DeviceNet Remote I/O Communication Module RTU-DNET 
(12) Double click on 
(13) Set up the parameters in 
Item  | Function  | Default  | |
  | The sum of the length of the status word of   | 
  | |
Input IO  | the input data of the special module connected to it. The  | N/A  | |
status word of   | |||
Data Length  | |||
channel of the special module occupies 2 bytes. 8 points of  | 
  | ||
  | 
  | ||
  | the digital input are counted as 1 byte.  | 
  | |
  | The sum of the length of the control word of   | 
  | |
Output IO  | the output data of the special module connected to it. The  | 
  | |
control word of   | N/A  | ||
Data Length  | |||
channel of the special module occupies 2 bytes. 8 points of  | 
  | ||
  | 
  | ||
  | the digital output are counted as 1 byte.  | 
  | |
DIDO Input  | The digital input points shall be 8’s multiple. The number will  | N/A  | |
be regarded as 8 when it is less than 8 and regarded as 16  | |||
Points (X)  | |||
when it is bigger than 8 but less than 16.  | 
  | ||
  | 
  | ||
DIDO Output  | The digital output points shall be 8’s multiple. The number  | 
  | |
will be regarded as 8 when it is less than 8 and regarded as  | N/A  | ||
Points (Y)  | |||
16 when it is bigger than 8 but less than 16.  | 
  | ||
  | 
  | ||
AIAO Module  | The number of special modules connected to   | N/A  | |
Number  | Range: 0 ~ 8  | ||
  | |||
Diagnostic  | The interval when   | 5 (sec)  | |
Intervel Time  | Range: 1~ 65 secs  | ||
  | |||
IO Module  | How   | Alarm  | |
connected to it is offline. You can choose “Ignored”, "Alarm”  | |||
Offine Treatment  | |||
or “stop DeviceNet IO".  | 
  | ||
  | 
  | 
26  |