Mitsubishi 2033D SERIES technical manual LED Display Load on inverter Load on Inverter green

Page 21

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

2-2

2.1 LED Display

1) Load on inverter [ LOAD ON INVERTER ](green)

Illuminates when power is supplied from inverter to the critical load. (Indicates the state of inverter transfer switch "52C".)

2) Battery operation [ BATTERY OP. ](yellow)

Illuminates when power is supplied from batteries following a power failure.

3) Load on bypass [ LOAD ON BYPASS ](green)

Illuminates when power is supplied to load devices by static bypass.

4)Overload [ OVERLOAD ](red) Illuminates in overload condition.

5)LCD fault [ LCD FAULT ](red) Illuminates when an error occurs.

6)UPS fault [ UPS FAULT ](red) [Annunciater: intermittent or constant tones] Illuminates when an error occurs in the system. In this case, the details of the error are indicated on the display panel.

2.2MBP Lamp (Maintenance Bypass Pilot Lamp) (7)

When operated in maintenance bypass mode, this lamp will be illuminated.

2.3EPO button (Emergency Power Off button) (8)

When activated, the Emergency Power Off (EPO) function shuts down the UPS module. The critical load will lose power and also shutdown. The EPO function can be performed both locally or remotely.

MITSUBISHI ELECTRIC 2033D SERIES UPS

Image 21
Contents ALN-H0963 Preface Table of Contents UPS Module Information List of TablesList of Figures How to use this Manual Introduction Important Safety Instructions Retain These InstructionsCapacity kVA General Mitsubishi 2033D Series UPS Normal Operation OverviewInternal Static Bypass Line Single Line Diagram Battery Operation Inverter supply at battery operationPCB External Contact Signal Terminal IOAU-05 Mitsubishi 2033D Series UPS Specifications Static Bypass Input AC InputRating of Contactors and Fuses 540V 48A Operator Controls and IndicatorsEPO button Emergency Power Off button Battery operation Battery OP. yellowLED Display Load on inverter Load on Inverter green Load on bypass Load on Bypass greenLiquid Crystal Display MenusStart/Stop screen Figure Measurement Menu Figure Start/Stop screenSetup Menu Figure 11 Main screen Input Power Failure13 Main screen Fault indication Fault Indication FigureTN1 External Signal Terminal BlockRemote EPO TN216 Control Wiring for External Contacts Output Contacts for external alarm annunciationTerminals 37 to 38, 39 to 40 Total Alarm contact OUT9 Terminals 33 to 34, 35 to 36 Minor Fault contact OUT8Input Contacts for remote access of UPS Terminals 3 to 4 Remote Inverter Stop input terminal IN2Terminals 7 to 8 Power Demand Command contact input IN4 Terminals 5 to 6 Battery Temp. High contact input IN3Terminals 11 to 12 Asynchronous contact input IN6 Terminals 13 to 14 Charger IL. contact input IN7Pin Not used External communication connectorMitsubishi Electric 2033D Series UPS Mitsubishi 2033D Series UPSElectric Owners / Technical Manual BatteryProcedure for Cable Connections External Battery SupplyMitsubishi 2033D Series UPS Recommended cable size and torque requirements Crimp Type Compression Lug AUPS Terminal Designation 30kVA UPS BN,BP BN BP AC Bypass Input UPS-1 UPS-2 IOAU-05 TN2 IFAU-01Critical Load Cabinet Operating Procedures UPS Start-up Procedure UPS Shutdown ProcedureEPO Emergency Power Off Procedure Maintenance bypass set-up procedures Transfer of load from inverter to maintenance bypassTransfer of load from maintenance bypass to inverter Electric Owners / Technical Manual Response to UPS Failure UPS FaultUPS Component Parts Parts ReplacementContact Mitsubishi Electric Automation, Inc. at Fault CodesMitsubishi Code ListINV. or Conv Inverter Overload DC circuit failure Mitsubishi Electric Automation Inc 847