Liebert RAC2-8 manual Delays

Page 15

Section 3: Operation

SECTION 4 — GLOSSARY OF CONTROL FUNCTIONS includes a functional description of each delay.

Set Options Sub-menu (cont’d)

From the Set Units menu, press 4. SHUTDOWN to display the Shutdown on Alarm screen:

SHUTDOWN ON ALARM

01-Y 02-Y 03-Y 04-Y 05-Y 06-Y 07-Y 08-Y 1=YES O=NO E=NEXT

Beginning with unit 01, indicate 1 (Yes) or 0 (No) if the unit should shut down on alarm. When you have selected the shutdown status for the last unit, the RAC2-8 displays the Set Units menu.

When you have configured the delays, from the Set Units menu, press 5 to return to the Set Options Menu.

2. DELAYS

From the Set Options Sub-menu, press 2. DELAYS to display the Set Delays menu:

SET DELAYS MENU

 

1. ALARM

2.HOLD

3.UNIT RESTART

5.RETURN

From the Set Delays menu, press 1. ALARM to configure the Alarm Delay:

ENTER ALARM DELAY <10.0> XX.X MINUTES THEN PUSH ENTER PUSH CLEAR TO RETURN

Enter the desired time for the alarm delay. The default is 10 minutes. Press E to accept the new delay, then press C to return to the Set Delays menu.

From the Set Delays menu, press 2. HOLD to configure the Hold Delay:

ENTER HOLD DELAY <10.0> XX.X MINUTES THEN PUSH ENTER PUSH CLEAR TO RETURN

Enter the desired time for the hold delay. The default is 10 minutes. Press E to accept the new delay, then press C to return to the Set Delays menu.

10 User Manual (9/97)

Image 15
Contents $XWRð&KDQJHRYHUý&RQWUROOHU Table of Contents Table of Figures Unit RAC2-8Page Introduction Page Installation To start up the RAC2-8Operation Page Glossary of Control Functions for more details OperationStatus Sub-menu Sequencing Status Screens cont’dUnits DelayStatus Sub-menu cont’d Set Options Sub-menuSet Options Sub-menu cont’d Function Delays TEMP/HUM Standby PasswordAlarm Sub-menu DAY of Week Set Clock Sub-menuDate TimeUnit 01 Forced on Force OFF Restore Return LOG on TerminalStatus Screen Unit Status Setup Zones/Units OptionsSetup Zones/Units Options cont’d Number of ZONES/NUMBER of Units PER ZoneEmergency Power Units Unit Shutdown on Alarm08 0 no Alarms Review and Alarms Clear Unit LabelsSet Clock Override a Unit Set Modem Options Setup Temp/Humid Options Setup Temp/Humid Options cont’dSet Modem Options cont’d Setup Standby Unit Options Set New Password Display SS Alarm BlockList of Alarms AlarmsAutochangeover Alarm AnnunciationAlarm Communications Alarm DelayAutosequencing Key Clear AlarmsCommon Alarm-Inputs Common Alarm-OutputHold Delay DelayEmergency Power OFF EPO Emergency Power OperationInterval Humidity AlarmsHumidity Lockout Inactive UnitOverride Normal TemperaturePassword Power Failure ModeRunning Units Restart DelayRestore Standby TestingTerminal Temperature AlarmsTemperature Sensitivity Temperature StagingZones Installation TB2 RAC2-8 Dimensional Enclosure Diagram RAC2-8 Component Arrangement RAC2-8 Connection Diagram RAC2-8 Switch and Jumper Settings