Mitsubishi Troubleshooting UF809, UA810, UA814 in 2033D Series UPS

Page 51

MITSUBISHI

 

2033D SERIES UPS

Page Number:

 

ELECTRIC

OWNERS / TECHNICAL MANUAL

6-4

 

 

 

 

 

 

 

 

 

 

(Note 9)

 

 

 

 

(Note 1)

(Note 2)

(Note 3)

Code

Status message

 

Contents

Guidance

Buzzer

External

Failure

indication

 

 

 

 

 

send-out

lamp

 

 

 

 

 

 

contact

 

 

INVERTER OVERLOAD

 

WARNING:

 

 

 

UA806

Overload exceeded 105% (Note 7)

DECREASE

[2]

Alarm

-

> 100%

 

 

 

 

LOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INVERTER OVERLOAD

 

WARNING:

 

 

 

UA809

Overload exceeded 150% (Note 7)

DECREASE

[2]

Alarm

-

> 150%

 

 

 

 

LOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Instantaneous overload. (Output

WARNING:

 

 

 

UA810

INVERTER OVERLOAD

DECREASE

[2]

Alarm

-

voltage -30% for 2ms)

 

 

 

LOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UA812

BYPASS VOLTAGE OUT

Bypass voltage fell out of +/- 12%

CHECK BYPASS

[3]

Alarm

-

OF RANGE

 

range

INPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

UA813

BYPASS PHASE

 

Phase rotation is inverted when bypass

CHECK BYPASS

[2]

Alarm

-

ROTATION ERROR

 

voltage is normal

INPUT

 

 

 

 

 

 

 

 

 

 

 

 

UA814

BYPASS FREQUENCY

Bypass frequency fell out of inverter

CHECK BYPASS

[3]

Alarm

-

OUT OF RANGE

 

synchronization follow-up range

INPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

UA817

EMERGENCY STOP

 

Emergency stop applied

-

-

Alarm

-

ACTIVATED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UA832

ASYNCHRONOUS

 

Asynchronous transfer occurred

-

[2]

Alarm

-

TRANSFER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UA834

BATTERY DEPLETED

DC voltage dropped below discharge

-

-

Alarm

-

AC OUT STOPPED

 

end during inverter operation

 

 

 

 

 

 

 

 

 

 

 

 

 

UA835

BATTERY DEPLETED

Restart after battery depleted

-

-

Alarm

-

AND RESTART

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total of more than 110% load during

WARNING:

 

 

 

UA852

INVERTER OVERLOAD

DECEASE

[2]

Alarm

-

MMS operation.

 

 

 

LOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RETRY START

 

Continuous bypass voltage abnormal,

 

 

 

 

UA853

 

inverter stop, and 72B closed for 1 min.

 

[2]

Alarm

-

OPERATION

 

 

 

 

will stop the UPS. (Fan stop)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MITSUBISHI ELECTRIC 2033D SERIES UPS

Image 51
Contents ALN-H0963 Preface Table of Contents UPS Module Information List of TablesList of Figures How to use this Manual Introduction Important Safety Instructions Retain These InstructionsCapacity kVA General Mitsubishi 2033D Series UPS Normal Operation OverviewInternal Static Bypass Line Single Line Diagram Battery Operation Inverter supply at battery operationPCB External Contact Signal Terminal IOAU-05 Mitsubishi 2033D Series UPS Specifications Static Bypass Input AC InputRating of Contactors and Fuses 540V 48A Operator Controls and IndicatorsLoad on bypass Load on Bypass green Battery operation Battery OP. yellowEPO button Emergency Power Off button LED Display Load on inverter Load on Inverter greenLiquid Crystal Display MenusStart/Stop screen Figure Measurement Menu Figure Start/Stop screenSetup Menu Figure 11 Main screen Input Power Failure13 Main screen Fault indication Fault Indication FigureTN1 External Signal Terminal BlockRemote EPO TN216 Control Wiring for External Contacts Output Contacts for external alarm annunciationTerminals 3 to 4 Remote Inverter Stop input terminal IN2 Terminals 33 to 34, 35 to 36 Minor Fault contact OUT8Terminals 37 to 38, 39 to 40 Total Alarm contact OUT9 Input Contacts for remote access of UPSTerminals 13 to 14 Charger IL. contact input IN7 Terminals 5 to 6 Battery Temp. High contact input IN3Terminals 7 to 8 Power Demand Command contact input IN4 Terminals 11 to 12 Asynchronous contact input IN6Pin Not used External communication connectorMitsubishi Electric 2033D Series UPS Mitsubishi 2033D Series UPSElectric Owners / Technical Manual BatteryProcedure for Cable Connections External Battery SupplyMitsubishi 2033D Series UPS Recommended cable size and torque requirements Crimp Type Compression Lug AUPS Terminal Designation 30kVA UPS BN,BP BN BP AC Bypass Input UPS-1 UPS-2 IOAU-05 TN2 IFAU-01Critical Load Cabinet Operating Procedures UPS Start-up Procedure UPS Shutdown ProcedureEPO Emergency Power Off Procedure Maintenance bypass set-up procedures Transfer of load from inverter to maintenance bypassTransfer of load from maintenance bypass to inverter Electric Owners / Technical Manual Response to UPS Failure UPS FaultUPS Component Parts Parts ReplacementContact Mitsubishi Electric Automation, Inc. at Fault CodesMitsubishi Code ListINV. or Conv Inverter Overload DC circuit failure Mitsubishi Electric Automation Inc 847