Mitsubishi 2033D SERIES technical manual AC Input, Static Bypass Input

Page 18

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-12

TABLE 1.3 Detail of Specifications

 

 

 

 

 

 

 

 

 

 

 

 

Rated Output kVA

 

30

 

50

 

80

Rated Output kW

 

24

 

40

 

64

 

 

AC INPUT

 

 

 

Configuration

3 phase, 3 wire

 

 

 

Voltage

480 V

+15% to -15%

(-30% can be operated)

Frequency

60 Hz (45.4Hz to 65Hz)

 

 

 

Reflected Current THD

4% typ. at 100% load; 7% typ. at 50% load

 

 

STATIC BYPASS INPUT

 

Configuration

3 phase, 3 wire

 

 

 

Voltage

480 V

+/-10%

 

 

 

 

Frequency

60 Hz

 

 

 

 

 

 

 

BATTERY

 

 

 

Type

Lead Acid

 

 

 

Ride Through

Application Specific

 

 

 

Nominal Voltage

480 Vdc

 

 

 

 

 

Minimum Voltage

401 Vdc

 

 

 

 

 

Number of Cells

240

 

 

 

 

 

 

 

AC OUTPUT

 

Configuration

3 phase, 4 wire

 

 

 

Voltage

120/208 V, 277/480 V

 

 

 

Voltage Stability

+/-1%

 

 

 

 

 

Frequency

60 Hz

 

 

 

 

 

Frequency Stability

+/-0.05% in free running mode

 

Power Factor

0.8 nominal

 

 

 

Power Factor range

0.8 - 1.0 lagging (within output kW rating)

 

Voltage THD

2% typical THD at 100% Linear Load

 

 

5% typical THD at 100% non-linear load

 

Transient Response

+/-3% at 100% load step

 

 

 

 

+/-1% at loss/return of AC power

 

 

+/-3% at load transfer to/from static bypass

 

Transient Recovery

16.6ms

 

 

 

 

 

Inverter Overload

125% for 10 minutes,

150% for 1 minute

 

System Overload

1000% for 1 cycle (with bypass available)

 

Bypass Overload

150% for 1 minutes

 

 

 

 

 

ENVIRONMENTAL

 

Cooling

Forced Air

 

 

 

Operating Temperature

32F ~ 104F (0C - 40C)

 

 

Recommended 68F - 86F (20C - 30C)

 

Relative Humidity

5% ~ 95% Non Condensing

 

Altitude

0 ~ 9000 feet No Derating

 

Location

Indoor (free from corrosive gases and dust)

 

 

(PCB conformally coated for use in industrial environment)

Paint Color

Munsell 5Y7/1 (Beige)

 

 

 

MITSUBISHI ELECTRIC 2033D SERIES UPS

Image 18
Contents ALN-H0963 Preface Table of Contents List of Tables UPS Module InformationList of Figures How to use this Manual Important Safety Instructions Retain These Instructions IntroductionCapacity kVA General Mitsubishi 2033D Series UPS Overview Normal OperationInternal Static Bypass Line Inverter supply at battery operation Single Line Diagram Battery OperationPCB External Contact Signal Terminal IOAU-05 Mitsubishi 2033D Series UPS Specifications AC Input Static Bypass InputRating of Contactors and Fuses Operator Controls and Indicators 540V 48ALED Display Load on inverter Load on Inverter green Battery operation Battery OP. yellowEPO button Emergency Power Off button Load on bypass Load on Bypass greenLiquid Crystal Display MenusStart/Stop screen Figure Start/Stop screen Measurement Menu FigureSetup Menu Figure Input Power Failure 11 Main screenFault Indication Figure 13 Main screen Fault indicationExternal Signal Terminal Block TN1TN2 Remote EPOOutput Contacts for external alarm annunciation 16 Control Wiring for External ContactsInput Contacts for remote access of UPS Terminals 33 to 34, 35 to 36 Minor Fault contact OUT8Terminals 37 to 38, 39 to 40 Total Alarm contact OUT9 Terminals 3 to 4 Remote Inverter Stop input terminal IN2Terminals 11 to 12 Asynchronous contact input IN6 Terminals 5 to 6 Battery Temp. High contact input IN3Terminals 7 to 8 Power Demand Command contact input IN4 Terminals 13 to 14 Charger IL. contact input IN7External communication connector Pin Not usedMitsubishi 2033D Series UPS Mitsubishi Electric 2033D Series UPSBattery Electric Owners / Technical ManualExternal Battery Supply Procedure for Cable ConnectionsMitsubishi 2033D Series UPS Recommended cable size and torque requirements Crimp Type Compression Lug AUPS Terminal Designation 30kVA UPS BN,BP BN BP AC Bypass Input UPS-1 UPS-2 IOAU-05 TN2 IFAU-01Critical Load Cabinet Operating Procedures UPS Start-up Procedure UPS Shutdown ProcedureEPO Emergency Power Off Procedure Maintenance bypass set-up procedures Transfer of load from inverter to maintenance bypassTransfer of load from maintenance bypass to inverter UPS Fault Electric Owners / Technical Manual Response to UPS FailureParts Replacement UPS Component PartsFault Codes Contact Mitsubishi Electric Automation, Inc. atCode List MitsubishiINV. or Conv Inverter Overload DC circuit failure Mitsubishi Electric Automation Inc 847