MITSUBISHI
ELECTRIC
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
TABLE 1.3 Detail of Specifications
Rated Output kVA | 100 |
| 150 |
| 225 |
| 300 |
| 375 |
| 500 |
| 750 |
Rated Output kW | 80 |
| 120 |
| 180 |
| 270 |
| 338 |
| 450 |
| 675 |
|
|
| AC | INPUT |
|
|
|
|
|
|
|
| |
Configuration | 3 phase, 3 wire |
|
|
|
|
|
|
|
|
| |||
Voltage | 277/480 V, 346/600 V | +15% to |
|
|
|
|
| ||||||
Frequency | 60 Hz |
|
|
|
|
|
|
|
|
|
|
| |
Reflected Current THD | 6% max. at 100% load; | 9% max. at 50% load |
|
|
| ||||||||
|
| STATIC BYPASS INPUT |
|
|
|
|
| ||||||
Configuration | 3 phase, 4 wire |
|
|
|
|
|
|
|
|
| |||
Voltage | 277/480 V, 346/600 V |
|
|
|
|
|
| ||||||
Frequency | 60 Hz |
|
|
|
|
|
|
|
|
|
|
| |
|
|
| BATTERY |
|
|
|
|
|
|
| |||
Type | Lead Acid |
|
|
|
|
|
|
|
|
|
|
| |
Ride Through | Application Specific |
|
|
|
|
|
|
|
|
| |||
Nominal Voltage | 480 Vdc |
|
|
|
|
|
|
|
|
|
|
| |
Minimum Voltage | 400 Vdc |
|
|
|
|
|
|
|
|
|
|
| |
Number of Cells | 240 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| AC OUTPUT |
|
|
|
|
|
|
| |||
Configuration | 3 phase, 4 wire |
|
|
|
|
|
|
|
|
| |||
Voltage | 277/480 V, 346/600 V |
|
|
|
|
|
|
|
|
| |||
Voltage Stability |
|
|
|
|
|
|
|
|
|
|
|
|
|
Frequency | 60 Hz |
|
|
|
|
|
|
|
|
|
|
| |
Frequency Stability |
|
|
|
|
|
|
| ||||||
Power Factor | 0.8 nominal |
|
|
|
| 0.9 nominal |
|
|
|
|
| ||
Power Factor range | 0.8 to 1.0 lagging (within output | kW rating) |
|
|
|
|
| ||||||
Voltage THD | 2% maximum THD at 100% Linear Load |
|
|
|
|
| |||||||
| 5% maximum THD at 100% |
|
|
|
|
| |||||||
Transient Response |
|
|
|
|
| ||||||||
|
|
|
|
|
| ||||||||
|
|
|
| ||||||||||
Transient Recovery | Less than 20ms |
|
|
|
|
|
|
|
|
| |||
Voltage Unbalance | 1% maximum at 100% unbalanced load |
|
|
|
|
| |||||||
Phase Displacement | 1deg. maximum at 100% load |
|
|
|
|
|
|
| |||||
Inverter Overload | 125% for 10 minutes; 150% for 1 minute |
|
|
|
|
| |||||||
System Overload | 1000% for 1 cycle |
|
| 500% for 1 cycle |
|
|
| ||||||
| (with bypass available) |
|
| (with bypass available) |
|
|
| ||||||
Bypass Overload | 125% for 10 minutes |
|
|
|
|
|
|
|
|
| |||
Withstand Rating | 65kA* |
|
|
|
|
|
| * : with optional fuse |
| ||||
|
|
| ENVIRONMENTAL |
|
|
|
|
| |||||
Cooling | Forced Air |
|
|
|
|
|
|
|
|
|
|
| |
Operating Temperature | 32゚F to 104゚F ( 0゚C to 40゚C). |
|
|
|
|
|
|
| |||||
| Recommended : 68゚F to 86゚F ( 20゚C to 30゚C) |
|
|
|
|
| |||||||
Relative Humidity | 5% ~ 95% Non Condensing |
|
|
|
|
|
|
| |||||
Altitude | 0 to 9000 feet No Derating |
|
|
|
|
|
|
| |||||
Location | Indoor (free from corrosive gases and dust) |
|
|
|
|
| |||||||
Paint Color | Munsell 5Y7/1 (Beige) |
|
|
|
|
|
|
|
|
|