MITSUBISHI | 2033D SERIES UPS | Page Number: |
ELECTRIC | OWNERS / TECHNICAL MANUAL |
C) Inverter supply at battery operation
FIGURE 1.3 Single Line Diagram - Battery Operation
CB
AC Bypass
Input
CB
AC input
User supplied
|
| Static Transfer |
| Maintenance |
|
|
| Bypass | |
|
| Switch |
| |
|
|
| Switch | |
| 52RS |
|
| |
|
|
|
| |
| CONVERTER | INVERTER |
|
|
|
|
|
| Output |
52RC | FI | FO | 52C | 52CS |
|
|
|
| |
|
| FB |
|
|
|
| 72B |
| Power Flow |
|
|
|
| |
| BATTERY |
|
| Not in Use |
| 50kVA, | 80kVA: |
| |
|
| UPS Module | ||
|
| External Battery |
Referring to Figure 1.3: In the event of AC input source failure or interruption, the converter will
a)The battery capacity expires and the inverter turns off, or
b)Input power is restored after which the converter will power the inverter and critical load and simultaneously recharge the batteries.
A fully charged battery will provide power for the specified time at the rated load, or longer, at a reduced load.
When power is restored after a low battery shutdown, the converter automatically restarts operation, recharges the batteries and the Inverter is automatically restarted without operator intervention. Load is automatically assumed by the inverter without operator intervention.
The power drawn by the load is equally shared between all system UPS during battery operation.
MITSUBISHI ELECTRIC 2033D SERIES UPS