3.4Operating Procedures
For MMS, Refer section “D) MMS
A)
Page Number:
a.) Verify that the External Bypass Input Circuit Breaker for each unit is closed (Breaker is user supplied.)
b.) If a dual source is feeding the UPS, close the External AC Rectifier Input Circuit Breaker manually (user supplied).
Start-up of UPS
1.Verify that Control Circuit Breakers (CPM) is closed.
(When Inverter is stopped, the Control Circuit Breaker is not normally opened)
2.The
3.Close Battery Disconnect Circuit Breaker (CB2).
4.The inverter can now be started.
Note: When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter start operation can only be performed remotely. If local inverter start operation is required (at the UPS), select "LOCAL" in "Remote/Local" selection in setup page. Select “LOCAL” mode for the purpose of this start up procedure.
5.On the LCD panel, select “START/STOP MENU” and press the “START” key.
6.The Inverter will start within 5 seconds. Start up is complete.
FIGURE 3.5-a Start-up Procedure