Mitsubishi 9800A Series technical manual Output Contacts for external alarm annunciation

Page 31

MITSUBISHI

ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

2-10

A)Output Contacts (for external alarm annunciation)

Output contacts consist of form Adry type contacts. Rated capacity of all output contacts is NEC Class2 (30Vdc/1Adc). All dry contacts should be operated at their rated values or lower. Figure 2.16 illustrates a typical installation. The external relay can also be a lamp, LED, computer, etc.

FIGURE 2.16 Control Wiring for External Contacts

UPS Cabinet

Terminal

Relay

ContactTerminal

External to UPS Cabinet

Relay

Coil

NEC Class 2 Power Source

User supplied

Details of output alarm contacts : TN1

Terminals 1 to 2, 3 to 4 "UPS failure" contact

Activated when a major fault has occurred with the system. Terminals 5 to 6, 7 to 8 "Load on Bypass" contact (OUT1)

Activated when the power is supplied from the static bypass input. Terminals 9 to 10, 11 to 12 "Load on Inverter" contact (OUT2)

Activated when the power is supplied by the inverter. Terminals 13 to 14, 15 to 16 "Battery Operation" contact (OUT3)

Activated when the battery is operating following an AC power failure. Terminals 17 to 18, 19 to 20 "Rectifier Operation" contact (OUT4)

Activated when the rectifier is operating.

Terminals 21 to 22, 23 to 24 "Battery Low Voltage" contact (OUT5)

Activated when the battery voltage drops below discharge end voltage level during inverter operation (i.e. During AC fail condition).

Terminals 25 to 26, 27 to 28 "Overload" contact (OUT6) Activated when an overload has occurred to the system.

Terminals 29 through 40 "Spare" contact (OUT7 through OUT9)

MITSUBISHI ELECTRIC 9800A SERIES UPS

Image 31
Contents ALN-H0776 For parallel operation possible model onlyPreface Table of Contents List of Tables External I/F circuit PCB IOAU-04 List of FiguresHow to use this Manual Introduction Important Safety Instructions Retain These InstructionsMitsubishi Electric 9800A Series UPS General Mitsubishi Electric 9800A Series UPS Overview Mccb Rectifier Single Line Diagram Battery Operation CPM CUPS Parts Location 500kVA DUPS Parts Location 750kVA External contact signal terminal IOAU-04 Mitsubishi Electric 9800A Series UPS Specifications AC Output BatteryEnvironmental Rating of Contactors and Fuses 540V Operator Controls and IndicatorsLED Display Load on inverter Load on Inverter green Battery operation Battery OP. yellowLoad on bypass Load on Bypass green Menu Liquid Crystal DisplayStart/Stop screen Figure Measurement Menu Figure Start/Stop screenSetup Menu Figure 11 Main screen Input Power Failure13 Main screen Fault indication Fault Indication FigureTN1 External Signal Terminal BlockCB2 AX TN216 Control Wiring for External Contacts Output Contacts for external alarm annunciationTerminals 5 to 6 Battery Temp. High contact input IN3 Input Contacts for remote access of UPSTerminals 3 to 4 Remote Inverter Stop input terminal IN2 External communication connector Terminals 7 to 8 Power Demand Command contact input IN4Minimum clearance required for ventilation Transportation and InstallationInstallation Procedure Mitsubishi 9800A Series UPSProcedure for Cable Connections External Battery SupplyElectric Owners / Technical Manual Mitsubishi 9800A Series UPS Procedure for Cable Connections for Parallel System Recommended Cable Sizes Number Crimp Type Compression LugBN,BP UPS moduleUPS module Cabinet Input UPS moduleInput Cabinet Bypass Output Input A50,B50,C50 A40,B40,C40 External signal terminal IOAU-04 TN2 DC circuit breaker Input Input Cabinet UPS module Wall mounted DC breaker Bypass Battery AC Output Floor mounted DC breaker Input cabinet UPS module Auxiliary Rectifier Cabinet RYER-E Critical Load Cabinet UPS-2 AC Output Critical Load CabinetIOAU-04 UPS-1 AC OutputUPS-n*1 UPS-1 IOAU-04 TN2 UPS-2Start-up of UPS B Shut-down Procedure Shut-down Procedure NumberUPS Bypass Operation ProcedureStart-up of UPS-1 Number MMS Start-up ProcedureResponse to UPS Failure UPS FaultBattery Parts ReplacementUPS Component Parts Contact Mitsubishi Electric Automation, Inc. at Fault CodesMitsubishi Igbt Fault a Inverter Voltage Activated Mitsubishi 9800A Series UPS Mitsubishi Electric Automation Inc 847