9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
WARNING 2
This UPS does not include a Bypass input circuit breaker (MCCB) to protect bypass circuit. The Bypass input circuit breaker (MCCB) is to be field supplied and installed. Recommended Breaker (MCCB)'s Specifications are as follows:
Capacity (kVA) | Bypass Voltage (Vac) | Bypass Rating (Aac) | Breaker (A) |
100 | 480 | 120 | 150 |
|
|
|
|
| 600 | 96 | 125 |
|
|
|
|
150 | 480 | 180 | 225 |
|
|
|
|
| 600 | 144 | 200 |
|
|
|
|
225 | 480 | 271 | 350 |
|
|
|
|
| 600 | 217 | 300 |
|
|
|
|
300 | 480 | 361 | 500 |
|
|
|
|
| 600 | 289 | 400 |
|
|
|
|
375 | 480 | 451 | 600 |
|
|
|
|
| 600 | 361 | 500 |
|
|
|
|
500 | 480 | 601 | 800 |
|
|
|
|
| 600 | 481 | 600 |
|
|
|
|
750 | 480 | 902 | 1200 |
|
|
|
|
| 600 | 722 | 900 |
|
|
|
|
AC input and AC output overcurrent protection and disconnect devices shall be field supplied and installed. The DC output MCCB shall be field supplied and installed. The overcurrent protection device should be installed in the Battery cabinet and rated as indicated in TABLE 1.4.