PERFORMANCE DATA COOL operation Rated frequency 79Hz
MSZ-GB50VA : MUZ-GB50VA
CAPACITY:5.0(kW) | SHF:0.69 | INPUT:1650(W) |
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| OUTDOOR DB(:) |
|
|
|
|
|
| ||||
INDOOR | INDOOR |
|
|
| 35 |
|
|
| 40 |
|
|
| 43 |
|
| ||||
DB(:) | WB(:) | Q |
| SHC |
| SHF | INPUT | Q | SHC |
| SHF | INPUT | Q | SHC |
| SHF | INPUT |
| |
21 |
| 18 | 4.90 |
| 2.50 |
| 0.51 | 1617 | 4.50 | 2.30 |
| 0.51 | 1716 | 4.30 | 2.19 |
| 0.51 | 1749 |
|
21 |
| 20 | 5.15 |
| 2.01 |
| 0.39 | 1683 | 4.80 | 1.87 |
| 0.39 | 1766 | 4.60 | 1.79 |
| 0.39 | 1815 |
|
22 |
| 18 | 4.90 |
| 2.70 |
| 0.55 | 1617 | 4.50 | 2.48 |
| 0.55 | 1716 | 4.30 | 2.37 |
| 0.55 | 1749 |
|
22 |
| 20 | 5.15 |
| 2.21 |
| 0.43 | 1683 | 4.80 | 2.06 |
| 0.43 | 1766 | 4.60 | 1.98 |
| 0.43 | 1815 |
|
22 |
| 22 | 5.45 |
| 1.69 |
| 0.31 | 1749 | 5.10 | 1.58 |
| 0.31 | 1848 | 4.90 | 1.52 |
| 0.31 | 1881 |
|
23 |
| 18 | 4.90 |
| 2.89 |
| 0.59 | 1617 | 4.50 | 2.66 |
| 0.59 | 1716 | 4.30 | 2.54 |
| 0.59 | 1749 |
|
23 |
| 20 | 5.15 |
| 2.42 |
| 0.47 | 1683 | 4.80 | 2.26 |
| 0.47 | 1766 | 4.60 | 2.16 |
| 0.47 | 1815 |
|
23 |
| 22 | 5.45 |
| 1.91 |
| 0.35 | 1749 | 5.10 | 1.79 |
| 0.35 | 1848 | 4.90 | 1.72 |
| 0.35 | 1881 |
|
24 |
| 18 | 4.90 |
| 3.09 |
| 0.63 | 1617 | 4.50 | 2.84 |
| 0.63 | 1716 | 4.30 | 2.71 |
| 0.63 | 1749 |
|
24 |
| 20 | 5.15 |
| 2.63 |
| 0.51 | 1683 | 4.80 | 2.45 |
| 0.51 | 1766 | 4.60 | 2.35 |
| 0.51 | 1815 |
|
24 |
| 22 | 5.45 |
| 2.13 |
| 0.39 | 1749 | 5.10 | 1.99 |
| 0.39 | 1848 | 4.90 | 1.91 |
| 0.39 | 1881 |
|
24 |
| 24 | 5.75 |
| 1.55 |
| 0.27 | 1815 | 5.40 | 1.46 |
| 0.27 | 1898 | 5.25 | 1.42 |
| 0.27 | 1947 |
|
25 |
| 18 | 4.90 |
| 3.28 |
| 0.67 | 1617 | 4.50 | 3.02 |
| 0.67 | 1716 | 4.30 | 2.88 |
| 0.67 | 1749 |
|
25 |
| 20 | 5.15 |
| 2.83 |
| 0.55 | 1683 | 4.80 | 2.64 |
| 0.55 | 1766 | 4.60 | 2.53 |
| 0.55 | 1815 |
|
25 |
| 22 | 5.45 |
| 2.34 |
| 0.43 | 1749 | 5.10 | 2.19 |
| 0.43 | 1848 | 4.90 | 2.11 |
| 0.43 | 1881 |
|
25 |
| 24 | 5.75 |
