DeviceNet Remote I/O Communication Module RTU-DNET

2.3DeviceNet Connection Port

The connector is used on the connection to DeviceNet. Wire by using the connector enclosed with RTU-DNET.

PIN

Signal

Color

Content

 

1

V-

Black

0 VDC

5

2

CAN_L

Blue

Signal-

4

3

SHIELD

-

Shielded

3

2

4

CAN_H

White

Signal+

1

 

5

V+

Red

24 VDC

 

2.4 RUN/STOP Switch

RUN/STOP action

 

Explanation

RUN

STOP → RUN

1.

Re-detecting the extension module.

 

2.

Reading/writing the data in the extension

 

 

 

module.

 

RUN → STOP

Stop reading/writing the data in the extension

STOP

module.

 

 

 

2.5 Address Switch

The switch is used on setting up the node address of RTU-DNET on DeviceNet. Range: 00 ~ 63 (64 ~ 99 are forbidden).

Switch setting

Content

 

 

0 ~ 63

Valid DeviceNet node address

 

 

64 ~ 99

Invalid DeviceNet node address

 

 

5

4 3

2

 

1

0

 

4

5

 

3

 

2

 

1

0

 

6

7

8 9

6

7

8 9

Example: If you need to set the node address of RTU-DNET to 26, simply switch the corresponding switch of x101 to 2 and the corresponding switch of x100 to 6.

Note:

zPlease set up the node address when the power is switched off. After the setup is completed, re-power RTU-DNET.

zWhen RTU-DNET is operating, changing the setting of node address will be invalid.

zUse slotted screwdriver to rotate the switch carefully in case you scratch the switch.

2.6Function Switch

The function switches are for:

zSetting up data retention function (IN0)

zSetting up the baud rate of DeviceNet (DR0 ~ DR1)

DR1

DR0

Baud rate

OFF

OFF

125 kbps

 

 

 

OFF

ON

250 kbps

 

 

 

ON

OFF

500 kbps

ON

ON

Incorrect setting

 

 

 

6

DVP-PLC Application Manual

Image 8
Contents RTU-DNET Page Table of Contents LED Indicator & TROUBLE-SHOOTING Introduction CanDVP-08ST DVP-02DADVP-04DA DVP-04ADProduct Profile & Outline DVP-04TCDVP-04PT DVP-06XAPIN VDC CanlShield CanhIN1 Basic OperationIN0 How to Configure RTU-DNET TermsRTU-DNET Uint Interval time DeviceNet Remote I/O Communication Module RTU-DNET DeviceNet Remote I/O Communication Module RTU-DNET DeviceNet I/O Mapping Data DeviceNet Remote I/O Communication Module RTU-DNET Low byte of control word of RTU-DNET Byte RTU-DNET → DeviceNet master Master DeviceNet Remote I/O Communication Module RTU-DNET DeviceNet Remote I/O Communication Module RTU-DNET DeviceNet Remote I/O Communication Module RTU-DNET DeviceNet Remote I/O Communication Module RTU-DNET How to Construct a DeviceNet Network Using RTU-DNET DVPDNET-SLAscii COM1DVP-SV DeviceNet Remote I/O Communication Module RTU-DNET DeviceNet Remote I/O Communication Module RTU-DNET DeviceNet Remote I/O Communication Module RTU-DNET DeviceNet Remote I/O Communication Module RTU-DNET DeviceNet Remote I/O Communication Module RTU-DNET DVPDNET-SL → RTU-DNET RTU-DNET → DVPDNET-SLD6287H LED Indicator & Trouble-shooting Power LEDAppendix a DeviceNet Objects RTU-DNET Supports UsintWord UdintByte Macid UsintBool Get InstanceType Appendix B DeviceNet Objects Defined by RTU-DNET RTU-DNET DeviceNet Remote I/O Communication Module RTU-DNET DeviceNet Remote I/O Communication Module RTU-DNET Service code Implemented for Data type Claass Instance 0x0E