If a total UPS shutdown is required, verify that the critical load is OFF.
Shut-down of UPS
1. Press the "START/STOP MENU" from the Main Menu on the LCD.
Note: When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter stop operation can only be performed remotely. If local inverter stop operation is required (at the UPS), select "LOCAL" in "Remote/Local" selection in setup page. Select “LOCAL” mode for the purpose of this stop procedure.
2.Press both "STOP" keys simultaneously on the LCD.
3.In general, only the Inverter will be stopped and the Rectifier will remain energized to charge the batteries.
Opening the user supplied External Input AC Circuit Breaker (if dual source used), the External Bypass Input Circuit Breaker and the DC Disconnect Circuit Breaker, CB2, will shut down the load.
4.If stopping both the Rectifier and Charger is required, open the Battery Disconnect circuit breaker (CB2) manually.
5.If a dual source is feeding the UPS, open the External AC Rectifier Input Circuit Breaker (user supplied) manually.
6.If turning off all power to the critical load is desired, open the External Bypass Input Circuit Breaker (user supplied) manually.
FIGURE 3.5-b Shut-down Procedure