Section 4: Glossary of Control Functions

Alarm Annunciation

The RAC2-8 provides the following alarm annunciation mechanisms:

Audible indication (horn).

A lighted ‘Alarms Present’ front panel indicator.

Activation of the Common Alarm relay output.

Display of alarm messages on the front panel LCD.

Warnings activate the ‘Alarms Present’ indicator and a message on the

LCD, but no audible alarm or Common Alarm.

When an alarm occurs the LCD immediately displays a message (unless an Override screen is being displayed). Pushing the Alarms Present/Silence pushbutton acknowledges the alarm and silences the alarm horn. The alarm message is displayed until the alarm is acknowledged (silenced). After the alarm is silenced, normal status display scanning resumes.

Any alarms present are displayed during scanning of normal display pages. If more than 4 alarms are present additional pages of alarms are created as necessary. Up to 20 alarms are stored in a First-In-First-Out sequence.

Alarm Communications

EIA-232 Terminal Port—Transmits Alarm with time stamp.

EIA-232 Modem Port—Dials out alarm.

Both EIA-232 ports are compatible with SS-AMS (SiteScan Alarm

Management System).

EIA-422 (proprietary) to SiteScan monitoring system.

Alarm Delay

Delay before an alarm is annunciated (false alarm delay). This delay begins on the occurrence of an alarm condition in a unit. If the alarm condition has not corrected itself by the end of the delay period, the alarm is annunciated and an autochangeover to the standby unit Occurs. If a unit is programmed to shutdown on an alarm, the unit shuts down when the alarm is annunciated. The Alarm Delay timer counts both up and down and an active Alarm Delay timer can be monitored at the display. The Alarm Delay is user selectable from the display. Range - 0.1 to 60 minutes, in increments of 0.1 minute (6 sec).

Autochangeover

If an alarm occurs in a Running unit, a Standby unit in the same zone is started. The Running unit in alarm is stopped if it is programmed to shut down, and the Standby unit is started. The Standby unit changes status to become the Running unit and remains running until the Alarm is manually cleared. Messages are written to the terminal to record the status changes. Status screens show new unit status at the local display. After a changeover, the newly started unit may briefly have a High Temp or other alarm. A user selectable Hold Delay begins when any

28 User Manual (9/97)

Image 33
Contents $XWRð&KDQJHRYHUý&RQWUROOHU Table of Contents Table of Figures Unit RAC2-8Page Introduction Page Installation To start up the RAC2-8Operation Page Glossary of Control Functions for more details OperationStatus Sub-menu Sequencing Status Screens cont’dUnits DelayStatus Sub-menu cont’d Set Options Sub-menuSet Options Sub-menu cont’d Function Delays TEMP/HUM Standby PasswordAlarm Sub-menu Date Set Clock Sub-menuTime DAY of WeekUnit 01 Forced on Force OFF Restore Return LOG on TerminalStatus Screen Setup Zones/Units Options cont’d Setup Zones/Units OptionsNumber of ZONES/NUMBER of Units PER Zone Unit StatusEmergency Power Units Unit Shutdown on Alarm08 0 no Alarms Review and Alarms Clear Unit LabelsSet Clock Override a Unit Set Modem Options Setup Temp/Humid Options Setup Temp/Humid Options cont’dSet Modem Options cont’d Setup Standby Unit Options Set New Password Display SS Alarm BlockList of Alarms AlarmsAlarm Communications Alarm AnnunciationAlarm Delay AutochangeoverAutosequencing Common Alarm-Inputs Clear AlarmsCommon Alarm-Output KeyEmergency Power OFF EPO DelayEmergency Power Operation Hold DelayHumidity Lockout Humidity AlarmsInactive Unit IntervalPassword Normal TemperaturePower Failure Mode OverrideRestore Restart DelayStandby Testing Running UnitsTemperature Sensitivity Temperature AlarmsTemperature Staging TerminalZones Installation TB2 RAC2-8 Dimensional Enclosure Diagram RAC2-8 Component Arrangement RAC2-8 Connection Diagram RAC2-8 Switch and Jumper Settings