3. Outdoor unit failure mode table
MUZ-GB50VA
The left lamp of | Abnormal point | LED indication | Condition | Correspondence | Indoor/outdoor | ||||||||||
OPERATION INDICATOR | (Outdoor P.C. board) | unit failure mode | |||||||||||||
(Failure mode / protection) | |||||||||||||||
lamp (Indoor unit) | LED 1 | LED 2 |
|
|
|
|
|
| recall function | ||||||
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
OFF | None (Normal) | - | - |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| |||||
Outdoor power system | Lighting | Lighting | When over current protection stop is | • Check the connection |
|
|
|
|
| ||||||
|
|
|
| continuously performed three times | of the compressor |
|
|
|
|
| |||||
|
|
|
| within 1 minute after the compressor | connecting wire. |
|
|
|
|
| |||||
|
|
|
| gets started, or when converter | • Refer to |
|
|
|
|
| |||||
|
|
|
| protection stop or | "How to check |
|
|
|
|
| |||||
|
|
|
| protection stop is continuously | inverter / compressor". |
|
|
|
|
| |||||
|
|
|
| performed three times within 3 | • Check the stop valve. |
|
|
|
|
| |||||
|
|
|
| minutes after |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Discharge temperature | Lighting | Once | When thermistor shorts or opens | • Refer to |
|
|
|
|
| ||||||
| thermistor |
|
| during compressor running. | of outdoor thermistors". |
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Defrost thermistor | Lighting | Once |
|
|
|
|
|
|
|
|
|
|
| |
| Ambient temperature thermistor | Lighting | Twice |
|
|
|
|
|
|
|
|
|
|
| |
| Fin temperature thermistor | Lighting | 3 times |
|
|
|
|
|
|
|
|
|
|
| |
| P.C. board temperature | Lighting | 4 times |
|
|
| • Replace the outdoor |
|
|
|
|
| |||
| thermistor |
|
|
|
|
| electronic control |
|
|
|
|
| |||
|
|
|
|
|
|
| P.C. board. |
|
|
|
|
| |||
| Outdoor heat exchanger | Lighting | 9 times |
|
|
| • Refer to |
|
|
|
|
| |||
| temperature thermistor |
|
|
|
|
| of outdoor thermistors". |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Over current | Once | Goes | When 28A current flow into intelligent | • Reconnect compressor |
|
|
|
|
| ||||||
|
|
| out | power module. | connector. |
|
|
|
|
| |||||
|
|
|
|
|
|
| • Refer to |
|
|
|
|
| |||
|
|
|
|
|
|
| check inverter/ |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
| compressor." |
|
|
|
|
| |||
|
|
|
|
|
|
| • Check the stop valve. |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Discharge temperature | Lighting | Lighting | When discharge temperature exceeds | •Check refrigerant circuit |
|
|
|
|
| ||||||
|
|
|
| 116°C during operation. | and refrigerant amount. |
|
|
|
|
| |||||
|
|
|
| Compressor can restart if discharge | • Refer to |
|
|
|
|
| |||||
|
|
|
| temperature thermistor reads 100: or | of LEV". |
|
|
|
|
| |||||
|
|
|
| less 3 minutes later. |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
High pressure | Lighting | Lighting | When the outdoor heat exchanger | •Check refrigerant circuit |
|
|
|
|
| ||||||
|
|
|
| temperature exceeds 70: | and refrigerant amount. |
|
|
|
|
| |||||
|
|
|
| during cooling or the indoor gas | • Check the stop valve. |
|
|
|
|
| |||||
|
|
|
| pipe temperature exceeds 70: |
|
|
|
|
|
|
|
| |||
|
|
|
| during heating. |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Fin temperature | 3 times | Goes | When the fin temperature exceeds | • Check around outdoor |
|
|
|
|
| ||||||
|
|
| out | 87: during operation. | unit. |
|
|
|
|
| |||||
|
|
|
|
|
|
| • Check outdoor unit air |
|
|
|
|
| |||
|
|
|
|
|
|
| passage. |
|
|
|
|
| |||
|
|
|
|
|
|
| • Refer to |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| ||||
| P.C. board temperature | 4 times | Goes | When the P.C. board temperature | of outdoor fan motor". |
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
| |||||||
|
|
| out | exceeds 70: during operation. |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Outdoor fan motor | Lighting | Lighting | When failure occurs continuously | • Refer to |
|
|
|
|
| ||||||
|
|
|
| three times within 30 seconds after | of outdoor fan motor". |
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
| the fan gets started. |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Nonvolatile memory data | Lighting | 5 times | When nonvolatile memory data | • Replace the outdoor |
|
|
|
|
| ||||||
electronic control |
|
|
|
|
| ||||||||||
|
|
|
| cannot be read properly. |
|
|
|
|
| ||||||
|
|
|
| P.C. board. |
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||
Discharge temperature | Lighting | Lighting | When the frequency of the | •Check refrigerant circuit |
|
|
|
|
| ||||||
|
|
|
| compressor is kept 80Hz or | and refrigerant amount. |
|
|
|
|
| |||||
|
|
|
| more and the discharge | • Refer to |
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
| temperature is kept under 39: | of LEV". |
|
|
|
|
| |||||
|
|
|
| for more than 20 minutes. |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table
18