Mitsubishi 9800A Series technical manual Number MMS Start-up Procedure, Start-up of UPS-1

Page 60

MITSUBISHI

ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

3-27

D)MMS Start-up Procedure

a)Verify that Critical Load Cabinet (CLC) Circuit Breaker SMB is closed.

b)Verify that CLC System Output Circuit Breaker 52L is open

c)Verify that CLC UPS Circuit Breakers 52L1, 52L2…and 52Ln are closed.

Start-up of UPS-1

1.Verify that Control Circuit Breakers (CPM) is closed.

(When Inverter is stopped, the Control Circuit Breaker is not normally opened)

2.The pre-charging cycle will begin and Input Contactor (CB1) will close automatically.

3.Close Battery Disconnect Circuit Breaker (CB2).

4.The inverter can now be started.

Note: When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter start operation can only be performed remotely. If local inverter start operation is required (at the UPS), select "LOCAL" in "Remote/Local" selection in setup page. Select “LOCAL” mode for the purpose of this start up procedure.

5.On the LCD panel, select “START/STOP MENU” and press the “START” key.

6.The Inverter will start within 5 seconds. Start up is complete.

Start-up of next UPS

1.The next UPS can be started in the same way as UPS-1.

2.When all UPS in MMS are started, the MMS system UPSs will simultaneously transfer from UPS MMS Bypass Operation to UPS MMS inverter Operation.

3.Verify there are no alarms on each UPS LCD and CLC LCD (if available)

Any steps to verify correct UPS MMS Inverter Operation.

Transfer from UPS MMS Inverter Operation To UPS MMS Bypass Operation

1.Transfer MMS system to UPS MMS Bypass Operation on CLC LCD (if available) or Transfer each UPS to bypass individually

Transfer of Load From Maintenance Bypass To inverter

1.Verify UPS MMS system is in UPS MMS Bypass Operation.

2.Transfer load from CLC Maintenance Bypass Circuit Breaker (SMB) to system Output Circuit Breaker (52L) per MMS CLC Maintenance Mode Interlock Operating Procedure, Part B.

3.Transfer from UPS MMS Bypass Operation to UPS MMS Inverter Operation from CLC LCD “System Bypass Operation Screens” if available or by starting each Individual UPS from UPS LCD, select “START/STOP MENU” and press “START” key.

4.After all UPS are ready to transfer to inverter all UPSs will simultaneously transfer from internal bypass to inverter.

MITSUBISHI ELECTRIC 9800A SERIES UPS

Image 60
Contents For parallel operation possible model only ALN-H0776Preface Table of Contents List of Tables List of Figures External I/F circuit PCB IOAU-04How to use this Manual Important Safety Instructions Retain These Instructions IntroductionMitsubishi Electric 9800A Series UPS General Mitsubishi Electric 9800A Series UPS Overview Mccb Rectifier Single Line Diagram Battery Operation CPM CUPS Parts Location 500kVA DUPS Parts Location 750kVA External contact signal terminal IOAU-04 Mitsubishi Electric 9800A Series UPS Specifications Battery AC OutputEnvironmental Rating of Contactors and Fuses Operator Controls and Indicators 540VBattery operation Battery OP. yellow LED Display Load on inverter Load on Inverter greenLoad on bypass Load on Bypass green Liquid Crystal Display MenuStart/Stop screen Figure Start/Stop screen Measurement Menu FigureSetup Menu Figure Input Power Failure 11 Main screenFault Indication Figure 13 Main screen Fault indicationExternal Signal Terminal Block TN1TN2 CB2 AXOutput Contacts for external alarm annunciation 16 Control Wiring for External ContactsInput Contacts for remote access of UPS Terminals 5 to 6 Battery Temp. High contact input IN3Terminals 3 to 4 Remote Inverter Stop input terminal IN2 Terminals 7 to 8 Power Demand Command contact input IN4 External communication connectorTransportation and Installation Installation ProcedureMitsubishi 9800A Series UPS Minimum clearance required for ventilationExternal Battery Supply Procedure for Cable ConnectionsElectric Owners / Technical Manual Mitsubishi 9800A Series UPS Procedure for Cable Connections for Parallel System Recommended Cable Sizes Crimp Type Compression Lug NumberUPS module BN,BPUPS module Input UPS module CabinetInput Cabinet Bypass Output Input A50,B50,C50 A40,B40,C40 External signal terminal IOAU-04 TN2 DC circuit breaker Input Input Cabinet UPS module Wall mounted DC breaker Bypass Battery AC Output Floor mounted DC breaker Input cabinet UPS module Auxiliary Rectifier Cabinet RYER-E Critical Load Cabinet Critical Load Cabinet IOAU-04UPS-1 AC Output UPS-2 AC OutputUPS-1 IOAU-04 TN2 UPS-2 UPS-n*1Start-up of UPS Shut-down Procedure Number B Shut-down ProcedureBypass Operation Procedure UPSNumber MMS Start-up Procedure Start-up of UPS-1UPS Fault Response to UPS FailureParts Replacement BatteryUPS Component Parts Fault Codes Contact Mitsubishi Electric Automation, Inc. atMitsubishi Igbt Fault a Inverter Voltage Activated Mitsubishi 9800A Series UPS Mitsubishi Electric Automation Inc 847