MITSUBISHI
ELECTRIC
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
Description of Figures 1.4, 1.5, and 1.6:
1.CPM - Circuit protector for control power supply.
2.Grounding bar (G)
3.External contact signal terminal block (FIGURE 1.6) - Terminal block to connect contact signal input/output lines to and from the external devices. Refer to Figure 2.15 section 2.4 for details.
4.RS232C communication connector (FIGURE 1.6) - Refer to Figure 2.18 section 2.5 for details.
5.Inverter start switch - This switch is used to transfer the UPS from static bypass to inverter during maintenance purposes. Transfers will
*Uninterrupted switching is made at the time of synchronous operation. Switching is impossible at the time of asynchronous operation.
6.“INVERTER STOP” switch - This switch is used to transfer the UPS from inverter to static bypass during maintenance purposes. Do not operate it under normal operation. Transfers will
*Uninterrupted switching is made at the time of synchronous operation. Switching is impossible at the time of asynchronous operation.
7.“FAULT RESET” switch (FOR SERVICE PERSONNEL ONLY) - This switch resets errors resulting from alarm conditions. (Do not operate this switch while inverter and converter are in operation.)
8.Maintenance (Set) button (FOR SERVICE PERSONNEL ONLY) - This switch sets the UPS menu parameters.
9.“Test mode” switch (FOR SERVICE PERSONNEL ONLY) - This switch changes system operation to the
10.“BOOT” switch (FOR SERVICE PERSONNEL ONLY) - This switch boots the processor in the main control circuit resulting from alarm conditions. (Do not operate this switch while inverter and converter are in operation).