| 1.78 |
| 0.31 | 1815 | 5.40 | 1.67 |
| 0.31 | 1898 | 5.25 | 1.31 |
| 0.25 | 1947 |
|
26 |
| 18 | 4.90 |
| 3.48 |
| 0.71 | 1617 | 4.50 | 3.20 |
| 0.71 | 1716 | 4.30 | 3.05 |
| 0.71 | 1749 |
|
26 |
| 20 | 5.15 |
| 3.04 |
| 0.59 | 1683 | 4.80 | 2.83 |
| 0.59 | 1766 | 4.60 | 2.71 |
| 0.59 | 1815 |
|
26 |
| 22 | 5.45 |
| 2.56 |
| 0.47 | 1749 | 5.10 | 2.40 |
| 0.47 | 1848 | 4.90 | 2.30 |
| 0.47 | 1881 |
|
26 |
| 24 | 5.75 |
| 2.01 |
| 0.35 | 1815 | 5.40 | 1.89 |
| 0.35 | 1898 | 5.25 | 1.21 |
| 0.23 | 1947 |
|
26 |
| 26 | 6.05 |
| 1.39 |
| 0.23 | 1881 | 5.70 | 1.31 |
| 0.23 | 1964 | 5.50 | 1.27 |
| 0.23 | 2013 |
|
27 |
| 18 | 4.90 |
| 3.68 |
| 0.75 | 1617 | 4.50 | 3.38 |
| 0.75 | 1716 | 4.30 | 3.23 |
| 0.75 | 1749 |
|
27 |
| 20 | 5.15 |
| 3.24 |
| 0.63 | 1683 | 4.80 | 3.02 |
| 0.63 | 1766 | 4.60 | 2.90 |
| 0.63 | 1815 |
|
27 |
| 22 | 5.45 |
| 2.78 |
| 0.51 | 1749 | 5.10 | 2.60 |
| 0.51 | 1848 | 4.90 | 2.50 |
| 0.51 | 1881 |
|
27 |
| 24 | 5.75 |
| 2.24 |
| 0.39 | 1815 | 5.40 | 2.11 |
| 0.39 | 1898 | 5.25 | 1.10 |
| 0.21 | 1947 |
|
27 |
| 26 | 6.05 |
| 1.63 |
| 0.27 | 1881 | 5.70 | 1.54 |
| 0.27 | 1964 | 5.50 | 1.49 |
| 0.27 | 2013 |
|
28 |
| 18 | 4.90 |
| 3.87 |
| 0.79 | 1617 | 4.50 | 3.56 |
| 0.79 | 1716 | 4.30 | 3.40 |
| 0.79 | 1749 |
|
28 |
| 20 | 5.15 |
| 3.45 |
| 0.67 | 1683 | 4.80 | 3.22 |
| 0.67 | 1766 | 4.60 | 3.08 |
| 0.67 | 1815 |
|
28 |
| 22 | 5.45 |
| 3.00 |
| 0.55 | 1749 | 5.10 | 2.81 |
| 0.55 | 1848 | 4.90 | 2.70 |
| 0.55 | 1881 |
|
28 |
| 24 | 5.75 |
| 2.47 |
| 0.43 | 1815 | 5.40 | 2.32 |
| 0.43 | 1898 | 5.25 | 1.00 |
| 0.19 | 1947 |
|
28 |
| 26 | 6.05 |
| 1.88 |
| 0.31 | 1881 | 5.70 | 1.77 |
| 0.31 | 1964 | 5.50 | 1.71 |
| 0.31 | 2013 |
|
29 |
| 18 | 4.90 |
| 4.07 |
| 0.83 | 1617 | 4.50 | 3.74 |
| 0.83 | 1716 | 4.30 | 3.57 |
| 0.83 | 1749 |
|
29 |
| 20 | 5.15 |
| 3.66 |
| 0.71 | 1683 | 4.80 | 3.41 |
| 0.71 | 1766 | 4.60 | 3.27 |
| 0.71 | 1815 |
|
29 |
| 22 | 5.45 |
| 3.22 |
| 0.59 | 1749 | 5.10 | 3.01 |
| 0.59 | 1848 | 4.90 | 2.89 |
