MITSUBISHI
ELECTRIC
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
NOTE: The UPS is equipped with a selectable output contact feature. The above alarms are the default settings. Contact MITSUBISHI
ELECTRIC AUTOMATION, INC. for setup information.
B)Input Contacts (for remote access of UPS)
External contacts are provided by the user of the UPS system. Terminal voltage at the UPS is 24Vdc. Provide external dry contact accordingly.
NOTE: Do not apply voltages to remote access input terminals. Damage to UPS may result.
Refer to Figure 2.17 for a typical wiring configuration. Although this figure applies to the remote start/stop terminals, the same wiring arrangement is used for emergency stop; battery liquid low; and battery temperature high.
FIGURE 2.17 Remote "Start" Contact Connections
UPS Cabinet | External to UPS | |
| Cabinet |
|
Relay | Start |
|
Coil | Start |
|
|
| |
| Switch | |
| Common | 4S |
| 0.5S - | |
24 VDC | ON |
|
OFF |
| |
Relay Coil current : 8.3mA | Use Momentary Switches Only |
|
User supplied
Details of input contacts for remote access : TN2
Terminals 1 to 2 Remote "Inverter Start" input terminal (IN1)
Used to start inverter from a remote location. UPS must be programmed for remote operation. Refer to Operations Menu for procedure.
Terminals 3 to 4 Remote "Inverter Stop" input terminal (IN2)
Used to stop inverter from a remote location. UPS must be programmed for remote operation. Refer to Operations Menu for procedure.
Terminals 5 to 6 "Battery Temp. High" contact input (IN3)
Input fed by a thermocouple that monitors battery temperature. The converter float voltage level is reduced for battery