Liebert RAC2-8 manual Terminal, LOG on

Page 21

Section 3: Operation

Terminal

Main Menu

Main Menu (cont’d)

When you make a program selection from the terminal, the screen is displayed again with the new value(s).

A local terminal can be connected directly by an EIA-232 communication cable to the RAC2-8, or a remote terminal can be connected through modems. All of the status information and control functions available at the RAC2-8 local display are available from the terminal. An additional function available at the terminal is Set Modem.

The terminal also displays a status message with time and date stamp whenever a unit changes status (OFF or ON). These status messages will be printed if a printer (instead of a terminal) is connected to the EIA-232 port. Once each 24 hours (at midnight) the terminal checks its ability to communicate with the RAC2-8 and writes a Comm Check message.

A terminal connected to an active RAC2-8 displays alarm and status messages when they occur. The prompt then asks the operator to press <space>, <S>, or <A>.

07-15-96

12:14:12

On UNIT

03

FORCED

ON

07-15-96

12:14:19

On UNIT

63

RESTORED Menu

Exited - Press <space> to Enter

Menu, <S>

for

Status, <A> for Alarms

 

 

 

 

 

 

 

 

 

 

<space> displays Main Menu after a password is entered. <S> displays present status.

<A> displays a list of alarms (up to 20).

LOG ON:

is the prompt to enter a password. This prompt is also displayed when the system is accessed through a modem.

The Main Menu is displayed on a terminal as shown below:

RAC2-8 MAIN MENU

1.Status

2.Setup Zones/Units Options Menu

3.Alarms Review

4.Alarms Clear

5.Set Clock

6.Override a Unit

7.Set Modem Options

8.Setup Temp/Humid Options Menu

9.Setup Standby Unit Options

A. Display SS Alarm Block

P. Set New Password

X. Exit

Each Main Menu item has a corresponding screen that lets you configure the system parameters. Each screen is shown in the following sections.

16 User Manual (9/97)

Image 21
Contents $XWRð&KDQJHRYHUý&RQWUROOHU Table of Contents Table of Figures Unit RAC2-8Page Introduction Page Installation To start up the RAC2-8Operation Page Glossary of Control Functions for more details OperationStatus Sub-menu Sequencing Status Screens cont’dUnits DelayStatus Sub-menu cont’d Set Options Sub-menuSet Options Sub-menu cont’d Function Delays TEMP/HUM Standby PasswordAlarm Sub-menu Date Set Clock Sub-menuTime DAY of WeekUnit 01 Forced on Force OFF Restore Return LOG on TerminalStatus Screen Setup Zones/Units Options cont’d Setup Zones/Units OptionsNumber of ZONES/NUMBER of Units PER Zone Unit StatusEmergency Power Units Unit Shutdown on Alarm08 0 no Alarms Review and Alarms Clear Unit LabelsSet Clock Override a Unit Set Modem Options Setup Temp/Humid Options Setup Temp/Humid Options cont’dSet Modem Options cont’d Setup Standby Unit Options Set New Password Display SS Alarm BlockList of Alarms AlarmsAlarm Communications Alarm AnnunciationAlarm Delay AutochangeoverAutosequencing Common Alarm-Inputs Clear AlarmsCommon Alarm-Output KeyEmergency Power OFF EPO DelayEmergency Power Operation Hold DelayHumidity Lockout Humidity AlarmsInactive Unit IntervalPassword Normal TemperaturePower Failure Mode OverrideRestore Restart DelayStandby Testing Running UnitsTemperature Sensitivity Temperature AlarmsTemperature Staging TerminalZones Installation TB2 RAC2-8 Dimensional Enclosure Diagram RAC2-8 Component Arrangement RAC2-8 Connection Diagram RAC2-8 Switch and Jumper Settings