| 0.59 | 1881 |
|
29 |
| 24 | 5.75 |
| 2.70 |
| 0.47 | 1815 | 5.40 | 2.54 |
| 0.47 | 1898 | 5.25 | 0.89 |
| 0.17 | 1947 |
|
29 |
| 26 | 6.05 |
| 2.12 |
| 0.35 | 1881 | 5.70 | 2.00 |
| 0.35 | 1964 | 5.50 | 1.93 |
| 0.35 | 2013 |
|
30 |
| 18 | 4.90 |
| 4.26 |
| 0.87 | 1617 | 4.50 | 3.92 |
| 0.87 | 1716 | 4.30 | 3.74 |
| 0.87 | 1749 |
|
30 |
| 20 | 5.15 |
| 3.86 |
| 0.75 | 1683 | 4.80 | 3.60 |
| 0.75 | 1766 | 4.60 | 3.45 |
| 0.75 | 1815 |
|
30 |
| 22 | 5.45 |
| 3.43 |
| 0.63 | 1749 | 5.10 | 3.21 |
| 0.63 | 1848 | 4.90 | 3.09 |
| 0.63 | 1881 |
|
30 |
| 24 | 5.75 |
| 2.93 |
| 0.51 | 1815 | 5.40 | 2.75 |
| 0.51 | 1898 | 5.25 | 0.79 |
| 0.15 | 1947 |
|
30 |
| 26 | 6.05 |
| 2.36 |
| 0.39 | 1881 | 5.70 | 2.22 |
| 0.39 | 1964 | 5.50 | 2.15 |
| 0.39 | 2013 |
|
31 |
| 18 | 4.90 |
| 4.46 |
| 0.91 | 1617 | 4.50 | 4.10 |
| 0.91 | 1716 | 4.30 | 3.91 |
| 0.91 | 1749 |
|
31 |
| 20 | 5.15 |
| 4.07 |
| 0.79 | 1683 | 4.80 | 3.79 |
| 0.79 | 1766 | 4.60 | 3.63 |
| 0.79 | 1815 |
|
31 |
| 22 | 5.45 |
| 3.65 |
| 0.67 | 1749 | 5.10 | 3.42 |
| 0.67 | 1848 | 4.90 | 3.28 |
| 0.67 | 1881 |
|
31 |
| 24 | 5.75 |
| 3.16 |
| 0.55 | 1815 | 5.40 | 2.97 |
| 0.55 | 1898 | 5.25 | 0.68 |
| 0.13 | 1947 |
|
31 |
| 26 | 6.05 |
| 2.60 |
| 0.43 | 1881 | 5.70 | 2.45 |
| 0.43 | 1964 | 5.50 | 2.37 |
| 0.43 | 2013 |
|
32 |
| 18 | 4.90 |
| 4.66 |
| 0.95 | 1617 | 4.50 | 4.28 |
| 0.95 | 1716 | 4.30 | 4.09 |
| 0.95 | 1749 |
|
32 |
| 20 | 5.15 |
| 4.27 |
| 0.83 | 1683 | 4.80 | 3.98 |
| 0.83 | 1766 | 4.60 | 3.82 |
| 0.83 | 1815 |
|
32 |
| 22 | 5.45 |
| 3.87 |
| 0.71 | 1749 | 5.10 | 3.62 |
| 0.71 | 1848 | 4.90 | 3.48 |
| 0.71 | 1881 |
|
32 |
| 24 | 5.75 |
| 3.39 |
| 0.59 | 1815 | 5.40 | 3.19 |
| 0.59 | 1898 | 5.25 | 0.58 |
| 0.11 | 1947 |
|
32 |
| 26 | 6.05 |
| 2.84 |
| 0.47 | 1881 | 5.70 | 2.68 |
| 0.47 | 1964 | 5.50 | 2.59 |
| 0.47 | 2013 |
|
NOTE |
| Q : Total capacity (kW) |
| SHF : Sensible heat factor | DB : | ||||||||||||||
| SHC : Sensible heat capacity (kW) | INPUT : Total power input (W) | WB : |
13