Mitsubishi 2033D SERIES technical manual Liquid Crystal Display, Menus, Start/Stop screen Figure

Page 22

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

2-3

2.4Liquid Crystal Display (9)

The Liquid Crystal Display (LCD) panel indicates power flow, measured values, operational guidance, data records and error messages. The LCD panel has a back-light which facilitates viewing in different ambient lighting conditions. The LCD will automatically clear and turn off, if the screen is not activated within 3 minute period. The LCD is turned back on when it is touched again. The ERROR indicator is cleared after 24 hours and can be reproduced by pressing any key on the panel.

2.4.1Menus

A)MAIN MENU (FIGURE 2.2)

The LCD panel indicates power flow and measured values, while also operating the start/stop function. The LCD panel also allows the user to verify the status and operation of the UPS Module.

FIGURE 2.2 Main screen

540V

48A

STS

52RC52C

72B

The following will be displayed when the START/STOP key on the LCD panel is pressed:

1.) Start/Stop screen (FIGURE 2.3)

The display indicates the start and stop operations for the UPS system. If this operation is PIN protected, the user is required to enter the security PIN before the screen can be accessed. Refer to (FIGURE 2.4).

When in remote mode, the message “REMOTE operating mode !” will appear on this Screen. The user cannot operate the start and stop functions without changing the setup from remote mode to local mode.

When bypass voltage is abnormal, the message “Bypass voltage abnormal” will appear. -Start:When the bypass voltage is abnormal, the LCD asks the operator if an interrupted transfer is acceptable (Load may be lost). (FIGURE 2.5)

-Stop:When the bypass voltage is abnormal, the user cannot transfer from inverter to bypass line.

MITSUBISHI ELECTRIC 2033D SERIES UPS

Image 22
Contents ALN-H0963 Preface Table of Contents List of Tables UPS Module InformationList of Figures How to use this Manual Important Safety Instructions Retain These Instructions IntroductionCapacity kVA General Mitsubishi 2033D Series UPS Overview Normal OperationInternal Static Bypass Line Inverter supply at battery operation Single Line Diagram Battery OperationPCB External Contact Signal Terminal IOAU-05 Mitsubishi 2033D Series UPS Specifications AC Input Static Bypass InputRating of Contactors and Fuses Operator Controls and Indicators 540V 48ALED Display Load on inverter Load on Inverter green Battery operation Battery OP. yellowEPO button Emergency Power Off button Load on bypass Load on Bypass greenMenus Liquid Crystal DisplayStart/Stop screen Figure Start/Stop screen Measurement Menu FigureSetup Menu Figure Input Power Failure 11 Main screenFault Indication Figure 13 Main screen Fault indicationExternal Signal Terminal Block TN1TN2 Remote EPOOutput Contacts for external alarm annunciation 16 Control Wiring for External ContactsInput Contacts for remote access of UPS Terminals 33 to 34, 35 to 36 Minor Fault contact OUT8Terminals 37 to 38, 39 to 40 Total Alarm contact OUT9 Terminals 3 to 4 Remote Inverter Stop input terminal IN2Terminals 11 to 12 Asynchronous contact input IN6 Terminals 5 to 6 Battery Temp. High contact input IN3Terminals 7 to 8 Power Demand Command contact input IN4 Terminals 13 to 14 Charger IL. contact input IN7External communication connector Pin Not usedMitsubishi 2033D Series UPS Mitsubishi Electric 2033D Series UPSBattery Electric Owners / Technical ManualExternal Battery Supply Procedure for Cable ConnectionsMitsubishi 2033D Series UPS Recommended cable size and torque requirements Crimp Type Compression Lug AUPS Terminal Designation 30kVA UPS BN,BP BN BP AC Bypass Input IFAU-01 UPS-1 UPS-2 IOAU-05 TN2Critical Load Cabinet UPS Shutdown Procedure Operating Procedures UPS Start-up ProcedureEPO Emergency Power Off Procedure Transfer of load from inverter to maintenance bypass Maintenance bypass set-up proceduresTransfer of load from maintenance bypass to inverter UPS Fault Electric Owners / Technical Manual Response to UPS FailureParts Replacement UPS Component PartsFault Codes Contact Mitsubishi Electric Automation, Inc. atCode List MitsubishiINV. or Conv Inverter Overload DC circuit failure Mitsubishi Electric Automation Inc 847