3-1

3.0INSTALLATION AND OPERATION

3.1Transportation and Installation

TABLE 3.1 How to transport and install the system

Transportation

Installation

Transport unit with forklift.

Using the pre drilled holes (4 - 24) in the

Carry with overhead crane using

UPS channel base, anchor the unit using

eyebolts provided.

appropriate hardware. (Not provided)

Note : Do not transport in a horizontal position. Cabinets must be maintained upright within +/- 15° of the vertical during handling.

3.2Installation Procedure

A)Note the load tolerance of the floor Refer to Table 3.2 for list of UPS weights.

TABLE 3.2 List of UPS weights

UPS Capacity (kVA)

30

50

80

Weight (lb)

2060

1810

1990

B)Minimum clearance required for ventilation

Right side

1.0" (25 mm) (not required when sidecars are used)

Left side

1.0"

(25 mm) (not required when sidecars are used)

Back side

0.0"

(0.0 mm)

Top side

23.6" (600 mm) (for air flow)

C)Space requirement for routine maintenance

Allow for the following space at the time of installation.

Front

39.4" (1000 mm)

Sides

0.0" (0.0 mm)

Rear

0.0" (0.0 mm)

MITSUBISHI ELECTRIC 2033D SERIES UPS

Image 33
Contents ALN-H0963 Preface Table of Contents UPS Module Information List of TablesList of Figures How to use this Manual Introduction Important Safety Instructions Retain These InstructionsCapacity kVA General Mitsubishi 2033D Series UPS Normal Operation OverviewInternal Static Bypass Line Single Line Diagram Battery Operation Inverter supply at battery operationPCB External Contact Signal Terminal IOAU-05 Mitsubishi 2033D Series UPS Specifications Static Bypass Input AC InputRating of Contactors and Fuses 540V 48A Operator Controls and IndicatorsEPO button Emergency Power Off button Battery operation Battery OP. yellowLED Display Load on inverter Load on Inverter green Load on bypass Load on Bypass greenLiquid Crystal Display MenusStart/Stop screen Figure Measurement Menu Figure Start/Stop screenSetup Menu Figure 11 Main screen Input Power Failure13 Main screen Fault indication Fault Indication FigureTN1 External Signal Terminal BlockRemote EPO TN216 Control Wiring for External Contacts Output Contacts for external alarm annunciationTerminals 37 to 38, 39 to 40 Total Alarm contact OUT9 Terminals 33 to 34, 35 to 36 Minor Fault contact OUT8Input Contacts for remote access of UPS Terminals 3 to 4 Remote Inverter Stop input terminal IN2Terminals 7 to 8 Power Demand Command contact input IN4 Terminals 5 to 6 Battery Temp. High contact input IN3Terminals 11 to 12 Asynchronous contact input IN6 Terminals 13 to 14 Charger IL. contact input IN7Pin Not used External communication connectorMitsubishi Electric 2033D Series UPS Mitsubishi 2033D Series UPSElectric Owners / Technical Manual BatteryProcedure for Cable Connections External Battery SupplyMitsubishi 2033D Series UPS Recommended cable size and torque requirements Crimp Type Compression Lug AUPS Terminal Designation 30kVA UPS BN,BP BN BP AC Bypass Input UPS-1 UPS-2 IOAU-05 TN2 IFAU-01Critical Load Cabinet Operating Procedures UPS Start-up Procedure UPS Shutdown ProcedureEPO Emergency Power Off Procedure Maintenance bypass set-up procedures Transfer of load from inverter to maintenance bypassTransfer of load from maintenance bypass to inverter Electric Owners / Technical Manual Response to UPS Failure UPS FaultUPS Component Parts Parts ReplacementContact Mitsubishi Electric Automation, Inc. at Fault CodesMitsubishi Code ListINV. or Conv Inverter Overload DC circuit failure Mitsubishi Electric Automation Inc 847