Mitsubishi Electronics MUZ-GB50VA How to check inverter/ compressor, Troubleshooting flow

Page 24

10-6. Troubleshooting flow

MUZ-GB50VA

A How to check inverter/ compressor

Disconnect the terminal of the compressor. 3 minutes after turning on the power supply, start

EMERGENCY OPERATION.

 

 

 

W • After the outdoor fan starts running, wait for 1 minutes or more before

 

 

 

Measure the voltage between each

 

measuring the voltage.

 

lead wire leading to the compressor.

 

• The output voltage values have the tolerance of i20%.

 

U (BLK) - V (WHT)

 

No

 

V (WHT) - W (RED)

 

 

 

 

 

 

 

 

COOL

HEAT

W (RED) - U (BLK)

 

 

 

 

 

 

 

 

Is voltage output on right table?

 

 

 

 

 

 

 

122V~154V

74V~126V

 

Yes

No

 

 

 

 

 

 

 

(56Hz~71Hz)

(30Hz~58Hz)

 

Is output balanced?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the input voltage to the outdoor electronic No

 

 

 

 

 

 

 

 

 

control P.C. board 370V or more?

 

 

 

Replace the power board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn off power supply of indoor and outdoor unit,

 

and measure the compressor winding resistance No

 

between the compressor terminals.

 

 

 

 

 

 

 

 

 

Is the resistance between each terminal normal?

 

 

 

Yes

 

 

 

 

 

 

 

Replace the

 

 

 

 

 

 

 

 

 

compressor.

 

 

 

 

 

 

 

 

 

 

 

Reconnect the lead wire of compressor, and turn on power supply to indoor and outdoor unit.

3 minutes later, starts EMERGENCY OPERATION.

Clarify the causes by counting time until the inverter stops. 0 to 10 seconds: compressor rare short

10 to 60 seconds: compressor lock

60 seconds to 5minutes: refrigerant circuit defective

5 minutes or more: normal

24

Image 24
Contents R410A Refrigerant OBR01 Contents Revised EDITION-ATechnical Changes MUZ-GA50VA E1SNB130FLDH SNB130FLDH1Specification AccessoriesPart Names and Functions MUZ-GB50VASpecifications and rating conditions of main electric parts Noise Criteria Curves Band OctaveOutlines and Dimensions MUZ-GB50VA Outdoor UnitWiring Diagram Outdoor Unit MUZ-GB50VARefrigerant System Diagram UnitmmPerformance Curves Indoor Unit Outdoor UnitCapacity and input curves Test RUN Operation How to operate fixed-frequency operation MUZ-GB50VACool operation MSZ-GB50VA MUZ-GB50VA Performance Data Cool operation Rated frequency 79HzOutdoor SHC SHF InputOutdoor DB Actuator Control Performance Data Heat operationOutdoor fan motor control R.V. coil controlTroubleshooting Relation between main sensor and actuator MUZ-GB50Failure mode recall function OFFOperational procedure Outdoor unit failure mode table Time flash Communication error Lighting Instruction of troubleshooting IndicatorOperation EmergencyTroubleshooting check table MUZ-GB50VA Operate Lightning Twice Outdoor power systemOnce Lighting Trouble criterion of main parts MUZ-GB50VA RED BLK BLK WHTWHT RED RED ORNHow to check inverter/ compressor Troubleshooting flowCheck of outdoor thermistors When heating operation does not work Check of R.V. coilCheck of power supply Check of outdoor fan motorCheck of current-limiting resistor Check of LEVParts side Electromagnetic noise enters into TV sets or radios Discharge temperature thermistor RT62 Noise filter P.C. board Outdoor power board CN2CN3 CN5Disassembly Instructions MUZ-GB50VA Outdoor Unit Operating Procedure PhotosRemoving the cabinet Photo Operating Procedure Photos Removing R.V. coilTure thermistor and ambient temperature thermistor Removing outdoor fan motor PhotoRemoving the compressor and 4-way valve Photo Removing the reactorRoHS Parts List RoHS compliant MUZ-GB MUZ-GB50VA Accessory MUZ-GB50