• Fan motor does not operate or stops operating shortly after starting the operation.

D Check of outdoor fan motor

Check the connection between the connector CN931 and CN932.

Is the resistance between each terminal Yes of outdoor fan motor normal?

No

(Fixed to either 5V or 0V DC) No

Disconnect CN932 from outdoor electronic control P.C. board, and turn on the power supply.

Rotate the outdoor fan motor manually and measure the voltage of CN931.

Between 1(+) and 5(-)

Between 2(+) and 5(-)

Between 3(+) and 5(-)

Does the voltage between each terminal become 5V DC and 0V DC repeatedly?

No

Yes

Replace the outdoor DC fan motor.

Does the outdoor fan motor rotates smoothly?

Yes

Replace the outdoor electronic control P.C. board.

Outdoor unit does not operate. (LED display: display OFF)

E Check of power supply

Check the connecting of parts of main power supply circuit.

Turn on power supply.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there voltage of 230V AC in the

No

 

 

 

 

 

Check the power supply cable.

power supply terminal block?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the output voltage from the noise

No

 

Is fuse (F64) blown?

No

filter P.C. board 230V AC?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

Replace the fuse.

 

 

 

 

 

 

 

 

 

 

Replace the noise filter P.C. board.

Is the input voltage to the power board 230V AC?

Yes

Is the input voltage to the outdoor electronic control P.C. board 325V DC?

Yes

No

Replace the reactor.

 

No

Replace the power board.

Replace the outdoor electronic control P.C. board.

27

Image 27
Contents Revised EDITION-A R410A Refrigerant OBR01 ContentsSNB130FLDH1 Technical ChangesMUZ-GA50VA E1 SNB130FLDHMUZ-GB50VA SpecificationAccessories Part Names and FunctionsSpecifications and rating conditions of main electric parts Band Octave Noise Criteria CurvesMUZ-GB50VA Outdoor Unit Outlines and DimensionsOutdoor Unit MUZ-GB50VA Wiring DiagramUnitmm Refrigerant System DiagramPerformance Curves Indoor Unit Outdoor UnitCapacity and input curves MUZ-GB50VA Test RUN Operation How to operate fixed-frequency operationCool operation SHC SHF Input MSZ-GB50VA MUZ-GB50VAPerformance Data Cool operation Rated frequency 79Hz OutdoorOutdoor DB R.V. coil control Actuator ControlPerformance Data Heat operation Outdoor fan motor controlRelation between main sensor and actuator MUZ-GB50 TroubleshootingOFF Failure mode recall functionOperational procedure Outdoor unit failure mode table Time flash Communication error Lighting Emergency Instruction of troubleshootingIndicator OperationOperate Lightning Twice Outdoor power system Troubleshooting check table MUZ-GB50VAOnce Lighting RED ORN Trouble criterion of main parts MUZ-GB50VARED BLK BLK WHT WHT REDTroubleshooting flow How to check inverter/ compressorCheck of outdoor thermistors Check of R.V. coil When heating operation does not workCheck of outdoor fan motor Check of power supplyCheck of LEV Check of current-limiting resistorParts side Electromagnetic noise enters into TV sets or radios Discharge temperature thermistor RT62 Noise filter P.C. board CN5 Outdoor power boardCN2 CN3Disassembly Instructions MUZ-GB50VA Outdoor Unit Operating Procedure PhotosRemoving the cabinet Photo Removing R.V. coil Operating Procedure PhotosRemoving outdoor fan motor Photo Ture thermistor and ambient temperature thermistorRemoving the reactor Removing the compressor and 4-way valve PhotoRoHS Parts List RoHS compliant MUZ-GB MUZ-GB50 MUZ-GB50VA Accessory