9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-12

Description of Figures 1.4, 1.5, and 1.6:

1.CPM - Circuit protector for control power supply.

2.Grounding bar (G)

3.External contact signal terminal block (FIGURE 1.6) - Terminal block to connect contact signal input/output lines to and from the external devices. Refer to Figure 2.15 section 2.4 for details.

4.RS232C communication connector (FIGURE 1.6) - Refer to Figure 2.18 section 2.5 for details.

5.Inverter start switch - This switch is used to transfer the UPS from static bypass to inverter during maintenance purposes. Transfers will lock-out if the bypass voltage is more than +12%,-12% of nominal.

*Uninterrupted switching is made at the time of synchronous operation. Switching is impossible at the time of asynchronous operation.

6.“INVERTER STOP” switch - This switch is used to transfer the UPS from inverter to static bypass during maintenance purposes. Do not operate it under normal operation. Transfers will lock-out if the bypass voltage is more than +12%,-12% of nominal.

*Uninterrupted switching is made at the time of synchronous operation. Switching is impossible at the time of asynchronous operation.

7.“FAULT RESET” switch (FOR SERVICE PERSONNEL ONLY) - This switch resets errors resulting from alarm conditions. (Do not operate this switch while inverter and converter are in operation.)

8.Maintenance (Set) button (FOR SERVICE PERSONNEL ONLY) - This switch sets the UPS menu parameters.

9.“Test mode” switch (FOR SERVICE PERSONNEL ONLY) - This switch changes system operation to the test-mode. (This switch should not be operated by personnel other than an Authorized Service Engineer).

10.“BOOT” switch (FOR SERVICE PERSONNEL ONLY) - This switch boots the processor in the main control circuit resulting from alarm conditions. (Do not operate this switch while inverter and converter are in operation).

MITSUBISHI ELECTRIC 9800A SERIES UPS

Image 18
Contents For parallel operation possible model only ALN-H0776Preface Table of Contents List of Tables List of Figures External I/F circuit PCB IOAU-04How to use this Manual Important Safety Instructions Retain These Instructions IntroductionMitsubishi Electric 9800A Series UPS General Mitsubishi Electric 9800A Series UPS Overview Mccb Rectifier Single Line Diagram Battery Operation CPM CUPS Parts Location 500kVA DUPS Parts Location 750kVA External contact signal terminal IOAU-04 Mitsubishi Electric 9800A Series UPS Specifications Battery AC OutputEnvironmental Rating of Contactors and Fuses Operator Controls and Indicators 540VBattery operation Battery OP. yellow LED Display Load on inverter Load on Inverter greenLoad on bypass Load on Bypass green Liquid Crystal Display MenuStart/Stop screen Figure Start/Stop screen Measurement Menu FigureSetup Menu Figure Input Power Failure 11 Main screenFault Indication Figure 13 Main screen Fault indicationExternal Signal Terminal Block TN1TN2 CB2 AXOutput Contacts for external alarm annunciation 16 Control Wiring for External ContactsInput Contacts for remote access of UPS Terminals 5 to 6 Battery Temp. High contact input IN3Terminals 3 to 4 Remote Inverter Stop input terminal IN2 Terminals 7 to 8 Power Demand Command contact input IN4 External communication connectorMitsubishi 9800A Series UPS Transportation and InstallationInstallation Procedure Minimum clearance required for ventilationExternal Battery Supply Procedure for Cable ConnectionsElectric Owners / Technical Manual Mitsubishi 9800A Series UPS Procedure for Cable Connections for Parallel System Recommended Cable Sizes Crimp Type Compression Lug NumberUPS module BN,BPUPS module Input UPS module CabinetInput Cabinet Bypass Output Input A50,B50,C50 A40,B40,C40 External signal terminal IOAU-04 TN2 DC circuit breaker Input Input Cabinet UPS module Wall mounted DC breaker Bypass Battery AC Output Floor mounted DC breaker Input cabinet UPS module Auxiliary Rectifier Cabinet RYER-E Critical Load Cabinet UPS-1 AC Output Critical Load CabinetIOAU-04 UPS-2 AC OutputUPS-1 IOAU-04 TN2 UPS-2 UPS-n*1Start-up of UPS Shut-down Procedure Number B Shut-down ProcedureBypass Operation Procedure UPSNumber MMS Start-up Procedure Start-up of UPS-1UPS Fault Response to UPS FailureParts Replacement BatteryUPS Component Parts Fault Codes Contact Mitsubishi Electric Automation, Inc. atMitsubishi Igbt Fault a Inverter Voltage Activated Mitsubishi 9800A Series UPS Mitsubishi Electric Automation Inc 847