MITSUBISHI |
| 9800A SERIES UPS |
| Page Number: | |||||
ELECTRIC | OWNERS / TECHNICAL MANUAL |
|
| ||||||
|
|
|
|
|
|
|
|
| |
UF166 | IGBT FAULT (A) |
| IGBT module (A) overcurrent |
| CALL SERVICE | [2] | Major | Lit on | |
|
| ENGINEER | |||||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
UF167 | IGBT FAULT (B) |
| IGBT module (B) overcurrent |
| CALL SERVICE | [2] | Major | Lit on | |
|
| ENGINEER | |||||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
UF168 | IGBT FAULT (C) |
| IGBT module (C) overcurrent |
| CALL SERVICE | [2] | Major | Lit on | |
|
| ENGINEER | |||||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
UF201 | INVERTER |
| Output overvoltage during inverter | CALL SERVICE | [2] | Major | Lit on | ||
OVERVOLTAGE |
| power supply (+ 15%) |
| ENGINEER | |||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| ||
UF202 | INVERTER |
| Output low voltage during inverter | CALL SERVICE | [2] | Major | Lit on | ||
UNDERVOLTAGE |
| supply |
| ENGINEER | |||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| |
UF203 | INVERTER |
| Inverter output overcurrent |
| CALL SERVICE | [2] | Major | Lit on | |
OVERCURRENT |
|
| ENGINEER | ||||||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| |
UP204 | OUTPUT CIRCUIT |
| Cross current fell out of 30% |
| CALL SERVICE | [2] | Major | Lit on | |
ABNORMAL |
|
| ENGINEER | ||||||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| |
UF209 | 52C ABNORMAL |
| 52C not turned ON |
| CALL SERVICE | [2] | Major | Lit on | |
|
| ENGINEER | |||||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
UF210 | 52C ABNORMAL |
| 52C not turned OFF |
| CALL SERVICE | [2] | Major | Lit on | |
|
| ENGINEER | |||||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
UF213 | INV. OR CONV. |
| Overheating of main circuit parts | CALL SERVICE | [2] | Major | Lit on | ||
OVERTEMPERATURE | ENGINEER | ||||||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| ||
UF214 | COOLING FAN |
| Abnormality of cooling fan inside | CALL SERVICE | [2] | Major | Lit on | ||
ABNORMAL |
| panel |
| ENGINEER | |||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| ||
UF255 | 52C ABNORMAL |
| 52C turned OFF during inverter | CALL SERVICE | [1] | Minor | Flicker | ||
| power supply |
| ENGINEER | ||||||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| ||
UF256 | OUTPUT VOLTAGE |
| Inverter output voltage fell out of | CALL SERVICE | [1] | Minor | Flicker | ||
ABNORMAL |
| +/- 5% |
| ENGINEER | |||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| ||
UF257 | 52C ABNORMAL |
| 52C not turned OFF when manual | CALL SERVICE | [1] | Minor | Flicker | ||
| transfer |
| ENGINEER | ||||||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| ||
UF258 | LOAD ABNORMAL |
| More than 4 overcurrents for 10 | CHECK LOAD | [1] | Minor | Flicker | ||
| minutes |
| |||||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
UF259 | Output voltage bus |
| Inverter output voltage bus |
| CALL SERVICE | [1] | Minor | Flicker | |
abnormal |
| abnormality |
| ENGINEER | |||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| |
|
|
| After UA810 occurred, Bypass |
|
|
|
|
| |
UF260 | LOAD SHORT |
| Abnormal occurred within 1 |
| CHECK LOAD | [1] | Minor | Flicker | |
|
|
| second. | (#1) |
|
|
|
| |
|
|
|
|
|
|
|
| ||
UF301 | UPS CONTROL CIRCUIT | Control microcomputer |
| CALL SERVICE | [2] | Major | Lit on | ||
ERROR |
| abnormality |
| ENGINEER | |||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| ||
UF302 | UPS CONTROL CIRCUIT | Control microcomputer |
| CALL SERVICE | [2] | Major | Lit on | ||
ERROR |
| abnormality |
| ENGINEER | |||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| ||
UF303 | UPS CONTROL CIRCUIT | Control microcomputer |
| CALL SERVICE | [2] | Major | Lit on | ||
ERROR |
| abnormality |
| ENGINEER | |||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| ||
UF304 | UPS CONTROL CIRCUIT | Parallel control circuit abnormality | CALL SERVICE | [2] | Major | Lit on | |||
ERROR |
| ENGINEER | |||||||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
MITSUBISHI ELECTRIC 9800A SERIES UPS