Mitsubishi 2033D SERIES technical manual Inverter supply at battery operation

Page 13

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-7

C) Inverter supply at battery operation

FIGURE 1.3 Single Line Diagram - Battery Operation

CB

AC Bypass

Input

CB

AC input

User supplied

 

 

Static Transfer

 

Maintenance

 

 

 

Bypass

 

 

Switch

 

 

 

 

Switch

 

52RS

 

 

 

 

 

 

 

CONVERTER

INVERTER

 

 

 

 

 

 

Output

52RC

FI

FO

52C

52CS

 

 

 

 

 

 

FB

 

 

 

 

72B

 

Power Flow

 

 

 

 

 

BATTERY

 

 

Not in Use

 

50kVA,

80kVA:

 

 

 

UPS Module

 

 

External Battery

Referring to Figure 1.3: In the event of AC input source failure or interruption, the converter will de-energize and the battery will immediately discharge and supply DC power to the inverter to maintain continuous AC power to the load. This operation will continue until:

a)The battery capacity expires and the inverter turns off, or

b)Input power is restored after which the converter will power the inverter and critical load and simultaneously recharge the batteries.

A fully charged battery will provide power for the specified time at the rated load, or longer, at a reduced load.

When power is restored after a low battery shutdown, the converter automatically restarts operation, recharges the batteries and the Inverter is automatically restarted without operator intervention. Load is automatically assumed by the inverter without operator intervention.

The power drawn by the load is equally shared between all system UPS during battery operation.

MITSUBISHI ELECTRIC 2033D SERIES UPS

Image 13
Contents ALN-H0963 Preface Table of Contents UPS Module Information List of TablesList of Figures How to use this Manual Introduction Important Safety Instructions Retain These InstructionsCapacity kVA General Mitsubishi 2033D Series UPS Normal Operation OverviewInternal Static Bypass Line Single Line Diagram Battery Operation Inverter supply at battery operationPCB External Contact Signal Terminal IOAU-05 Mitsubishi 2033D Series UPS Specifications Static Bypass Input AC InputRating of Contactors and Fuses 540V 48A Operator Controls and IndicatorsEPO button Emergency Power Off button Battery operation Battery OP. yellowLED Display Load on inverter Load on Inverter green Load on bypass Load on Bypass greenMenus Liquid Crystal DisplayStart/Stop screen Figure Measurement Menu Figure Start/Stop screenSetup Menu Figure 11 Main screen Input Power Failure13 Main screen Fault indication Fault Indication FigureTN1 External Signal Terminal BlockRemote EPO TN216 Control Wiring for External Contacts Output Contacts for external alarm annunciationTerminals 37 to 38, 39 to 40 Total Alarm contact OUT9 Terminals 33 to 34, 35 to 36 Minor Fault contact OUT8Input Contacts for remote access of UPS Terminals 3 to 4 Remote Inverter Stop input terminal IN2Terminals 7 to 8 Power Demand Command contact input IN4 Terminals 5 to 6 Battery Temp. High contact input IN3Terminals 11 to 12 Asynchronous contact input IN6 Terminals 13 to 14 Charger IL. contact input IN7Pin Not used External communication connectorMitsubishi Electric 2033D Series UPS Mitsubishi 2033D Series UPSElectric Owners / Technical Manual BatteryProcedure for Cable Connections External Battery SupplyMitsubishi 2033D Series UPS Recommended cable size and torque requirements Crimp Type Compression Lug AUPS Terminal Designation 30kVA UPS BN,BP BN BP AC Bypass Input IFAU-01 UPS-1 UPS-2 IOAU-05 TN2Critical Load Cabinet UPS Shutdown Procedure Operating Procedures UPS Start-up ProcedureEPO Emergency Power Off Procedure Transfer of load from inverter to maintenance bypass Maintenance bypass set-up proceduresTransfer of load from maintenance bypass to inverter Electric Owners / Technical Manual Response to UPS Failure UPS FaultUPS Component Parts Parts ReplacementContact Mitsubishi Electric Automation, Inc. at Fault CodesMitsubishi Code ListINV. or Conv Inverter Overload DC circuit failure Mitsubishi Electric Automation Inc 847