Mitsubishi Electronics MUZ-GB50VA service manual Once Lighting

Page 22

No.

Symptom

Indication

 

Abnormal point / Condition

Condition

Correspondence

LED1(Red)

LED2(Yellow)

 

 

 

 

 

 

 

20

Outdoor unit

Once

Lighting

 

Primary current protection

When the input current exceeds 15A.

These symptoms do not mean any abnormality of the

operates.

 

 

 

product, but check the following points.

 

Secondary current protection

When the current of the compressor exceeds 15A.

 

 

 

 

 

 

 

 

 

 

• Check if indoor filters are clogged.

 

 

 

 

 

 

 

 

 

Twice

Lighting

 

High-pressure protection

When the indoor gas pipe temperature exceeds 45: during heating.

• Check if refrigerant is short.

21

 

 

 

 

• Check if indoor/outdoor unit air circulation is short cycled.

 

 

 

 

Defrosting in cooling

When the indoor gas pipe temperature falls 3: or below during cooling.

 

 

 

 

 

 

 

 

 

 

 

22

 

3 times

Lighting

 

Discharge temperature

 

• Check refrigerant circuit and refrigerant amount.

 

 

When the discharge temperature exceeds 100: during operation.

• Refer to 10-6.G"Check of LEV".

 

 

protection

 

 

 

 

 

 

• Refer to 10-6.B"Check of outdoor thermistors".

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low discharge

When the frequency of the compressor is kept 80Hz or more and

• Refer to 10-6.G"Check of LEV".

23

 

4 times

Lighting

 

the discharge temperature is kept under 39: for more than 20

 

 

temperature protection

• Check refrigerant circuit and refrigerant amount.

 

 

 

 

 

minutes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This symptom does not mean any abnormality of the

 

 

 

 

 

Cooling high-pressure

When the outdoor heat exchanger temperature exceeds 58:

product, but check the following points.

24

 

5 times

Lighting

 

• Check if indoor filters are clogged.

 

 

protection

during operation.

 

 

• Check if refrigerant is short.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Check if indoor/outdoor unit air circulation is short cycled.

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

25

operates

9 times

Lighting

 

Inverter check mode

When the unit is operated with emergency operation switch.

-

26

Lighting

Lighting

Normal

-

-

22

Image 22
Contents R410A Refrigerant OBR01 Contents Revised EDITION-ASNB130FLDH Technical ChangesMUZ-GA50VA E1 SNB130FLDH1Part Names and Functions SpecificationAccessories MUZ-GB50VASpecifications and rating conditions of main electric parts Noise Criteria Curves Band OctaveOutlines and Dimensions MUZ-GB50VA Outdoor UnitWiring Diagram Outdoor Unit MUZ-GB50VARefrigerant System Diagram UnitmmIndoor Unit Outdoor Unit Performance CurvesCapacity and input curves Test RUN Operation How to operate fixed-frequency operation MUZ-GB50VACool operation Outdoor MSZ-GB50VA MUZ-GB50VAPerformance Data Cool operation Rated frequency 79Hz SHC SHF InputOutdoor DB Outdoor fan motor control Actuator ControlPerformance Data Heat operation R.V. coil controlTroubleshooting Relation between main sensor and actuator MUZ-GB50Failure mode recall function OFFOperational procedure Outdoor unit failure mode table Time flash Communication error Lighting Operation Instruction of troubleshootingIndicator EmergencyTroubleshooting check table MUZ-GB50VA Operate Lightning Twice Outdoor power systemOnce Lighting WHT RED Trouble criterion of main parts MUZ-GB50VARED BLK BLK WHT RED ORNHow to check inverter/ compressor Troubleshooting flowCheck of outdoor thermistors When heating operation does not work Check of R.V. coilCheck of power supply Check of outdoor fan motorCheck of current-limiting resistor Check of LEVParts side Electromagnetic noise enters into TV sets or radios Discharge temperature thermistor RT62 Noise filter P.C. board CN3 Outdoor power boardCN2 CN5MUZ-GB50VA Outdoor Unit Operating Procedure Photos Disassembly InstructionsRemoving the cabinet Photo Operating Procedure Photos Removing R.V. coilTure thermistor and ambient temperature thermistor Removing outdoor fan motor PhotoRemoving the compressor and 4-way valve Photo Removing the reactorRoHS Parts List RoHS compliant MUZ-GB MUZ-GB50VA Accessory MUZ-GB50