Mitsubishi Electronics MUZ-GB50VA service manual Outdoor power board, CN2, CN3, CN5

Page 33

3. Outdoor power board

MUZ-GB50VA

 

 

Connect to the compressor

 

 

Voltage among phases: 5V to

 

 

180V

 

325-370V DC

Connect to the earth

Output (Red)

 

 

(+)

1

CN2

 

 

 

 

(–)

3

Connect to the controller board

(+)1-5(–): Signal transmission

 

(White)

(To electronic control P.C. board)

 

 

5V DC pulse wave

 

 

 

 

 

(+)2-5(–): Zero cross signal

 

 

3-4

: Not used

 

 

(+)6-5(–): 15V

 

 

(+)7-5(–): 15V

 

 

CN3

 

 

 

Fin temperature thermistor RT64

 

 

) Signal reception (From

 

 

electronic control P.C. board)

 

 

5V DC pulse wave

 

 

CN5

 

 

 

Primary current detection

 

 

(Connect to the noise filter)

Connect to the compressor

Voltage among phases: 5V to 180V

Connect to the earth

325-370V DC Output (Red)

(+)

1

(–)3 (White)

CN2

Connect to the controller board (+)1-5(–): Signal transmission (To electronic control P.C. board)

5V DC pulse wave

(+)2-5(–): Zero cross signal 3-4 : Not used

(+)6-5(–): 15V

(+)7-5(–): 15V

CN3

Fin temperature thermistor RT64

) Signal reception (From electronic control P.C. board) 5V DC pulse wave

CN5

Primary current detection (Connect to the noise filter)

33

Image 33
Contents Revised EDITION-A R410A Refrigerant OBR01 ContentsMUZ-GA50VA E1 Technical ChangesSNB130FLDH SNB130FLDH1Accessories SpecificationPart Names and Functions MUZ-GB50VASpecifications and rating conditions of main electric parts Band Octave Noise Criteria CurvesMUZ-GB50VA Outdoor Unit Outlines and DimensionsOutdoor Unit MUZ-GB50VA Wiring DiagramUnitmm Refrigerant System DiagramPerformance Curves Indoor Unit Outdoor UnitCapacity and input curves MUZ-GB50VA Test RUN Operation How to operate fixed-frequency operationCool operation Performance Data Cool operation Rated frequency 79Hz MSZ-GB50VA MUZ-GB50VAOutdoor SHC SHF InputOutdoor DB Performance Data Heat operation Actuator ControlOutdoor fan motor control R.V. coil controlRelation between main sensor and actuator MUZ-GB50 TroubleshootingOFF Failure mode recall functionOperational procedure Outdoor unit failure mode table Time flash Communication error Lighting Indicator Instruction of troubleshootingOperation EmergencyOperate Lightning Twice Outdoor power system Troubleshooting check table MUZ-GB50VAOnce Lighting RED BLK BLK WHT Trouble criterion of main parts MUZ-GB50VAWHT RED RED ORNTroubleshooting flow How to check inverter/ compressorCheck of outdoor thermistors Check of R.V. coil When heating operation does not workCheck of outdoor fan motor Check of power supplyCheck of LEV Check of current-limiting resistorParts side Electromagnetic noise enters into TV sets or radios Discharge temperature thermistor RT62 Noise filter P.C. board CN2 Outdoor power boardCN3 CN5Disassembly Instructions MUZ-GB50VA Outdoor Unit Operating Procedure PhotosRemoving the cabinet Photo Removing R.V. coil Operating Procedure PhotosRemoving outdoor fan motor Photo Ture thermistor and ambient temperature thermistorRemoving the reactor Removing the compressor and 4-way valve PhotoRoHS Parts List RoHS compliant MUZ-GB MUZ-GB50 MUZ-GB50VA Accessory