Mitsubishi Electronics MUZ-GB50VA service manual Time flash Communication error Lighting

Page 19

MUZ-GB50VA

The left lamp of

Abnormal point

LED indication

Condition

Correspondence

Indoor/outdoor

OPERATION INDICATOR

(Outdoor P.C. board)

unit failure mode

(Failure mode / protection)

lamp (Indoor unit)

LED 1

LED 2

 

 

recall function

 

 

 

 

 

 

 

 

 

 

 

 

11-time flash

Communication error

Lighting

6 times

Communication error occurs

• Check the connecting

 

 

 

 

between P.C. boards

 

 

between the electronic control P.C.

 

 

 

 

 

 

wire between outdoor

 

 

 

 

 

 

 

board and power board for more

 

 

 

 

 

 

 

electronic control

 

 

 

 

 

 

 

than 10 seconds.

 

 

 

 

 

 

 

P.C. board and power

 

 

 

 

 

 

 

When the communication between

 

 

 

 

 

 

 

board.

 

 

 

 

 

 

 

boards protection stop is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

continuously performed twice.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current sensor

Lighting

7 times

When a short or open circuit is

• Replace the power

 

 

 

 

 

 

 

detected in the current sensor

board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

during compressor operating.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current sensor protection stop is

 

 

 

 

 

 

 

 

continuously performed twice.

 

 

 

 

 

Zero cross detecting circuit

5 times

Goes

When zero cross signal cannot be

• Check the connecting

 

 

 

 

 

 

out

detected while the compressor is

wire among electronic

 

 

 

 

 

 

 

 

 

 

 

 

 

operating.

control P.C. board,

 

 

 

 

 

 

 

The protection stop of the zero

noise filter P.C. board

 

 

 

 

 

 

 

and power board.

 

 

 

 

 

 

 

cross detecting circuit is

 

 

 

 

 

 

 

continuously performed 10 times.

 

 

 

 

 

Converter

5 times

Goes

When a failure is detected in the

• Replace the power

 

 

 

 

 

 

out

operation of the converter during

board.

 

 

 

 

 

 

 

operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bus-bar voltage

5 times

Goes

When the bus-bar voltage exceeds

 

 

 

 

 

(1)

 

out

400V or falls to 200V or below

 

 

 

 

 

 

 

 

during compressor operating.

 

 

 

 

 

 

 

 

 

 

 

 

 

Bus-bar voltage

6 times

Goes

When the bus-bar voltage exceeds

 

 

 

 

 

(2)

 

out

400V or falls to 50V or below during

 

 

 

 

 

wEven if this protection stop is

 

 

compressor operating.

 

 

 

 

 

performed continuously three

 

 

 

 

 

 

 

 

times, it does not mean the

 

 

 

 

 

 

 

 

abnormality in outdoor power

 

 

 

 

 

 

 

 

system.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-4.).

19

Image 19
Contents Revised EDITION-A R410A Refrigerant OBR01 ContentsSNB130FLDH1 Technical ChangesMUZ-GA50VA E1 SNB130FLDHMUZ-GB50VA SpecificationAccessories Part Names and FunctionsSpecifications and rating conditions of main electric parts Band Octave Noise Criteria CurvesMUZ-GB50VA Outdoor Unit Outlines and DimensionsOutdoor Unit MUZ-GB50VA Wiring DiagramUnitmm Refrigerant System DiagramIndoor Unit Outdoor Unit Performance CurvesCapacity and input curves MUZ-GB50VA Test RUN Operation How to operate fixed-frequency operationCool operation SHC SHF Input MSZ-GB50VA MUZ-GB50VAPerformance Data Cool operation Rated frequency 79Hz OutdoorOutdoor DB R.V. coil control Actuator ControlPerformance Data Heat operation Outdoor fan motor controlRelation between main sensor and actuator MUZ-GB50 TroubleshootingOFF Failure mode recall functionOperational procedure Outdoor unit failure mode table Time flash Communication error Lighting Emergency Instruction of troubleshootingIndicator OperationOperate Lightning Twice Outdoor power system Troubleshooting check table MUZ-GB50VAOnce Lighting RED ORN Trouble criterion of main parts MUZ-GB50VARED BLK BLK WHT WHT REDTroubleshooting flow How to check inverter/ compressorCheck of outdoor thermistors Check of R.V. coil When heating operation does not workCheck of outdoor fan motor Check of power supplyCheck of LEV Check of current-limiting resistorParts side Electromagnetic noise enters into TV sets or radios Discharge temperature thermistor RT62 Noise filter P.C. board CN5 Outdoor power boardCN2 CN3MUZ-GB50VA Outdoor Unit Operating Procedure Photos Disassembly InstructionsRemoving the cabinet Photo Removing R.V. coil Operating Procedure PhotosRemoving outdoor fan motor Photo Ture thermistor and ambient temperature thermistorRemoving the reactor Removing the compressor and 4-way valve PhotoRoHS Parts List RoHS compliant MUZ-GB MUZ-GB50 MUZ-GB50VA Accessory