Telemetry Option Configuration
Depending on which mode you are using the Orion unit in, you may need to set up other options such as alarm levels.
vThese options are not relevant if you are using the unit as a straight modem.
Analogue Input Setup
Figure 15 - Analogue In | |
For each input, select: |
|
Type: | 20mA input |
| 0 to +5V input |
| 0 to 10V input |
Alarm threshold: | 1 to 1023 - proportion of full scale (0 = never alarm) |
Alarm validation period: | 1 to 255 - time for which condition must persist (in 10ms |
| blocks) |
Alarm condition: | Greater than or less than threshold level |
Digital Input Setup
Figure 16 - Digital In Set-up
1892 1335 - Orion Radio Modem Operating Instructions - v1.3 / Aug 2006 | 19 |