Mitsubishi 9800A Series technical manual Mccb Rectifier

Page 12

MITSUBISHI

ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-6

The Bypass Input circuit breaker (MCCB) for protection of the UPS and cables are field supplied and field installed. (See WARNING 2 on page 1-2)

B)Bypass Operation: Load Power supplied through each system UPS internal static bypass line.

FIGURE 1.2 Single Line Diagram - Bypass Operation: Load fed through Internal static bypass line.

CB

AC Bypass

Input

User supplied

MCCB

RECTIFIER

AC input

CB1

Static Transfer

Switch

CB3

INVERTER 52S

52C

Output

 

 

 

 

 

 

 

CB2

 

Power Flow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Not in Use

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery cabinet

UPS Module

Referring to Figure 1.2: The Internal Static Bypass line is a Hard wired line through CB3 and contactor 52S which supplies the critical load with unconditioned input power.

Each system UPS internal static bypass line will equally share the power supplied to the critical load.

The internal static bypass line will route power to the critical load while the UPS module is de-energized during Start-up and before the system is fully operational.

Bypass operation will occur In the event of a load overcurrent, with all system UPS transferring to bypass without interruption to the critical load.

The internal control system determines the operation of the two paths, with the load powered from the inverter being the normal operation.

MITSUBISHI ELECTRIC 9800A SERIES UPS

Image 12
Contents For parallel operation possible model only ALN-H0776Preface Table of Contents List of Tables List of Figures External I/F circuit PCB IOAU-04How to use this Manual Important Safety Instructions Retain These Instructions IntroductionMitsubishi Electric 9800A Series UPS General Mitsubishi Electric 9800A Series UPS Overview Mccb Rectifier Single Line Diagram Battery Operation CPM CUPS Parts Location 500kVA DUPS Parts Location 750kVA External contact signal terminal IOAU-04 Mitsubishi Electric 9800A Series UPS Specifications Battery AC OutputEnvironmental Rating of Contactors and Fuses Operator Controls and Indicators 540VBattery operation Battery OP. yellow LED Display Load on inverter Load on Inverter greenLoad on bypass Load on Bypass green Liquid Crystal Display MenuStart/Stop screen Figure Start/Stop screen Measurement Menu FigureSetup Menu Figure Input Power Failure 11 Main screenFault Indication Figure 13 Main screen Fault indicationExternal Signal Terminal Block TN1TN2 CB2 AXOutput Contacts for external alarm annunciation 16 Control Wiring for External ContactsInput Contacts for remote access of UPS Terminals 5 to 6 Battery Temp. High contact input IN3Terminals 3 to 4 Remote Inverter Stop input terminal IN2 Terminals 7 to 8 Power Demand Command contact input IN4 External communication connectorTransportation and Installation Installation ProcedureMitsubishi 9800A Series UPS Minimum clearance required for ventilationExternal Battery Supply Procedure for Cable ConnectionsElectric Owners / Technical Manual Mitsubishi 9800A Series UPS Procedure for Cable Connections for Parallel System Recommended Cable Sizes Crimp Type Compression Lug NumberUPS module BN,BPUPS module Input UPS module CabinetInput Cabinet Bypass Output Input A50,B50,C50 A40,B40,C40 External signal terminal IOAU-04 TN2 DC circuit breaker Input Input Cabinet UPS module Wall mounted DC breaker Bypass Battery AC Output Floor mounted DC breaker Input cabinet UPS module Auxiliary Rectifier Cabinet RYER-E Critical Load Cabinet Critical Load Cabinet IOAU-04UPS-1 AC Output UPS-2 AC OutputUPS-1 IOAU-04 TN2 UPS-2 UPS-n*1Start-up of UPS Shut-down Procedure Number B Shut-down ProcedureBypass Operation Procedure UPSNumber MMS Start-up Procedure Start-up of UPS-1UPS Fault Response to UPS FailureParts Replacement BatteryUPS Component Parts Fault Codes Contact Mitsubishi Electric Automation, Inc. atMitsubishi Igbt Fault a Inverter Voltage Activated Mitsubishi 9800A Series UPS Mitsubishi Electric Automation Inc 847