MITSUBISHI | 2033D SERIES UPS | Page Number: |
ELECTRIC | OWNERS / TECHNICAL MANUAL |
WARNING 2
This UPS does not include a Bypass input circuit breaker (MCCB) to protect bypass circuit. Bypass input circuit breaker (MCCB) are to be field supplied and installed. Recommended Breaker (MCCB)'s Specifications are as follows:
Capacity (kVA) | Bypass Voltage (Vac) | Bypass Rating (Aac) | Recommended |
|
|
| Breaker (Aac) |
30 | 480 | 36 | 45 |
50 | 480 | 60 | 80 |
80 | 480 | 96 | 125 |
AC input and AC output over current protection and disconnect devices shall be field supplied and installed. DC output over current protection and disconnect device shall be field supplied and installed. The over current protection device shall be rated as indicated in TABLE 1.4.
MITSUBISHI ELECTRIC 2033D SERIES UPS