B) Shut-down Procedure

 

Page Number:

3-25

If a total UPS shutdown is required, verify that the critical load is OFF.

Shut-down of UPS

1. Press the "START/STOP MENU" from the Main Menu on the LCD.

Note: When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter stop operation can only be performed remotely. If local inverter stop operation is required (at the UPS), select "LOCAL" in "Remote/Local" selection in setup page. Select “LOCAL” mode for the purpose of this stop procedure.

2.Press both "STOP" keys simultaneously on the LCD.

3.In general, only the Inverter will be stopped and the Rectifier will remain energized to charge the batteries.

Opening the user supplied External Input AC Circuit Breaker (if dual source used), the External Bypass Input Circuit Breaker and the DC Disconnect Circuit Breaker, CB2, will shut down the load.

4.If stopping both the Rectifier and Charger is required, open the Battery Disconnect circuit breaker (CB2) manually.

5.If a dual source is feeding the UPS, open the External AC Rectifier Input Circuit Breaker (user supplied) manually.

6.If turning off all power to the critical load is desired, open the External Bypass Input Circuit Breaker (user supplied) manually.

FIGURE 3.5-b Shut-down Procedure

540V

MITSUBISHI ELECTRIC 9800A SERIES UPS

Image 58
Contents For parallel operation possible model only ALN-H0776Preface Table of Contents List of Tables List of Figures External I/F circuit PCB IOAU-04How to use this Manual Important Safety Instructions Retain These Instructions IntroductionMitsubishi Electric 9800A Series UPS General Mitsubishi Electric 9800A Series UPS Overview Mccb Rectifier Single Line Diagram Battery Operation CPM CUPS Parts Location 500kVA DUPS Parts Location 750kVA External contact signal terminal IOAU-04 Mitsubishi Electric 9800A Series UPS Specifications AC Output BatteryEnvironmental Rating of Contactors and Fuses Operator Controls and Indicators 540VLED Display Load on inverter Load on Inverter green Battery operation Battery OP. yellowLoad on bypass Load on Bypass green Menu Liquid Crystal DisplayStart/Stop screen Figure Start/Stop screen Measurement Menu FigureSetup Menu Figure Input Power Failure 11 Main screenFault Indication Figure 13 Main screen Fault indicationExternal Signal Terminal Block TN1TN2 CB2 AXOutput Contacts for external alarm annunciation 16 Control Wiring for External ContactsTerminals 5 to 6 Battery Temp. High contact input IN3 Input Contacts for remote access of UPSTerminals 3 to 4 Remote Inverter Stop input terminal IN2 Terminals 7 to 8 Power Demand Command contact input IN4 External communication connectorMitsubishi 9800A Series UPS Transportation and InstallationInstallation Procedure Minimum clearance required for ventilationProcedure for Cable Connections External Battery SupplyElectric Owners / Technical Manual Mitsubishi 9800A Series UPS Procedure for Cable Connections for Parallel System Recommended Cable Sizes Crimp Type Compression Lug NumberUPS module BN,BPUPS module Input UPS module CabinetInput Cabinet Bypass Output Input A50,B50,C50 A40,B40,C40 External signal terminal IOAU-04 TN2 DC circuit breaker Input Input Cabinet UPS module Wall mounted DC breaker Bypass Battery AC Output Floor mounted DC breaker Input cabinet UPS module Auxiliary Rectifier Cabinet RYER-E Critical Load Cabinet UPS-1 AC Output Critical Load CabinetIOAU-04 UPS-2 AC OutputUPS-1 IOAU-04 TN2 UPS-2 UPS-n*1Start-up of UPS Shut-down Procedure Number B Shut-down ProcedureBypass Operation Procedure UPSNumber MMS Start-up Procedure Start-up of UPS-1UPS Fault Response to UPS FailureBattery Parts ReplacementUPS Component Parts Fault Codes Contact Mitsubishi Electric Automation, Inc. atMitsubishi Igbt Fault a Inverter Voltage Activated Mitsubishi 9800A Series UPS Mitsubishi Electric Automation Inc 847