Mitsubishi Electronics MUZ-GB50VA service manual Refrigerant System Diagram, Unitmm

Page 8

7

REFRIGERANT SYSTEM DIAGRAM

MUZ-GB50VA

OUTDOOR UNIT

Unit:mm

Muffler 4-way valve #100

Refrigerant pipe [12.7

 

 

 

 

 

 

(with heat insulator)

 

 

 

 

 

 

Stop valve

 

 

 

 

 

 

(with service port)

 

 

Outdoor

 

 

Flared connection

Discharge

 

 

 

 

 

 

heat

 

Ambient

 

temperature

Defrost

exchanger

temperature

 

thermistor

 

 

 

thermistor

 

RT62

 

thermistor

 

 

RT65

 

 

 

RT61

 

 

 

 

Compressor

 

 

 

 

 

 

 

Outdoor heat

 

 

 

 

 

exchanger

 

 

 

 

 

 

temperature

 

 

 

 

 

thermistor

 

 

Flared connection

 

 

 

RT68

 

 

Strainer

LEV

 

R.V. coil

 

 

 

Strainer

Refrigerant flow in cooling

Receiver #100

 

#100

OFF

 

 

 

 

ON

Refrigerant flow in heating

Stop valve

Capillary tube

 

 

 

 

 

Refrigerant pipe [6.35

[3.6[2.450

 

 

 

 

 

 

 

 

 

 

(with heat insulator)

 

 

 

 

 

 

MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE

 

 

Refrigerant piping : m

Piping size O.D : mm

Model

 

 

 

Max. length

 

Max. Height difference

 

 

 

 

 

 

 

 

 

 

A

 

B

Gas

Liquid

MUZ-GB50VA

30

 

15

12.7

6.35

 

 

 

 

 

 

Indoor unit

Max. Height

difference

B

Max. length

A

Outdoor unit

ADDITIONAL REFRIGERANT CHARGE (R410A:g)

Model

Outdoor unit

 

 

Refrigerant piping length (one way)

 

 

 

 

 

 

 

 

 

 

precharged

7m

10m

 

15m

20m

 

25m

30m

 

 

 

MUZ-GB50VA

1,500

0

60

 

160

260

 

360

460

 

 

 

 

 

 

 

 

 

 

Calculation : Xg=20g/m (Refrigerant piping length (m)–7)

NOTE : Refrigerant piping exceeding 7m requires additional refrigerant charge according to the calculation.

8

Image 8
Contents R410A Refrigerant OBR01 Contents Revised EDITION-ATechnical Changes MUZ-GA50VA E1SNB130FLDH SNB130FLDH1Specification AccessoriesPart Names and Functions MUZ-GB50VASpecifications and rating conditions of main electric parts Noise Criteria Curves Band OctaveOutlines and Dimensions MUZ-GB50VA Outdoor UnitWiring Diagram Outdoor Unit MUZ-GB50VARefrigerant System Diagram UnitmmCapacity and input curves Performance CurvesIndoor Unit Outdoor Unit Test RUN Operation How to operate fixed-frequency operation MUZ-GB50VACool operation MSZ-GB50VA MUZ-GB50VA Performance Data Cool operation Rated frequency 79HzOutdoor SHC SHF InputOutdoor DB Actuator Control Performance Data Heat operationOutdoor fan motor control R.V. coil controlTroubleshooting Relation between main sensor and actuator MUZ-GB50Failure mode recall function OFFOperational procedure Outdoor unit failure mode table Time flash Communication error Lighting Instruction of troubleshooting IndicatorOperation EmergencyTroubleshooting check table MUZ-GB50VA Operate Lightning Twice Outdoor power systemOnce Lighting Trouble criterion of main parts MUZ-GB50VA RED BLK BLK WHTWHT RED RED ORNHow to check inverter/ compressor Troubleshooting flowCheck of outdoor thermistors When heating operation does not work Check of R.V. coilCheck of power supply Check of outdoor fan motorCheck of current-limiting resistor Check of LEVParts side Electromagnetic noise enters into TV sets or radios Discharge temperature thermistor RT62 Noise filter P.C. board Outdoor power board CN2CN3 CN5Removing the cabinet Photo Disassembly InstructionsMUZ-GB50VA Outdoor Unit Operating Procedure Photos Operating Procedure Photos Removing R.V. coilTure thermistor and ambient temperature thermistor Removing outdoor fan motor PhotoRemoving the compressor and 4-way valve Photo Removing the reactorRoHS Parts List RoHS compliant MUZ-GB MUZ-GB50VA Accessory MUZ-GB50