Outdoor unit does not operate at all, or stops immediately due to overcurrent.

F Check of current-limiting resistor

When the current-limiting resistor is open, the rush current limiting relay (X64) may not work properly.

Is the resistance of current-limiting resistor (R64A or R64B) on the noise filter P.C. board normal? (Normal resistance : 10' i5%)

Open

Replace the power P.C. board.

Not

Turn ON the power

open

supply and press

 

EMERGENCY

 

OPERATION switch.

Does LED on the outdoor electronic control P.C. board light up?

Yes

Does the rush current limiting relay (X64) work properly?

No

Yes

Replace the noise filter P.C. board or the outdoor electronic control P.C. board.

Replace the outdoor electronic control P.C. board or power P.C. board or the compressor.

No

Replace the noise filter P.C. board.

Check other electric parts in the main circuit together in the case that the current-limiting resistor is defective.

When cooling, heat exchanger of non-operating indoor unit frosts.

When heating, non-operating indoor unit get warm.

G Check of LEV

Turn on power supply to the outdoor unit after checking LEV coil is mounted to the LEV body securely.

Is "click - click" sound heard?

Or, do you feel vibration of the LEV coil with a hand?

No

Disconnect the connector CN795.

Is there normal resistance to LEV coil?

No

Replace the LEV coil.

Yes

Normal

Yes Replace the outdoor electronic control P.C. board.

28

Image 28
Contents R410A Refrigerant OBR01 Contents Revised EDITION-ATechnical Changes MUZ-GA50VA E1SNB130FLDH SNB130FLDH1Specification AccessoriesPart Names and Functions MUZ-GB50VASpecifications and rating conditions of main electric parts Noise Criteria Curves Band OctaveOutlines and Dimensions MUZ-GB50VA Outdoor UnitWiring Diagram Outdoor Unit MUZ-GB50VARefrigerant System Diagram UnitmmIndoor Unit Outdoor Unit Performance CurvesCapacity and input curves Test RUN Operation How to operate fixed-frequency operation MUZ-GB50VACool operation MSZ-GB50VA MUZ-GB50VA Performance Data Cool operation Rated frequency 79HzOutdoor SHC SHF InputOutdoor DB Actuator Control Performance Data Heat operationOutdoor fan motor control R.V. coil controlTroubleshooting Relation between main sensor and actuator MUZ-GB50Failure mode recall function OFFOperational procedure Outdoor unit failure mode table Time flash Communication error Lighting Instruction of troubleshooting IndicatorOperation EmergencyTroubleshooting check table MUZ-GB50VA Operate Lightning Twice Outdoor power systemOnce Lighting Trouble criterion of main parts MUZ-GB50VA RED BLK BLK WHTWHT RED RED ORNHow to check inverter/ compressor Troubleshooting flowCheck of outdoor thermistors When heating operation does not work Check of R.V. coilCheck of power supply Check of outdoor fan motorCheck of current-limiting resistor Check of LEVParts side Electromagnetic noise enters into TV sets or radios Discharge temperature thermistor RT62 Noise filter P.C. board Outdoor power board CN2CN3 CN5MUZ-GB50VA Outdoor Unit Operating Procedure Photos Disassembly InstructionsRemoving the cabinet Photo Operating Procedure Photos Removing R.V. coilTure thermistor and ambient temperature thermistor Removing outdoor fan motor PhotoRemoving the compressor and 4-way valve Photo Removing the reactorRoHS Parts List RoHS compliant MUZ-GB MUZ-GB50VA Accessory MUZ-GB50