MITSUBISHI | 9800A SERIES UPS | Page Number: |
ELECTRIC | OWNERS / TECHNICAL MANUAL |
(Note 1) Audible annunciator: [1] intermittent sound, [2] continuous sound.
(Note 2) 1) "Major" is defined as major failure. Inverter transferred to the static bypass line;
2)"Minor" is defined as a minor failure. UPS continues to operate normally, but cause of alarm must be identified;
(Note 3) Indicates one of two possible LED illumination patterns - continuously on (lit) or intermittent (flicker).
(Note 4) External
(Note 5) Trips the battery breaker CB2.
(Note 6) For other than
(Note 7) If the specified time elapses, will transfer to the bypass power supply.
(Note 8) Shows only when corresponding option settings are made.
(Note 9) Code indication means:
Alarm | ||
Failure | ||
U%0++ | Rectifier circuit failure | |
U%1++ | DC circuit failure | |
U%2++ | Inverter circuit failure | |
U%3++ | Control circuit failure | |
U%4++ | Bypass system failure | |
U%8++ | Alarm | |
U%+00 - U%+49 | Major failure | |
U%+50 - U%+99 | Minor failure | |
*) | “+” denotes any numeral from 0 to 9 | |
*) | “%” denotes either “A” or “F” |
MITSUBISHI ELECTRIC 9800A SERIES UPS