Mitsubishi 2033D SERIES technical manual External Battery Supply, Procedure for Cable Connections

Page 35

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

3-3

E)External Battery Supply

Please refer to the following when installing and maintaining batteries:

1.The customer shall refer to the battery manufacturer's installation manual for battery installation and maintenance instructions.

2.The maximum permitted fault current from the remote battery supply, and the DC voltage rating of the battery supply over-current protective device are shown in Table 3.4.

TABLE 3.4 Maximum Permitted Fault Current

UPS CAPACITY

DC VOLTAGE

MAXIMUM PERMITTED

(kVA)

RATING (V)

FAULT CURRENT (A)

 

 

 

30

480

25000

50

480

25000

80

480

25000

3.3Procedure for Cable Connections *

i.Confirm the capacity of the UPS being installed. Identify the input/output power terminal blocks as shown in the appropriate Figures 3.1-a, b through 3.2-a, b.

ii.Connect the grounding conductor from the input service entrance to the UPS ground bar.

*Wire per local and/or national code.

iii.Two (2) sources feeding the UPS:

(1)Connect the converter input power cables from the input service entrance to the converter input power terminals, identified as A, B, C in Figures 3.2-a, b. Input cables must be sized for an ampere rating larger than the maximum input drawn by the converter. (Refer to equipment nameplate for current ratings.) Refer to Table 3.5 for recommended cable sizes.

(2)Confirm that an external bypass input circuit breaker (MCCB) is installed (refer to WARNING 2, page 1-2). Connect the bypass input power cables from the input service entrance to the bypass input power terminals, identified as A40, B40, and C40 in Figures 3.2-a, b. Bypass input cables must be sized for an ampere rating larger than the maximum output current capacity of the UPS. Refer to Table 3.5 for recommended cable sizes.

(3)Referring to Figures 3.2-a, b, connect UPS load terminals A50, B50, C50 and N50 to the load distribution panel. Refer to Table 3.5 for cable sizes.

(4)Connect the external signal terminal block as desired. Refer to section 2.5 and Figure

2.15for functional description. 12 AWG, or less, shielded conductor is recommended.

MITSUBISHI ELECTRIC 2033D SERIES UPS

Image 35
Contents ALN-H0963 Preface Table of Contents UPS Module Information List of TablesList of Figures How to use this Manual Introduction Important Safety Instructions Retain These InstructionsCapacity kVA General Mitsubishi 2033D Series UPS Normal Operation OverviewInternal Static Bypass Line Single Line Diagram Battery Operation Inverter supply at battery operationPCB External Contact Signal Terminal IOAU-05 Mitsubishi 2033D Series UPS Specifications Static Bypass Input AC InputRating of Contactors and Fuses 540V 48A Operator Controls and IndicatorsLoad on bypass Load on Bypass green Battery operation Battery OP. yellowEPO button Emergency Power Off button LED Display Load on inverter Load on Inverter greenStart/Stop screen Figure Liquid Crystal DisplayMenus Measurement Menu Figure Start/Stop screenSetup Menu Figure 11 Main screen Input Power Failure13 Main screen Fault indication Fault Indication FigureTN1 External Signal Terminal BlockRemote EPO TN216 Control Wiring for External Contacts Output Contacts for external alarm annunciationTerminals 3 to 4 Remote Inverter Stop input terminal IN2 Terminals 33 to 34, 35 to 36 Minor Fault contact OUT8Terminals 37 to 38, 39 to 40 Total Alarm contact OUT9 Input Contacts for remote access of UPSTerminals 13 to 14 Charger IL. contact input IN7 Terminals 5 to 6 Battery Temp. High contact input IN3Terminals 7 to 8 Power Demand Command contact input IN4 Terminals 11 to 12 Asynchronous contact input IN6Pin Not used External communication connectorMitsubishi Electric 2033D Series UPS Mitsubishi 2033D Series UPSElectric Owners / Technical Manual BatteryProcedure for Cable Connections External Battery SupplyMitsubishi 2033D Series UPS Recommended cable size and torque requirements Crimp Type Compression Lug AUPS Terminal Designation 30kVA UPS BN,BP BN BP AC Bypass Input Critical Load Cabinet UPS-1 UPS-2 IOAU-05 TN2IFAU-01 EPO Emergency Power Off Procedure Operating Procedures UPS Start-up ProcedureUPS Shutdown Procedure Transfer of load from maintenance bypass to inverter Maintenance bypass set-up proceduresTransfer of load from inverter to maintenance bypass Electric Owners / Technical Manual Response to UPS Failure UPS FaultUPS Component Parts Parts ReplacementContact Mitsubishi Electric Automation, Inc. at Fault CodesMitsubishi Code ListINV. or Conv Inverter Overload DC circuit failure Mitsubishi Electric Automation Inc 847