Mitsubishi Electronics MUZ-GB50VA service manual Failure mode recall function, Off

Page 16

10-2. Failure mode recall function

Outline of the function

This air conditioner can memorize the abnormal condition which has occurred once.

Even though LED indication listed on the troubleshooting check table (10-4.) disappears, the memorized failure details can be recalled.

This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.

1. Flow chart of failure mode recall function for the indoor/outdoor unit

Operational procedure

The cause of abnormality cannot be found because the abnormality doesn't recur.

Setting up the failure mode recall function

Turn ON the power supply.

<Preparation of the remote controller>

1 While pressing both OPERATION SELECT

button and TOO COOL button on the remote controller at the same time, press RESET button.

2First, release RESET button.

And release the other two buttons after all LCD except the set temperature in operation display section of the remote controller is displayed after 3 seconds.

Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. w1

Does the left lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds?

Blinks: Either indoor or outdoor unit is abnormal. Beep are emitted at the same timing

as the blinking of the left lamp of OPERATION INDICATOR lamp. W2

No

(OFF)

W1. Regardless of normal or abnormal, a short beep is emitted once as the signal is received.

Indoor unit is normal.

But the outdoor unit might be abnormal because there are some abnormalities that can't be recalled with this way.

Confirm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function.(Refer to 10-2.2)

Judgment of indoor/outdoor abnormality

Yes

(Blinks)

 

Before blinking, does the left lamp of

 

Yes

 

 

 

 

 

OPERATION INDICATOR lamp stay ON for 3

 

 

 

 

 

 

seconds?

 

 

 

 

 

 

 

Stays ON for 3 seconds (without beep):

 

 

 

 

 

 

 

The outdoor unit is abnormal.

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The indoor unit is abnormal.

 

 

 

The outdoor unit is abnormal.

 

Check the blinking pattern, and confirm the abnormal point with the indoor unit

 

Check the blinking pattern, and confirm the abnormal point with the

 

failure mode table (Refer to indoor unit service manual.)

 

 

 

outdoor unit failure mode table (Refer to 10-2.3).

 

Make sure to check at least two consecutive blinking cycles.

W2

 

Make sure to check at least two consecutive blinking cycles. W3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Releasing the failure mode recall function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Release the failure mode recall function by the following procedures.

 

 

 

 

 

Turn OFF the power supply and turn it ON again.

 

 

 

 

 

 

 

Press RESET button of the remote controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Repair the defective parts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Deleting the abnormal memorized condition

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above.

2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.

3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.

4Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.

Note1.Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly. 2.If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.

W2. Blinking pattern when the indoor unit is abnormal:

Blinking at 0.5-

Blinking at 0.5-

 

2.5-second OFF second interval

2.5-second OFF second interval

 

ON

 

 

OFF

 

 

Beeps

Beeps

Beeps

Repeated cycle

Repeated cycle

Repeated cycle

W3.Blinking pattern when the outdoor unit is abnormal:

 

 

 

 

 

 

 

 

Blinking at 0.5-

 

 

 

 

 

 

 

 

Blinking at 0.5-

 

 

 

2.5-second OFF

3-second ON

second interval

 

 

 

2.5-second OFF

3-second ON

second interval

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No beep

 

 

 

 

Beeps

 

 

 

 

 

No beep

 

 

 

 

Beeps

 

 

 

 

 

Repeated cycle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Repeated cycle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Repeated cycle

16

Image 16
Contents R410A Refrigerant OBR01 Contents Revised EDITION-ATechnical Changes MUZ-GA50VA E1SNB130FLDH SNB130FLDH1Specification AccessoriesPart Names and Functions MUZ-GB50VASpecifications and rating conditions of main electric parts Noise Criteria Curves Band OctaveOutlines and Dimensions MUZ-GB50VA Outdoor UnitWiring Diagram Outdoor Unit MUZ-GB50VARefrigerant System Diagram UnitmmIndoor Unit Outdoor Unit Performance CurvesCapacity and input curves Test RUN Operation How to operate fixed-frequency operation MUZ-GB50VACool operation MSZ-GB50VA MUZ-GB50VA Performance Data Cool operation Rated frequency 79HzOutdoor SHC SHF Input Outdoor DB Actuator Control Performance Data Heat operationOutdoor fan motor control R.V. coil controlTroubleshooting Relation between main sensor and actuator MUZ-GB50Failure mode recall function OFFOperational procedure Outdoor unit failure mode table Time flash Communication error Lighting Instruction of troubleshooting IndicatorOperation EmergencyTroubleshooting check table MUZ-GB50VA Operate Lightning Twice Outdoor power systemOnce Lighting Trouble criterion of main parts MUZ-GB50VA RED BLK BLK WHTWHT RED RED ORNHow to check inverter/ compressor Troubleshooting flowCheck of outdoor thermistors When heating operation does not work Check of R.V. coilCheck of power supply Check of outdoor fan motorCheck of current-limiting resistor Check of LEVParts side Electromagnetic noise enters into TV sets or radios Discharge temperature thermistor RT62 Noise filter P.C. board Outdoor power board CN2CN3 CN5MUZ-GB50VA Outdoor Unit Operating Procedure Photos Disassembly InstructionsRemoving the cabinet Photo Operating Procedure Photos Removing R.V. coilTure thermistor and ambient temperature thermistor Removing outdoor fan motor PhotoRemoving the compressor and 4-way valve Photo Removing the reactorRoHS Parts List RoHS compliant MUZ-GB MUZ-GB50VA Accessory MUZ-GB50