Section 1: Introduction
See SECTION 5 —
INSTALLATION for special instructions when using the
The Liebert
The most important control functions are Autochangeover, Autosequencing, and Standby Testing. Each unit can be assigned a Running or Standby status.
Autochangeover turns on a Standby unit if a Running unit in the same zone has an alarm. The Running unit (with alarm) will be turned off if that control option is selected. Each unit will return to its previous status when the alarm is manually cleared.
Autosequencing balances unit
Standby Testing turns on Standby units at programmed intervals to test their operation. Note that Autosequencing and Standby Testing cannot both be selected at the same time.
Other control functions include Manual Override, Emergency Power Operation, Power Failure Mode, Password, and Programmable Delays. Refer to SECTION 4 — GLOSSARY OF CONTROL FUNCTIONS for more details.
System outputs include Humidity Lockout Relay, Optional Control Lockout Relay, and Common Alarm. Communication ports are