Liebert RAC2-8 Setup Zones/Units Options, Number of ZONES/NUMBER of Units PER Zone, Unit Status

Page 23

Section 3: Operation

Setup Zones/Units Options

Press 2 from the Main Menu to display the Set Options menu. The following screens show the terminal display that enables you to configure the Options menu items.

NUMBER OF ZONES/NUMBER OF UNITS PER ZONE

RAC2-8 MAIN MENU

SET OPTIONS MENU

1.Set Number of Zones

2.Set Number of Units per Zone

3.Set Unit Status

4.Set Emergency Power Units

5.Set Unit Shutdown on Alarm

6.Set Unit Labels

7.Set Alarm Delay

8.Set Hold Delay

9.Set Restart Delay

<ESC> TO EXIT

CURRENT NUMBER OF ZONES = 1

ENTER NEW NUMBER (1-4) <ESC to quit> >2

CURRENT NUMBER OF ZONES = 2

ENTER NEW NUMBER (1-4) <ESC to quit> >

SET OPTIONS MENU

** SET NUMBER OF UNITS PER ZONE ** ZONE 1 = 4 UNITS

ZONE 2 = 0 UNITS

ZONE 3 = UNPROGRAMMED

ZONE 4 = UNPROGRAMMED

ENTER ZONE (1 - 2) <ESC to quit> >2 ZONE 2 has 0 UNITS

ENTER NEW NUMBER (2-8) <ESC to quit> >2

** SET NUMBER OF UNITS PER ZONE ** ZONE 1 = 4 UNITS

ZONE 2 = 2 UNITS

ZONE 3 = UNPROGRAMMED

ZONE 4 = UNPROGRAMMED

ENTER ZONE (1 - 2) <ESC to quit> >

SET OPTIONS MENU

Setup Zones/Units Options (cont’d)

Configure the number of zones and number of units as desired.

UNIT STATUS

SET OPTIONS

MENU

 

** SET UNIT

STATUS **

 

UNIT

LABEL ZONE

STATUS

-----------------------------------------------

1

01

1

RUNNING

 

 

 

 

18 User Manual (9/97)

Image 23
Contents $XWRð&KDQJHRYHUý&RQWUROOHU Table of Contents Table of Figures Unit RAC2-8Page Introduction Page Operation InstallationTo start up the RAC2-8 Page Glossary of Control Functions for more details OperationStatus Sub-menu Sequencing Status Screens cont’dUnits DelaySet Options Sub-menu cont’d Status Sub-menu cont’dSet Options Sub-menu Function Delays TEMP/HUM Standby PasswordAlarm Sub-menu DAY of Week Set Clock Sub-menuDate TimeUnit 01 Forced on Force OFF Restore Return LOG on TerminalStatus Screen Unit Status Setup Zones/Units OptionsSetup Zones/Units Options cont’d Number of ZONES/NUMBER of Units PER ZoneEmergency Power Units Unit Shutdown on Alarm08 0 no Set Clock Alarms Review and Alarms ClearUnit Labels Override a Unit Set Modem Options Set Modem Options cont’d Setup Temp/Humid OptionsSetup Temp/Humid Options cont’d Setup Standby Unit Options Set New Password Display SS Alarm BlockList of Alarms AlarmsAutochangeover Alarm AnnunciationAlarm Communications Alarm DelayAutosequencing Key Clear AlarmsCommon Alarm-Inputs Common Alarm-OutputHold Delay DelayEmergency Power OFF EPO Emergency Power OperationInterval Humidity AlarmsHumidity Lockout Inactive UnitOverride Normal TemperaturePassword Power Failure ModeRunning Units Restart DelayRestore Standby TestingTerminal Temperature AlarmsTemperature Sensitivity Temperature StagingZones Installation TB2 RAC2-8 Dimensional Enclosure Diagram RAC2-8 Component Arrangement RAC2-8 Connection Diagram RAC2-8 Switch and Jumper Settings