Liebert RAC2-8 Delay, Emergency Power OFF EPO, Emergency Power Operation, Force on, Force OFF

Page 36

Section 4: Glossary of Control Functions

Delay

Refer to Alarm Delay, Hold Delay, and Restart Delay.

E key

The Enter key <E> at the local control panel serves two functions:

Causes data entered in setup display pages to be stored in the RAC2-8 permanent memory.

Causes selection of next unit on multi-unit displays.

Emergency Power OFF (EPO)

EPO can be initiated from a remote switch wired to the RAC2-8. This user input causes all units to be turned OFF immediately. RAC2-8 control power is maintained. This Normally Closed contact must be Open for 0.5 seconds for the input signal to be detected.

After the input signal is removed (closed), the alarm must be manually cleared. Then all units programmed to be Running are started sequentially, separated by the Restart Delay.

Emergency Power Operation

This user input activates a separate mode for operating on an emergency power source (a UPS system or standby generator) which may have limited capacity. Only units selected to be ON during this mode are running. Select ON units for this mode from the display. Autochangeover, Autosequencing, and Standby Testing are inactive during this mode to reduce power load. Units that are OFF during this mode will remain OFF until normal mode is resumed. This mode also energizes both lockout relays, Humidity and (Optional) Control.

Force ON

To manually turn a unit ON from the display. Refer to Override.

Force OFF

To manually turn a unit OFF from the display. Refer to Override.

Hold Delay

Delay after turn ON of a Standby unit to allow the newly started unit to gain control. During the Hold Delay alarms from this unit and all other units are ignored. This delay begins when any changeover Occurs, either in Autosequence or Standby Test mode. An active Hold Delay can be monitored at the display. At the end of the Hold Delay, the Alarm Delay time begins. The Hold Delay is user selectable from the display.

Range—0.1 to 60 minutes, selectable in increments of 0.1 minute (6 seconds).

Liebert RAC2-8 31

Image 36
Contents $XWRð&KDQJHRYHUý&RQWUROOHU Table of Contents Table of Figures RAC2-8 UnitPage Introduction Page Installation To start up the RAC2-8Operation Page Operation Glossary of Control Functions for more detailsSequencing Status Screens cont’d Status Sub-menuDelay UnitsStatus Sub-menu cont’d Set Options Sub-menuSet Options Sub-menu cont’d Function Delays TEMP/HUM Password StandbyAlarm Sub-menu Set Clock Sub-menu DateTime DAY of WeekUnit 01 Forced on Force OFF Restore Return Terminal LOG onStatus Screen Setup Zones/Units Options Setup Zones/Units Options cont’dNumber of ZONES/NUMBER of Units PER Zone Unit StatusUnit Shutdown on Alarm Emergency Power Units08 0 no Alarms Review and Alarms Clear Unit LabelsSet Clock Override a Unit Set Modem Options Setup Temp/Humid Options Setup Temp/Humid Options cont’dSet Modem Options cont’d Setup Standby Unit Options Display SS Alarm Block Set New PasswordAlarms List of AlarmsAlarm Annunciation Alarm CommunicationsAlarm Delay AutochangeoverAutosequencing Clear Alarms Common Alarm-InputsCommon Alarm-Output KeyDelay Emergency Power OFF EPOEmergency Power Operation Hold DelayHumidity Alarms Humidity LockoutInactive Unit IntervalNormal Temperature PasswordPower Failure Mode OverrideRestart Delay RestoreStandby Testing Running UnitsTemperature Alarms Temperature SensitivityTemperature Staging TerminalZones Installation TB2 RAC2-8 Dimensional Enclosure Diagram RAC2-8 Component Arrangement RAC2-8 Connection Diagram RAC2-8 Switch and Jumper Settings