Mitsubishi 9800A Series technical manual Input Contacts for remote access of UPS

Page 32

MITSUBISHI

ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

2-11

NOTE: The UPS is equipped with a selectable output contact feature. The above alarms are the default settings. Contact MITSUBISHI

ELECTRIC AUTOMATION, INC. for setup information.

B)Input Contacts (for remote access of UPS)

External contacts are provided by the user of the UPS system. Terminal voltage at the UPS is 24Vdc. Provide external dry contact accordingly.

NOTE: Do not apply voltages to remote access input terminals. Damage to UPS may result.

Refer to Figure 2.17 for a typical wiring configuration. Although this figure applies to the remote start/stop terminals, the same wiring arrangement is used for emergency stop; battery liquid low; and battery temperature high.

FIGURE 2.17 Remote "Start" Contact Connections

UPS Cabinet

External to UPS

 

Cabinet

 

Relay

Start

 

Coil

Start

 

 

 

 

Switch

 

Common

4S

 

0.5S -

24 VDC

ON

 

OFF

 

Relay Coil current : 8.3mA

Use Momentary Switches Only

 

User supplied

Details of input contacts for remote access : TN2

Terminals 1 to 2 Remote "Inverter Start" input terminal (IN1)

Used to start inverter from a remote location. UPS must be programmed for remote operation. Refer to Operations Menu for procedure.

Terminals 3 to 4 Remote "Inverter Stop" input terminal (IN2)

Used to stop inverter from a remote location. UPS must be programmed for remote operation. Refer to Operations Menu for procedure.

Terminals 5 to 6 "Battery Temp. High" contact input (IN3)

Input fed by a thermocouple that monitors battery temperature. The converter float voltage level is reduced for battery over-temperature conditions. External thermocouple is user supplied

MITSUBISHI ELECTRIC 9800A SERIES UPS

Image 32
Contents For parallel operation possible model only ALN-H0776Preface Table of Contents List of Tables List of Figures External I/F circuit PCB IOAU-04How to use this Manual Important Safety Instructions Retain These Instructions IntroductionMitsubishi Electric 9800A Series UPS General Mitsubishi Electric 9800A Series UPS Overview Mccb Rectifier Single Line Diagram Battery Operation CPM CUPS Parts Location 500kVA DUPS Parts Location 750kVA External contact signal terminal IOAU-04 Mitsubishi Electric 9800A Series UPS Specifications Environmental BatteryAC Output Rating of Contactors and Fuses Operator Controls and Indicators 540VLoad on bypass Load on Bypass green Battery operation Battery OP. yellowLED Display Load on inverter Load on Inverter green Start/Stop screen Figure Liquid Crystal DisplayMenu Start/Stop screen Measurement Menu FigureSetup Menu Figure Input Power Failure 11 Main screenFault Indication Figure 13 Main screen Fault indicationExternal Signal Terminal Block TN1TN2 CB2 AXOutput Contacts for external alarm annunciation 16 Control Wiring for External ContactsTerminals 3 to 4 Remote Inverter Stop input terminal IN2 Input Contacts for remote access of UPSTerminals 5 to 6 Battery Temp. High contact input IN3 Terminals 7 to 8 Power Demand Command contact input IN4 External communication connectorTransportation and Installation Installation ProcedureMitsubishi 9800A Series UPS Minimum clearance required for ventilationElectric Owners / Technical Manual External Battery SupplyProcedure for Cable Connections Mitsubishi 9800A Series UPS Procedure for Cable Connections for Parallel System Recommended Cable Sizes Crimp Type Compression Lug NumberUPS module BN,BPUPS module Input UPS module CabinetInput Cabinet Bypass Output Input A50,B50,C50 A40,B40,C40 External signal terminal IOAU-04 TN2 DC circuit breaker Input Input Cabinet UPS module Wall mounted DC breaker Bypass Battery AC Output Floor mounted DC breaker Input cabinet UPS module Auxiliary Rectifier Cabinet RYER-E Critical Load Cabinet Critical Load Cabinet IOAU-04UPS-1 AC Output UPS-2 AC OutputUPS-1 IOAU-04 TN2 UPS-2 UPS-n*1Start-up of UPS Shut-down Procedure Number B Shut-down ProcedureBypass Operation Procedure UPSNumber MMS Start-up Procedure Start-up of UPS-1UPS Fault Response to UPS FailureUPS Component Parts Parts ReplacementBattery Fault Codes Contact Mitsubishi Electric Automation, Inc. atMitsubishi Igbt Fault a Inverter Voltage Activated Mitsubishi 9800A Series UPS Mitsubishi Electric Automation Inc 847