setup using Concept Hardware configuration Traffic Cop Network configuration Setup using ProWORX NxTTCP/IP configuration O Scanner configuration Page 30072-452-37 2008-02