The cooling operation or heating operation does not operate. (LED display: Both LED1 and LED2 lighting)

C Check of R.V. coil

When heating operation does not work.

1.Disconnect the lead wire leading to the compressor.

2.3 minutes after turning on the power supply, start EMERGENCY OPERATION in HEAT mode.

Is there voltage of 230V AC between pin1 and

No

pin 2 at connector CN912? W

 

Yes

 

Turn off power supply of indoor and outdoor unit.

1.Turn off power supply of indoor and outdoor unit, and disconnect the connector CN781 in the outdoor electronic control P.C. board.

2.3 minutes after turning on the power supply, start EMERGENCY OPERATION in HEAT mode.

Disconnect the connector CN912 in noise filter P. C. board. Is there normal resistance to R.V. coil?

Yes

Replace the 4-way valve.

No

Replace the R.V. coil.

Is there voltage 12V DC

No

between the connector CN781 pin 5 (+) and pin 3 (-)?

Yes

Replace the noise filter P.C. board.

Replace the electronic control P.C. board.

• When cooling operation does not work.

1.Disconnect the lead wire leading to the compressor.

2.3 minutes after turning on the power supply, start EMERGENCY OPERATION in COOL mode.

Is there voltage of 230V AC between pin1 and

No

 

Replace the 4-way valve.

pin 2 at connector CN912? W

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

WIf the connector CN912 is not connected or R.V. coil is open, voltage occurs between terminals even when the control is OFF.

1.Turn off power supply of indoor and outdoor unit, and disconnect the connector CN781 in the outdoor electronic control P.C. board.

2.3 minutes after turning on the power supply, start EMERGENCY OPERATION in COOL mode.

Is there voltage 12V DC

No

between the connector CN781 Replace the noise filter P.C. board. pin 5 (+) and pin 3 (-)?

Yes

Replace the outdoor electronic control P.C. board.

26

Image 26
Contents R410A Refrigerant OBR01 Contents Revised EDITION-ASNB130FLDH Technical ChangesMUZ-GA50VA E1 SNB130FLDH1Part Names and Functions SpecificationAccessories MUZ-GB50VASpecifications and rating conditions of main electric parts Noise Criteria Curves Band OctaveOutlines and Dimensions MUZ-GB50VA Outdoor UnitWiring Diagram Outdoor Unit MUZ-GB50VARefrigerant System Diagram UnitmmCapacity and input curves Performance CurvesIndoor Unit Outdoor Unit Test RUN Operation How to operate fixed-frequency operation MUZ-GB50VACool operation Outdoor MSZ-GB50VA MUZ-GB50VAPerformance Data Cool operation Rated frequency 79Hz SHC SHF InputOutdoor DB Outdoor fan motor control Actuator ControlPerformance Data Heat operation R.V. coil controlTroubleshooting Relation between main sensor and actuator MUZ-GB50Failure mode recall function OFFOperational procedure Outdoor unit failure mode table Time flash Communication error Lighting Operation Instruction of troubleshootingIndicator EmergencyTroubleshooting check table MUZ-GB50VA Operate Lightning Twice Outdoor power systemOnce Lighting WHT RED Trouble criterion of main parts MUZ-GB50VARED BLK BLK WHT RED ORNHow to check inverter/ compressor Troubleshooting flowCheck of outdoor thermistors When heating operation does not work Check of R.V. coilCheck of power supply Check of outdoor fan motorCheck of current-limiting resistor Check of LEVParts side Electromagnetic noise enters into TV sets or radios Discharge temperature thermistor RT62 Noise filter P.C. board CN3 Outdoor power boardCN2 CN5Removing the cabinet Photo Disassembly InstructionsMUZ-GB50VA Outdoor Unit Operating Procedure Photos Operating Procedure Photos Removing R.V. coilTure thermistor and ambient temperature thermistor Removing outdoor fan motor PhotoRemoving the compressor and 4-way valve Photo Removing the reactorRoHS Parts List RoHS compliant MUZ-GB MUZ-GB50VA Accessory MUZ-GB50