9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-14

TABLE 1.3 Detail of Specifications

Rated Output kVA

100

 

150

 

225

 

300

 

375

 

500

 

750

Rated Output kW

80

 

120

 

180

 

270

 

338

 

450

 

675

 

 

 

AC

INPUT

 

 

 

 

 

 

 

 

Configuration

3 phase, 3 wire

 

 

 

 

 

 

 

 

 

Voltage

277/480 V, 346/600 V

+15% to -15%

 

 

 

 

 

Frequency

60 Hz +/-5%

 

 

 

 

 

 

 

 

 

 

 

Reflected Current THD

6% max. at 100% load;

9% max. at 50% load

 

 

 

 

 

STATIC BYPASS INPUT

 

 

 

 

 

Configuration

3 phase, 4 wire

 

 

 

 

 

 

 

 

 

Voltage

277/480 V, 346/600 V

+/-10%

 

 

 

 

 

 

Frequency

60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BATTERY

 

 

 

 

 

 

 

Type

Lead Acid

 

 

 

 

 

 

 

 

 

 

 

Ride Through

Application Specific

 

 

 

 

 

 

 

 

 

Nominal Voltage

480 Vdc

 

 

 

 

 

 

 

 

 

 

 

Minimum Voltage

400 Vdc

 

 

 

 

 

 

 

 

 

 

 

Number of Cells

240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC OUTPUT

 

 

 

 

 

 

 

Configuration

3 phase, 4 wire

 

 

 

 

 

 

 

 

 

Voltage

277/480 V, 346/600 V

 

 

 

 

 

 

 

 

 

Voltage Stability

+/-1%

 

 

 

 

 

 

 

 

 

 

 

 

Frequency

60 Hz

 

 

 

 

 

 

 

 

 

 

 

Frequency Stability

+/-0.05% in free running mode

 

 

 

 

 

 

 

Power Factor

0.8 nominal

 

 

 

 

0.9 nominal

 

 

 

 

 

Power Factor range

0.8 to 1.0 lagging (within output

kW rating)

 

 

 

 

 

Voltage THD

2% maximum THD at 100% Linear Load

 

 

 

 

 

 

5% maximum THD at 100% non-linear load

 

 

 

 

 

Transient Response

+/-2% maximum at 100% load step

 

 

 

 

 

 

+/-1% maximum at loss/return of AC power

 

 

 

 

 

 

+/-5% maximum at load transfer to/from static bypass

 

 

 

Transient Recovery

Less than 20ms

 

 

 

 

 

 

 

 

 

Voltage Unbalance

1% maximum at 100% unbalanced load

 

 

 

 

 

Phase Displacement

1deg. maximum at 100% load

 

 

 

 

 

 

 

Inverter Overload

125% for 10 minutes; 150% for 1 minute

 

 

 

 

 

System Overload

1000% for 1 cycle

 

 

500% for 1 cycle

 

 

 

 

(with bypass available)

 

 

(with bypass available)

 

 

 

Bypass Overload

125% for 10 minutes

 

 

 

 

 

 

 

 

 

Withstand Rating

65kA*

 

 

 

 

 

 

* : with optional fuse

 

 

 

 

ENVIRONMENTAL

 

 

 

 

 

Cooling

Forced Air

 

 

 

 

 

 

 

 

 

 

 

Operating Temperature

32F to 104F ( 0C to 40C).

 

 

 

 

 

 

 

 

Recommended : 68F to 86F ( 20C to 30C)

 

 

 

 

 

Relative Humidity

5% ~ 95% Non Condensing

 

 

 

 

 

 

 

Altitude

0 to 9000 feet No Derating

 

 

 

 

 

 

 

Location

Indoor (free from corrosive gases and dust)

 

 

 

 

 

Paint Color

Munsell 5Y7/1 (Beige)

 

 

 

 

 

 

 

 

 

MITSUBISHI ELECTRIC 9800A SERIES UPS

Image 20
Contents For parallel operation possible model only ALN-H0776Preface Table of Contents List of Tables List of Figures External I/F circuit PCB IOAU-04How to use this Manual Important Safety Instructions Retain These Instructions IntroductionMitsubishi Electric 9800A Series UPS General Mitsubishi Electric 9800A Series UPS Overview Mccb Rectifier Single Line Diagram Battery Operation CPM CUPS Parts Location 500kVA DUPS Parts Location 750kVA External contact signal terminal IOAU-04 Mitsubishi Electric 9800A Series UPS Specifications Environmental BatteryAC Output Rating of Contactors and Fuses Operator Controls and Indicators 540VLoad on bypass Load on Bypass green Battery operation Battery OP. yellowLED Display Load on inverter Load on Inverter green Start/Stop screen Figure Liquid Crystal DisplayMenu Start/Stop screen Measurement Menu FigureSetup Menu Figure Input Power Failure 11 Main screenFault Indication Figure 13 Main screen Fault indicationExternal Signal Terminal Block TN1TN2 CB2 AXOutput Contacts for external alarm annunciation 16 Control Wiring for External ContactsTerminals 3 to 4 Remote Inverter Stop input terminal IN2 Input Contacts for remote access of UPSTerminals 5 to 6 Battery Temp. High contact input IN3 Terminals 7 to 8 Power Demand Command contact input IN4 External communication connectorTransportation and Installation Installation ProcedureMitsubishi 9800A Series UPS Minimum clearance required for ventilationElectric Owners / Technical Manual External Battery SupplyProcedure for Cable Connections Mitsubishi 9800A Series UPS Procedure for Cable Connections for Parallel System Recommended Cable Sizes Crimp Type Compression Lug NumberUPS module BN,BPUPS module Input UPS module CabinetInput Cabinet Bypass Output Input A50,B50,C50 A40,B40,C40 External signal terminal IOAU-04 TN2 DC circuit breaker Input Input Cabinet UPS module Wall mounted DC breaker Bypass Battery AC Output Floor mounted DC breaker Input cabinet UPS module Auxiliary Rectifier Cabinet RYER-E Critical Load Cabinet Critical Load Cabinet IOAU-04UPS-1 AC Output UPS-2 AC OutputUPS-1 IOAU-04 TN2 UPS-2 UPS-n*1Start-up of UPS Shut-down Procedure Number B Shut-down ProcedureBypass Operation Procedure UPSNumber MMS Start-up Procedure Start-up of UPS-1UPS Fault Response to UPS FailureUPS Component Parts Parts ReplacementBattery Fault Codes Contact Mitsubishi Electric Automation, Inc. atMitsubishi Igbt Fault a Inverter Voltage Activated Mitsubishi 9800A Series UPS Mitsubishi Electric Automation Inc 847